| 2019-04-29 11:55:49 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 0.4 - THERE IS NO INDCATION OF INFORMATION |
| | UNDER SECTION, FIRE ALARM. THERE ARE, HOWEVER, |
| | INDICATIONS OF FIRE ALARM ON OTHER PLAN SHEETS. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 2) SHEET C 6.00 - THEREARE INDICATION OF FIRE MAINS AND |
| | UNDERGROUNG FIRE LINES. |
| | |
| | ALL UNDERGROUND FIRE LINE AND FIRE MAINS SHALL BE |
| | INSTALLED AND INSPECTED PER NFPA 24. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS |
| | PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT, |
| | |
| | |
| | |
| | 2A) SHEET C 6.00 - WATER SUPPLY SHALL BE INSTALLED AND |
| | MAINTAINED PRIOR TO ANY WORK ON A STRUCTURE. |
| | |
| | PER NFPA 241, SAFEGUARDING CONSTRUCTION, ALTERATION, |
| | AND DEMOLITION OPERATIONS |
| | |
| | 8.7.2 WATER SUPPLY. |
| | 8.7.2.1* AWATER SUPPLY FOR FIRE PROTECTION, EITHER |
| | TEMPORARY OR |
| | PERMANENT, SHALL BE MADE AVAILABLE AS SOON AS |
| | COMBUSTIBLE |
| | MATERIAL ACCUMULATES. |
| | 8.7.2.2 THERE SHALL BE NO DELAY IN THE INSTALLATION OF |
| | FIRE PROTECTION |
| | EQUIPMENT. (SEE A.8.2.5.) |
| | 8.7.2.3* WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE |
| | TO |
| | BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND IN |
| | SERVICE |
| | PRIOR TO COMMENCING CONSTRUCTION WORK ON ANY STRUCTURE. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS |
| | PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT, |
| | |
| | |
| | |
| | 3) SHEET FP 2.1.2 - THERE APPEAR TO BE AN INDICATION OF |
| | ONE STANDPIPE CABINET WITHIN THE EXIT CORRIDOR. |
| | . |
| | PER NFPA 1 |
| | |
| | 13.2.2.2 NEW BUILDINGS SHALL BE EQUIPPED WITH A CLASS I |
| | STANDPIPE |
| | SYSTEM INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF |
| | SECTION 13.2 |
| | WHERE ANY OF THE FOLLOWING CONDITIONS EXIST: |
| | (1) MORE THAN THREE STORIES ABOVE GRADE WHERE THE |
| | BUILDING IS |
| | PROTECTED BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM |
| | |
| | PER NFPA 14 |
| | |
| | 7.3.2* CLASS I SYSTEMS. CLASS I SYSTEMS SHALL BE |
| | PROVIDED WITH |
| | 21?2 IN. (65 MM) HOSE CONNECTIONS IN THE FOLLOWING |
| | LOCATIONS: |
| | (1) AT THE MAIN FLOOR LANDING IN EXIT STAIRWAYS |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 3A) SHEET FP 2.1.2 - THERE ARE INDICATIONS OF |
| | STANDPIPE. |
| | |
| | PER NFPA 241: |
| | |
| | 7.6 STANDPIPES. IN ALL NEW BUILDINGS IN WHICH |
| | STANDPIPES ARE |
| | REQUIRED OR WHERE STANDPIPES EXIST IN BUILDINGS BEING |
| | ALTERED |
| | OR DEMOLISHED, SUCH STANDPIPES SHALL BE MAINTAINED IN |
| | CONFORMITY |
| | WITH THE PROGRESS OF BUILDING CONSTRUCTION IN SUCH A |
| | MANNER |
| | THAT THEY ARE ALWAYS READY FOR USE. |
| | |
| | 8.7.4.2 STANDPIPE INSTALLATIONS IN BUILDINGS UNDER |
| | CONSTRUCTION. |
| | WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION, IN |
| | BUILDINGS UNDER CONSTRUCTION, A STANDPIPE SYSTEM, |
| | EITHER TEMPORARY |
| | OR PERMANENT IN NATURE, SHALL BE INSTALLED IN |
| | ACCORDANCE |
| | WITH 8.7.4.2.1 THROUGH 8.7.4.2.10. |
| | 8.7.4.2.1 THE STANDPIPES SHALL BE PROVIDED WITH |
| | CONSPICUOUSLY |
| | MARKED AND READILY ACCESSIBLE FIRE DEPARTMENT |
| | CONNECTIONS |
| | ON THE OUTSIDE OF THE BUILDING AT THE STREET LEVEL AND |
| | SHALL |
| | HAVE AT LEAST ONE STANDARD HOSE OUTLET AT EACH FLOOR. |
| | 8.7.4.2.2 THE PIPE SIZES, HOSE VALVES, HOSE, WATER |
| | SUPPLY, AND |
| | OTHER DETAILS FOR NEW CONSTRUCTION SHALL BE IN |
| | ACCORDANCE WITH |
| | THIS STANDARD. |
| | 8.7.4.2.3 THE STANDPIPES SHALL BE SECURELY SUPPORTED |
| | AND RESTRAINED |
| | AT EACH ALTERNATE FLOOR. |
| | 8.7.4.2.4* AT LEAST ONE APPROVED HOSE VALVE FOR |
| | ATTACHING FIRE |
| | DEPARTMENT HOSE SHALL BE PROVIDED AT EACH INTERMEDIATE |
| | LANDING |
| | OR FLOOR LEVEL IN THE EXIT STAIRWAY, AS DETERMINED BY |
| | THE |
| | AUTHORITY HAVING JURISDICTION. |
| | 8.7.4.2.5 VALVES SHALL BE KEPT CLOSED AT ALL TIMES AND |
| | GUARDED |
| | AGAINST MECHANICAL INJURY. |
| | 8.7.4.2.6 HOSE VALVES SHALL HAVE NH STANDARD EXTERNAL |
| | THREADS FOR THE VALVE SIZE SPECIFIED IN ACCORDANCE WITH |
| | NFPA 1963, STANDARD FOR FIRE HOSE CONNECTIONS, UNLESS |
| | MODIFIED |
| | BY 8.7.4.2.7. |
| | 8.7.4.2.7 WHERE LOCAL FIRE DEPARTMENT CONNECTIONS DO |
| | NOT CONFORM |
| | TO NFPA 1963, STANDARD FOR FIRE HOSE CONNECTIONS, THE |
| | AUTHORITY |
| | HAVING JURISDICTION SHALL DESIGNATE THE CONNECTION TO |
| | BE USED. |
| | 8.7.4.2.8* THE STANDPIPES SHALL BE EXTENDED UP WITH |
| | EACH |
| | FLOOR AND SHALL BE SECURELY CAPPED AT THE TOP. |
| | 8.7.4.2.9 TOP HOSE OUTLETS SHALL BE NOT MORE THAN ONE |
| | FLOOR |
| | BELOW THE HIGHEST FORMS, STAGING, AND SIMILAR |
| | COMBUSTIBLES AT |
| | ALL TIMES. |
| | 8.7.4.2.10 TEMPORARY STANDPIPES SHALL REMAIN IN SERVICE |
| | UNTIL |
| | THE PERMANENT STANDPIPE INSTALLATION IS COMPLETE. |
| | |
| | STANDPIPES ARE REQUIRED TO BE INSTALLED WHEN |
| | CONSTRUCTION STARTS AT THE 3RD LEVEL. |
| | |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS |
| | PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT, |
| | |
| | |
| | 3B) THERE APPEARS TO ONLY ON FIRE DEPARTMENT CONNECTION |
| | ON EACH FLOOR. |
| | |
| | PER NFPA 14 |
| | |
| | 7.3.2.2* WHERE THE MOST REMOTE PORTION OF A |
| | NONSPRINKLERED |
| | FLOOR OR STORY IS LOCATED IN EXCESS OF 150 FT (45.7 M) |
| | OF TRAVEL |
| | DISTANCE FROM A HOSE CONNECTION IN OR ADJACENT TO A |
| | REQUIRED |
| | EXIT OR THE MOST REMOTE PORTION OF A SPRINKLERED FLOOR |
| | OR STORY |
| | IS LOCATED IN EXCESS OF 200 FT (61 M) OF TRAVEL |
| | DISTANCE FROM A |
| | HOSE CONNECTION IN OR ADJACENT TO A REQUIRED EXIT, |
| | ADDITIONAL |
| | HOSE CONNECTIONS SHALL BE PROVIDED, IN APPROVED |
| | LOCATIONS, |
| | WHERE REQUIRED BY THE LOCAL FIRE DEPARTMENT OR THE AHJ. |
| | |
| | PLEASE REVIEW AND CORRECT AS THE DISTANCE APPEARS TO BE |
| | EXCEEDED OR JUSTIFY WITH SPECIFIC DIMENSIONS. |
| | |
| | |
| | 4) SHEET LS 4.0 - UNDER THE PROJECT NARRATIVE THERE ARE |
| | INDICATIONS OF "ENCLOSED PARKING GARAGE AND "HIGHEST |
| | OCCUPIED FLOOR LEVEL ABOVE FIRE DEPARTMENT ACCESS |
| | 317'-6", AS WELL AS, OTHER HIGH RISE REFERENCES. |
| | |
| | PLEASE REVIEW AND CLARIFY/CORRECT. |
| | |
| | |
| | |
| | |
| | 5) SHEET LS 0.4.1(A 0.4 ACTUAL) - WITHIN THE INDEX |
| | SHEET LS 0.4.1 IS INDICATED FOR THE LIFE SAFETY OF |
| | FLOOR 1 - 5. THERE ARE NO INDICATIONS OF LIFE SAFETY ON |
| | THAT SHEET. SHEET LS 0.4.1 IS INDICATED AS SHEET A 0.4 |
| | IN THE LOWER RIGHT TILTE BLOOCK. |
| | |
| | PLEASE REVIEW AND COORECT AND PROVIDE THE APPLICABLE |
| | LIFE SAFETY SHEETS. |
| | |
| | |
| | |
| | |
| | 5) SHEET E 2.4.0 - THERE INDICATIONS OF FIRE ALARM |
| | DEVICES AND EQUIPMENT. |
| | |
| | ALL FIRE ALARM EQUIPMENT AND DEVICES SHALL BE INSTALLED |
| | UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS |
| | PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT, |
| | |
| | |
| | |
| | 5) SHEET E 2.4.1 - THERE IS AN INDICATION OF A FACP |
| | WITHIN A FOYER AREA; HOWEVER, THERE IN NO INDICATION OF |
| | A SMOKE DETECTOR OVER IT. |
| | |
| | PER NFPA 72 |
| | |
| | 10.4.4* IN AREAS THAT ARE NOT CONTINUOUSLY OCCUPIED, |
| | AUTOMATIC |
| | SMOKE DETECTION SHALL BE PROVIDED AT THE LOCATION OF |
| | EACH FIRE ALARM CONTROL UNIT(S), NOTIFICATION APPLIANCE |
| | CIRCUIT |
| | POWER EXTENDERS, AND SUPERVISING STATION TRANSMITTING |
| | EQUIPMENT |
| | TO PROVIDE NOTIFICATION OF FIRE AT THAT LOCATION. |
| | EXCEPTION: WHERE AMBIENT CONDITIONS PROHIBIT |
| | INSTALLATION OF AUTOMATIC |
| | SMOKE DETECTION, AUTOMATIC HEAT DETECTION SHALL BE |
| | PERMITTED. |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 6) SHEET A 7.4.1 - A 42" GUARD RAIL IS INDICATED AT THE |
| | EXTERIOR OF THE STAIRWELLS. DETAILS OF THIS PROPOSED |
| | RAILING IS LIMITED. |
| | |
| | PER NFPA 101, CH 7 MEANS OF EGRESS. |
| | |
| | 7.2.2.6.2* VISUAL PROTECTION. OUTSIDE STAIRS SHALL BE |
| | ARRANGED TO |
| | AVOID ANY IMPEDIMENTS TO THEIR USE BY PERSONS HAVING A |
| | FEAR OF HIGH |
| | PLACES. OUTSIDE STAIRS MORE THAN 36 FT (11 M) ABOVE THE |
| | FINISHED |
| | GROUND LEVEL, OTHER THAN PREVIOUSLY APPROVED EXISTING |
| | STAIRS, SHALL BE |
| | PROVIDED WITH AN OPAQUE VISUAL OBSTRUCTION NOT LESS |
| | THAN 48. IN. |
| | (1220 MM) IN HEIGHT. |
| | |
| | PLEASE REVIEW AND CORRECT/PROVIDE DETAILS OF |
| | COMPLIANCE. |
| | |
| | |
| | |
| | 7)WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION |
| | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |