| 2019-05-08 13:11:46 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19040464 |
| | 5/8/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ENERGYGAUGE COMPLIANCE SUBMITTAL MUST BE |
| | CERTIFIED ON PAGE 4 WITH ELECTRONIC SEALS AND |
| | SIGNATURES BY THE DESIGN PROFESSIONALS OF RECORD- |
| | SECTION C103.1.1 FBC EC. |
| | |
| | 2) THE SUBMITTED TRACE HEAT LOAD CALCULATIONS ARE NOT |
| | IN COMPLIANCE WITH SECTIONS C407.5.2.2 & C407.5.2.2 FBC |
| | EC BECAUSE ZONES HAVE NOT BEEN DEFINED. PLEASE REVIEW |
| | THE CODE SECTIONS PRINTED BELOW. |
| | |
| | C407.5.2.2 HVAC ZONES NOT DESIGNED. WHERE HVAC ZONES |
| | HAVE NOT YET BEEN DESIGNED, THERMAL BLOCKS SHALL BE |
| | DEFINED BASED ON SIMILAR INTERNAL LOAD DENSITIES, |
| | OCCUPANCY, LIGHTING, THERMAL AND TEMPERATURE SCHEDULES, |
| | AND IN COMBINATION WITH THE FOLLOWING GUIDELINES: |
| | 1.SEPARATE THERMAL BLOCKS SHALL BE ASSUMED FOR INTERIOR |
| | AND PERIMETER SPACES. INTERIOR SPACES SHALL BE THOSE |
| | LOCATED MORE THAN 15 FEET (4572 MM) FROM AN EXTERIOR |
| | WALL. PERIMETER SPACES SHALL BE THOSE LOCATED CLOSER |
| | THAN 15 FEET (4572 MM) FROM AN EXTERIOR WALL. |
| | 2.SEPARATE THERMAL BLOCKS SHALL BE ASSUMED FOR SPACES |
| | ADJACENT TO GLAZED EXTERIOR WALLS: A SEPARATE ZONE |
| | SHALL BE PROVIDED FOR EACH ORIENTATION, EXCEPT |
| | ORIENTATIONS THAT DIFFER BY NOT MORE THAN 45 DEGREES |
| | (0.79 RAD) SHALL BE PERMITTED TO BE CONSIDERED TO BE |
| | THE SAME ORIENTATION. EACH ZONE SHALL INCLUDE FLOOR |
| | AREA THAT IS 15 FEET (4572 MM) OR LESS FROM A GLAZED |
| | PERIMETER WALL, EXCEPT THAT FLOOR AREA WITHIN 15 FEET |
| | (4572 MM) OF GLAZED PERIMETER WALLS HAVING MORE THAN |
| | ONE ORIENTATION SHALL BE DIVIDED PROPORTIONATELY |
| | BETWEEN ZONES. |
| | 3.SEPARATE THERMAL BLOCKS SHALL BE ASSUMED FOR SPACES |
| | HAVING FLOORS THAT ARE IN CONTACT WITH THE GROUND OR |
| | EXPOSED TO AMBIENT CONDITIONS FROM ZONES THAT DO NOT |
| | SHARE THESE FEATURES. |
| | 4.SEPARATE THERMAL BLOCKS SHALL BE ASSUMED FOR SPACES |
| | HAVING EXTERIOR CEILING OR ROOF ASSEMBLIES FROM ZONES |
| | THAT DO NOT SHARE THESE FEATURES. |
| | |
| | C407.5.2.3MULTIFAMILY RESIDENTIAL BUILDINGS. |
| | RESIDENTIAL SPACES SHALL BE MODELED USING ONE THERMAL |
| | BLOCK PER SPACE EXCEPT THAT THOSE FACING THE SAME |
| | ORIENTATIONS ARE PERMITTED TO BE COMBINED INTO ONE |
| | THERMAL BLOCK. CORNER UNITS AND UNITS WITH ROOF OR |
| | FLOOR LOADS SHALL ONLY BE COMBINED WITH UNITS SHARING |
| | THESE FEATURES. |
| | |
| | 3) SHEET M2.1.1: PROVIDE EXHAUST VENTILATION |
| | CALCULATIONS FOR THE STORAGE AND DOMESTIC PUMP ROOM AND |
| | INDICATE THE SEQUENCE OF OPERATION FOR THE FANS- SEE |
| | TABLE 403.3.1.1 AND 501.4 FBC M. A) SHOW THE REQUIRED |
| | CLEARANCE DISTANCES FOR THE EXHAUST OUTLETS TO OPERABLE |
| | AND MECHANICAL AIR INTAKES, AND FROM GRADE- SECTION |
| | 501.3.1 FBC M. |
| | |
| | 4) M5.1.1: PLEASE CORRECT THE FBC MINIMUM VENTILATION |
| | CALCULATIONS AND REMOVE OR CORRECT THE NOTES SPECIFYING |
| | RATES BASED ON THE TABLES IN THE FBC R, THE FBC R CODE |
| | IS APPLICABLE ONLY FOR SINGLE FAMILY HOMES, DUPLEXES, |
| | AND TOWNHOUSES. REFER TO SECTION 403.3.2.1 FBC M COPIED |
| | BELOW, AND INDICATE COMPLIANCE: |
| | |
| | 403.3.2.1 OUTDOOR AIR FOR DWELLING UNITS. |
| | |
| | AN OUTDOOR AIR VENTILATION SYSTEM CONSISTING OF A |
| | MECHANICAL EXHAUST SYSTEM, SUPPLY SYSTEM OR COMBINATION |
| | THEREOF SHALL BE INSTALLED FOR EACH DWELLING UNIT. |
| | LOCAL EXHAUST OR SUPPLY SYSTEMS, INCLUDING OUTDOOR AIR |
| | DUCTS CONNECTED TO THE RETURN SIDE OF AN AIR HANDLER, |
| | ARE PERMITTED TO SERVE AS SUCH A SYSTEM. THE OUTDOOR |
| | AIR VENTILATION SYSTEM SHALL BE DESIGNED TO PROVIDE THE |
| | REQUIRED RATE OF OUTDOOR AIR CONTINUOUSLY DURING THE |
| | PERIOD THAT THE BUILDING IS OCCUPIED. THE MINIMUM |
| | CONTINUOUS OUTDOOR AIRFLOW RATE SHALL BE DETERMINED IN |
| | ACCORDANCE WITH EQUATION 4-9. |
| | |
| | (EQUATION 4-9) |
| | WHERE: |
| | |
| | QOA = OUTDOOR AIRFLOW RATE, CFM |
| | |
| | AFLOOR = FLOOR AREA, FT2 |
| | |
| | NBR = NUMBER OF BEDROOMS; NOT TO BE LESS THAN ONE |
| | |
| | EXCEPTION: THE OUTDOOR AIR VENTILATION SYSTEM IS NOT |
| | REQUIRED TO OPERATE CONTINUOUSLY WHERE THE SYSTEM HAS |
| | CONTROLS THAT ENABLE OPERATION |
| | FOR NOT LESS THAN 1 HOUR OF EACH 4-HOUR PERIOD. THE |
| | AVERAGE OUTDOOR AIR FLOW RATE OVER THE 4-HOUR PERIOD |
| | SHALL BE NOT LESS THAN THAT PRESCRIBED BY EQUATION 4-9. |
| | |
| | 5) SHEETS M2.4.1, M2.4.2, M2.4.3, M2.4.4, M2.4.5 & |
| | M7.4.2: THE PLANS DO NOT INDICATE HOW AIR IN THE |
| | CORRIDORS IS BEING RETURNED TO RTU-OA. PLEASE NOTE THAT |
| | CORRIDORS SHALL NOT SERVE AS RETURN DUCTS- SECTION |
| | 601.2 FBC M |
| | |
| | 6) SHEETS M4.4.1, M4.4.2, M4.4.3, M4.4.4, M4.4.5, & |
| | M4.4.6: LOCAL EXHAUST SYSTEMS ARE REQUIRED FOR THE |
| | KITCHENS AT A RATE OF 100 CFMS INTERMITTENT OR 25 CFMS |
| | CONTINUOUS. INDICATE HOW COMPLIANCE WILL BE MET. |
| | |
| | 7) A4.4.10, M4.4.1, M4.4.2, M4.4.3, M4.4.4, M4.4.5, & |
| | M4.4.6: THE CITY OF WPB BUILDING DEPARTMENT REQUIRES |
| | EITHER THE DESIGN PROFESSIONAL OF RECORD OR THE |
| | INTUMESCENT PAINT MANUFACTURER TO CERTIFY THE |
| | APPLICATION OF THE PAINT ON THE INTERIOR SIDES OF THE |
| | AC CLOSET DOORS- SECTION 107.2.1 WPB. FINAL MECHANICAL |
| | APPROVAL IS CONTINGENT ON RECEIPT OF A SIGNED AND |
| | SEALED LETTER OR REPORT BY THE DESIGN PROFESSIONAL OF |
| | RECORD, OR A MANUFACTURER'S CERTIFICATION LETTER WITH |
| | AN APPROVAL STAMP BY THE DESIGN PROFESSIONAL. PLEASE |
| | PLACE NOTES ON THE PLANS ACCORDINGLY. |
| | |
| | 8) M4.4.1, M4.4.2, M4.4.3, M4.4.4, M4.4.5, & M4.4.6: |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CLOTHES |
| | DRYERS- SECTION 504.1 FBC M. PLEASE NOTE THAT DRYER |
| | EXHAUST DUCTS SHALL NOT RUN THROUGH ABOVE CEILING |
| | PLENUM SPACES- SECTION 504.4 FBC M. |
| | |
| | 9) M4.4.6: THE RETURN GRILL AT THE MASTER BEDROOM IS |
| | UNDERSIZED PER SECTION 601.6(2) AND 601.6(3) FBC M. THE |
| | RETURN MUST BE SIZED LARGE ENOUGH TO RETURN ALL AIR |
| | FROM THE SUITE AT 50 SQ. INCHES PER 100 CFMS OF SUPPLY |
| | AIR. |
| | |
| | 10) M7.4.2- AC CLOSET DETAIL: INDICATE THEY TYPE AND |
| | SIZE OF CONDENSATE PIPING FOR THE AIR HANDLER- SECTIONS |
| | 307.2.1 AND 602.2.1 FBC M. |
| | |
| | 11) M2.4.6 & M7.4.2: PROVIDE COMPLETE WIND LOAD |
| | ENGIMNEERING FOR ATTACHEMNT OF THE RTU AND CURB, AND |
| | EXTERIOR DUXCTWORK PO THE ROOF STRUCTURE- SECTION |
| | 301.15 FBC M. |
| | |
| | 12) FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S |
| | ARE REQUIRED FOR THE ROOFTOP CONDENSER STANDS AND |
| | EXHAUST AND O/A INLET LOUVERS. THESE MAY BE SUBMITTED |
| | NOW WITH THE ENGINEER OF RECORD'S SHOP DRAWING STAMP OF |
| | APPROVAL, OR MAY BE DEFERRED SUBMITTALS- SEE SECTION |
| | 107.3.4.1 WPB. PLEASE NOTE THAT THE O/A LOUVERS SHALL |
| | BE AMCA 550 RATED PER SECTION 401.5 FBC M. |
| | |
| | 13) CLARIFY IF THERE WILL BE AN ELEVATOR MACHINERY OR |
| | CONTROL ROOM AND SHOW THE LOCATION IF APPLICABLE- |
| | SECTION 3005.1. PLEASE NOTE THAT ELEVATOR MACHINE OR |
| | CONTROLS ROOMS REQUIRE INDEPENDENT VENTILATION SYSTEMS- |
| | SECTION 3005.2. FBC B. |
| | |
| | 14) CLARIFY IF THE HOISTWAY WILL BE VENTED AND PROVIDE |
| | DETAILS- LOCATION OF VENT, TYPE AND SIZE OF VENT AND |
| | DAMPER ETC. PLEASE NOTE THAT PLUMBING AND MECHANICAL |
| | SYSTEMS SHALL NOT BE LOCATED IN THE HOISTWAY ENCLOSURE- |
| | SECTION 3002.9 FBC B. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |