2019-05-08 13:11:461ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040464
 5/8/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGYGAUGE COMPLIANCE SUBMITTAL MUST BE
 CERTIFIED ON PAGE 4 WITH ELECTRONIC SEALS AND
 SIGNATURES BY THE DESIGN PROFESSIONALS OF RECORD-
 SECTION C103.1.1 FBC EC.
  
 2) THE SUBMITTED TRACE HEAT LOAD CALCULATIONS ARE NOT
 IN COMPLIANCE WITH SECTIONS C407.5.2.2 & C407.5.2.2 FBC
 EC BECAUSE ZONES HAVE NOT BEEN DEFINED. PLEASE REVIEW
 THE CODE SECTIONS PRINTED BELOW.
  
 C407.5.2.2 HVAC ZONES NOT DESIGNED. WHERE HVAC ZONES
 HAVE NOT YET BEEN DESIGNED, THERMAL BLOCKS SHALL BE
 DEFINED BASED ON SIMILAR INTERNAL LOAD DENSITIES,
 OCCUPANCY, LIGHTING, THERMAL AND TEMPERATURE SCHEDULES,
 AND IN COMBINATION WITH THE FOLLOWING GUIDELINES:
 1.SEPARATE THERMAL BLOCKS SHALL BE ASSUMED FOR INTERIOR
 AND PERIMETER SPACES. INTERIOR SPACES SHALL BE THOSE
 LOCATED MORE THAN 15 FEET (4572 MM) FROM AN EXTERIOR
 WALL. PERIMETER SPACES SHALL BE THOSE LOCATED CLOSER
 THAN 15 FEET (4572 MM) FROM AN EXTERIOR WALL.
 2.SEPARATE THERMAL BLOCKS SHALL BE ASSUMED FOR SPACES
 ADJACENT TO GLAZED EXTERIOR WALLS: A SEPARATE ZONE
 SHALL BE PROVIDED FOR EACH ORIENTATION, EXCEPT
 ORIENTATIONS THAT DIFFER BY NOT MORE THAN 45 DEGREES
 (0.79 RAD) SHALL BE PERMITTED TO BE CONSIDERED TO BE
 THE SAME ORIENTATION. EACH ZONE SHALL INCLUDE FLOOR
 AREA THAT IS 15 FEET (4572 MM) OR LESS FROM A GLAZED
 PERIMETER WALL, EXCEPT THAT FLOOR AREA WITHIN 15 FEET
 (4572 MM) OF GLAZED PERIMETER WALLS HAVING MORE THAN
 ONE ORIENTATION SHALL BE DIVIDED PROPORTIONATELY
 BETWEEN ZONES.
 3.SEPARATE THERMAL BLOCKS SHALL BE ASSUMED FOR SPACES
 HAVING FLOORS THAT ARE IN CONTACT WITH THE GROUND OR
 EXPOSED TO AMBIENT CONDITIONS FROM ZONES THAT DO NOT
 SHARE THESE FEATURES.
 4.SEPARATE THERMAL BLOCKS SHALL BE ASSUMED FOR SPACES
 HAVING EXTERIOR CEILING OR ROOF ASSEMBLIES FROM ZONES
 THAT DO NOT SHARE THESE FEATURES.
  
 C407.5.2.3MULTIFAMILY RESIDENTIAL BUILDINGS.
 RESIDENTIAL SPACES SHALL BE MODELED USING ONE THERMAL
 BLOCK PER SPACE EXCEPT THAT THOSE FACING THE SAME
 ORIENTATIONS ARE PERMITTED TO BE COMBINED INTO ONE
 THERMAL BLOCK. CORNER UNITS AND UNITS WITH ROOF OR
 FLOOR LOADS SHALL ONLY BE COMBINED WITH UNITS SHARING
 THESE FEATURES.
  
 3) SHEET M2.1.1: PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR THE STORAGE AND DOMESTIC PUMP ROOM AND
 INDICATE THE SEQUENCE OF OPERATION FOR THE FANS- SEE
 TABLE 403.3.1.1 AND 501.4 FBC M. A) SHOW THE REQUIRED
 CLEARANCE DISTANCES FOR THE EXHAUST OUTLETS TO OPERABLE
 AND MECHANICAL AIR INTAKES, AND FROM GRADE- SECTION
 501.3.1 FBC M.
  
 4) M5.1.1: PLEASE CORRECT THE FBC MINIMUM VENTILATION
 CALCULATIONS AND REMOVE OR CORRECT THE NOTES SPECIFYING
 RATES BASED ON THE TABLES IN THE FBC R, THE FBC R CODE
 IS APPLICABLE ONLY FOR SINGLE FAMILY HOMES, DUPLEXES,
 AND TOWNHOUSES. REFER TO SECTION 403.3.2.1 FBC M COPIED
 BELOW, AND INDICATE COMPLIANCE:
  
 403.3.2.1 OUTDOOR AIR FOR DWELLING UNITS.
  
 AN OUTDOOR AIR VENTILATION SYSTEM CONSISTING OF A
 MECHANICAL EXHAUST SYSTEM, SUPPLY SYSTEM OR COMBINATION
 THEREOF SHALL BE INSTALLED FOR EACH DWELLING UNIT.
 LOCAL EXHAUST OR SUPPLY SYSTEMS, INCLUDING OUTDOOR AIR
 DUCTS CONNECTED TO THE RETURN SIDE OF AN AIR HANDLER,
 ARE PERMITTED TO SERVE AS SUCH A SYSTEM. THE OUTDOOR
 AIR VENTILATION SYSTEM SHALL BE DESIGNED TO PROVIDE THE
 REQUIRED RATE OF OUTDOOR AIR CONTINUOUSLY DURING THE
 PERIOD THAT THE BUILDING IS OCCUPIED. THE MINIMUM
 CONTINUOUS OUTDOOR AIRFLOW RATE SHALL BE DETERMINED IN
 ACCORDANCE WITH EQUATION 4-9.
  
 (EQUATION 4-9)
 WHERE:
  
 QOA = OUTDOOR AIRFLOW RATE, CFM
  
 AFLOOR = FLOOR AREA, FT2
  
 NBR = NUMBER OF BEDROOMS; NOT TO BE LESS THAN ONE
  
 EXCEPTION: THE OUTDOOR AIR VENTILATION SYSTEM IS NOT
 REQUIRED TO OPERATE CONTINUOUSLY WHERE THE SYSTEM HAS
 CONTROLS THAT ENABLE OPERATION
 FOR NOT LESS THAN 1 HOUR OF EACH 4-HOUR PERIOD. THE
 AVERAGE OUTDOOR AIR FLOW RATE OVER THE 4-HOUR PERIOD
 SHALL BE NOT LESS THAN THAT PRESCRIBED BY EQUATION 4-9.
  
 5) SHEETS M2.4.1, M2.4.2, M2.4.3, M2.4.4, M2.4.5 &
 M7.4.2: THE PLANS DO NOT INDICATE HOW AIR IN THE
 CORRIDORS IS BEING RETURNED TO RTU-OA. PLEASE NOTE THAT
 CORRIDORS SHALL NOT SERVE AS RETURN DUCTS- SECTION
 601.2 FBC M
  
 6) SHEETS M4.4.1, M4.4.2, M4.4.3, M4.4.4, M4.4.5, &
 M4.4.6: LOCAL EXHAUST SYSTEMS ARE REQUIRED FOR THE
 KITCHENS AT A RATE OF 100 CFMS INTERMITTENT OR 25 CFMS
 CONTINUOUS. INDICATE HOW COMPLIANCE WILL BE MET.
  
 7) A4.4.10, M4.4.1, M4.4.2, M4.4.3, M4.4.4, M4.4.5, &
 M4.4.6: THE CITY OF WPB BUILDING DEPARTMENT REQUIRES
 EITHER THE DESIGN PROFESSIONAL OF RECORD OR THE
 INTUMESCENT PAINT MANUFACTURER TO CERTIFY THE
 APPLICATION OF THE PAINT ON THE INTERIOR SIDES OF THE
 AC CLOSET DOORS- SECTION 107.2.1 WPB. FINAL MECHANICAL
 APPROVAL IS CONTINGENT ON RECEIPT OF A SIGNED AND
 SEALED LETTER OR REPORT BY THE DESIGN PROFESSIONAL OF
 RECORD, OR A MANUFACTURER'S CERTIFICATION LETTER WITH
 AN APPROVAL STAMP BY THE DESIGN PROFESSIONAL. PLEASE
 PLACE NOTES ON THE PLANS ACCORDINGLY.
  
 8) M4.4.1, M4.4.2, M4.4.3, M4.4.4, M4.4.5, & M4.4.6:
 SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CLOTHES
 DRYERS- SECTION 504.1 FBC M. PLEASE NOTE THAT DRYER
 EXHAUST DUCTS SHALL NOT RUN THROUGH ABOVE CEILING
 PLENUM SPACES- SECTION 504.4 FBC M.
  
 9) M4.4.6: THE RETURN GRILL AT THE MASTER BEDROOM IS
 UNDERSIZED PER SECTION 601.6(2) AND 601.6(3) FBC M. THE
 RETURN MUST BE SIZED LARGE ENOUGH TO RETURN ALL AIR
 FROM THE SUITE AT 50 SQ. INCHES PER 100 CFMS OF SUPPLY
 AIR.
  
 10) M7.4.2- AC CLOSET DETAIL: INDICATE THEY TYPE AND
 SIZE OF CONDENSATE PIPING FOR THE AIR HANDLER- SECTIONS
 307.2.1 AND 602.2.1 FBC M.
  
 11) M2.4.6 & M7.4.2: PROVIDE COMPLETE WIND LOAD
 ENGIMNEERING FOR ATTACHEMNT OF THE RTU AND CURB, AND
 EXTERIOR DUXCTWORK PO THE ROOF STRUCTURE- SECTION
 301.15 FBC M.
  
 12) FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S
 ARE REQUIRED FOR THE ROOFTOP CONDENSER STANDS AND
 EXHAUST AND O/A INLET LOUVERS. THESE MAY BE SUBMITTED
 NOW WITH THE ENGINEER OF RECORD'S SHOP DRAWING STAMP OF
 APPROVAL, OR MAY BE DEFERRED SUBMITTALS- SEE SECTION
 107.3.4.1 WPB. PLEASE NOTE THAT THE O/A LOUVERS SHALL
 BE AMCA 550 RATED PER SECTION 401.5 FBC M.
  
 13) CLARIFY IF THERE WILL BE AN ELEVATOR MACHINERY OR
 CONTROL ROOM AND SHOW THE LOCATION IF APPLICABLE-
 SECTION 3005.1. PLEASE NOTE THAT ELEVATOR MACHINE OR
 CONTROLS ROOMS REQUIRE INDEPENDENT VENTILATION SYSTEMS-
 SECTION 3005.2. FBC B.
  
 14) CLARIFY IF THE HOISTWAY WILL BE VENTED AND PROVIDE
 DETAILS- LOCATION OF VENT, TYPE AND SIZE OF VENT AND
 DAMPER ETC. PLEASE NOTE THAT PLUMBING AND MECHANICAL
 SYSTEMS SHALL NOT BE LOCATED IN THE HOISTWAY ENCLOSURE-
 SECTION 3002.9 FBC B.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER