Plan Review Notes
Plan Review Notes For Permit 19040464
Permit Number 19040464
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-04-29 11:55:49THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 0.4 - THERE IS NO INDCATION OF INFORMATION
 UNDER SECTION, FIRE ALARM. THERE ARE, HOWEVER,
 INDICATIONS OF FIRE ALARM ON OTHER PLAN SHEETS.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) SHEET C 6.00 - THEREARE INDICATION OF FIRE MAINS AND
 UNDERGROUNG FIRE LINES.
  
 ALL UNDERGROUND FIRE LINE AND FIRE MAINS SHALL BE
 INSTALLED AND INSPECTED PER NFPA 24.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS
 PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT,
  
  
  
 2A) SHEET C 6.00 - WATER SUPPLY SHALL BE INSTALLED AND
 MAINTAINED PRIOR TO ANY WORK ON A STRUCTURE.
  
 PER NFPA 241, SAFEGUARDING CONSTRUCTION, ALTERATION,
 AND DEMOLITION OPERATIONS
  
 8.7.2 WATER SUPPLY.
 8.7.2.1* AWATER SUPPLY FOR FIRE PROTECTION, EITHER
 TEMPORARY OR
 PERMANENT, SHALL BE MADE AVAILABLE AS SOON AS
 COMBUSTIBLE
 MATERIAL ACCUMULATES.
 8.7.2.2 THERE SHALL BE NO DELAY IN THE INSTALLATION OF
 FIRE PROTECTION
 EQUIPMENT. (SEE A.8.2.5.)
 8.7.2.3* WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE
 TO
 BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND IN
 SERVICE
 PRIOR TO COMMENCING CONSTRUCTION WORK ON ANY STRUCTURE.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS
 PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT,
  
  
  
 3) SHEET FP 2.1.2 - THERE APPEAR TO BE AN INDICATION OF
 ONE STANDPIPE CABINET WITHIN THE EXIT CORRIDOR.
 .
 PER NFPA 1
  
 13.2.2.2 NEW BUILDINGS SHALL BE EQUIPPED WITH A CLASS I
 STANDPIPE
 SYSTEM INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF
 SECTION 13.2
 WHERE ANY OF THE FOLLOWING CONDITIONS EXIST:
 (1) MORE THAN THREE STORIES ABOVE GRADE WHERE THE
 BUILDING IS
 PROTECTED BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM
  
 PER NFPA 14
  
 7.3.2* CLASS I SYSTEMS. CLASS I SYSTEMS SHALL BE
 PROVIDED WITH
 21?2 IN. (65 MM) HOSE CONNECTIONS IN THE FOLLOWING
 LOCATIONS:
 (1) AT THE MAIN FLOOR LANDING IN EXIT STAIRWAYS
  
 PLEASE REVIEW AND CORRECT.
  
  
 3A) SHEET FP 2.1.2 - THERE ARE INDICATIONS OF
 STANDPIPE.
  
 PER NFPA 241:
  
 7.6 STANDPIPES. IN ALL NEW BUILDINGS IN WHICH
 STANDPIPES ARE
 REQUIRED OR WHERE STANDPIPES EXIST IN BUILDINGS BEING
 ALTERED
 OR DEMOLISHED, SUCH STANDPIPES SHALL BE MAINTAINED IN
 CONFORMITY
 WITH THE PROGRESS OF BUILDING CONSTRUCTION IN SUCH A
 MANNER
 THAT THEY ARE ALWAYS READY FOR USE.
  
 8.7.4.2 STANDPIPE INSTALLATIONS IN BUILDINGS UNDER
 CONSTRUCTION.
 WHERE REQUIRED BY THE AUTHORITY HAVING JURISDICTION, IN
 BUILDINGS UNDER CONSTRUCTION, A STANDPIPE SYSTEM,
 EITHER TEMPORARY
 OR PERMANENT IN NATURE, SHALL BE INSTALLED IN
 ACCORDANCE
 WITH 8.7.4.2.1 THROUGH 8.7.4.2.10.
 8.7.4.2.1 THE STANDPIPES SHALL BE PROVIDED WITH
 CONSPICUOUSLY
 MARKED AND READILY ACCESSIBLE FIRE DEPARTMENT
 CONNECTIONS
 ON THE OUTSIDE OF THE BUILDING AT THE STREET LEVEL AND
 SHALL
 HAVE AT LEAST ONE STANDARD HOSE OUTLET AT EACH FLOOR.
 8.7.4.2.2 THE PIPE SIZES, HOSE VALVES, HOSE, WATER
 SUPPLY, AND
 OTHER DETAILS FOR NEW CONSTRUCTION SHALL BE IN
 ACCORDANCE WITH
 THIS STANDARD.
 8.7.4.2.3 THE STANDPIPES SHALL BE SECURELY SUPPORTED
 AND RESTRAINED
 AT EACH ALTERNATE FLOOR.
 8.7.4.2.4* AT LEAST ONE APPROVED HOSE VALVE FOR
 ATTACHING FIRE
 DEPARTMENT HOSE SHALL BE PROVIDED AT EACH INTERMEDIATE
 LANDING
 OR FLOOR LEVEL IN THE EXIT STAIRWAY, AS DETERMINED BY
 THE
 AUTHORITY HAVING JURISDICTION.
 8.7.4.2.5 VALVES SHALL BE KEPT CLOSED AT ALL TIMES AND
 GUARDED
 AGAINST MECHANICAL INJURY.
 8.7.4.2.6 HOSE VALVES SHALL HAVE NH STANDARD EXTERNAL
 THREADS FOR THE VALVE SIZE SPECIFIED IN ACCORDANCE WITH
 NFPA 1963, STANDARD FOR FIRE HOSE CONNECTIONS, UNLESS
 MODIFIED
 BY 8.7.4.2.7.
 8.7.4.2.7 WHERE LOCAL FIRE DEPARTMENT CONNECTIONS DO
 NOT CONFORM
 TO NFPA 1963, STANDARD FOR FIRE HOSE CONNECTIONS, THE
 AUTHORITY
 HAVING JURISDICTION SHALL DESIGNATE THE CONNECTION TO
 BE USED.
 8.7.4.2.8* THE STANDPIPES SHALL BE EXTENDED UP WITH
 EACH
 FLOOR AND SHALL BE SECURELY CAPPED AT THE TOP.
 8.7.4.2.9 TOP HOSE OUTLETS SHALL BE NOT MORE THAN ONE
 FLOOR
 BELOW THE HIGHEST FORMS, STAGING, AND SIMILAR
 COMBUSTIBLES AT
 ALL TIMES.
 8.7.4.2.10 TEMPORARY STANDPIPES SHALL REMAIN IN SERVICE
 UNTIL
 THE PERMANENT STANDPIPE INSTALLATION IS COMPLETE.
  
 STANDPIPES ARE REQUIRED TO BE INSTALLED WHEN
 CONSTRUCTION STARTS AT THE 3RD LEVEL.
  
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS
 PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT,
  
  
 3B) THERE APPEARS TO ONLY ON FIRE DEPARTMENT CONNECTION
 ON EACH FLOOR.
  
 PER NFPA 14
  
 7.3.2.2* WHERE THE MOST REMOTE PORTION OF A
 NONSPRINKLERED
 FLOOR OR STORY IS LOCATED IN EXCESS OF 150 FT (45.7 M)
 OF TRAVEL
 DISTANCE FROM A HOSE CONNECTION IN OR ADJACENT TO A
 REQUIRED
 EXIT OR THE MOST REMOTE PORTION OF A SPRINKLERED FLOOR
 OR STORY
 IS LOCATED IN EXCESS OF 200 FT (61 M) OF TRAVEL
 DISTANCE FROM A
 HOSE CONNECTION IN OR ADJACENT TO A REQUIRED EXIT,
 ADDITIONAL
 HOSE CONNECTIONS SHALL BE PROVIDED, IN APPROVED
 LOCATIONS,
 WHERE REQUIRED BY THE LOCAL FIRE DEPARTMENT OR THE AHJ.
  
 PLEASE REVIEW AND CORRECT AS THE DISTANCE APPEARS TO BE
 EXCEEDED OR JUSTIFY WITH SPECIFIC DIMENSIONS.
  
  
 4) SHEET LS 4.0 - UNDER THE PROJECT NARRATIVE THERE ARE
 INDICATIONS OF "ENCLOSED PARKING GARAGE AND "HIGHEST
 OCCUPIED FLOOR LEVEL ABOVE FIRE DEPARTMENT ACCESS
 317'-6", AS WELL AS, OTHER HIGH RISE REFERENCES.
  
 PLEASE REVIEW AND CLARIFY/CORRECT.
  
  
  
  
 5) SHEET LS 0.4.1(A 0.4 ACTUAL) - WITHIN THE INDEX
 SHEET LS 0.4.1 IS INDICATED FOR THE LIFE SAFETY OF
 FLOOR 1 - 5. THERE ARE NO INDICATIONS OF LIFE SAFETY ON
 THAT SHEET. SHEET LS 0.4.1 IS INDICATED AS SHEET A 0.4
 IN THE LOWER RIGHT TILTE BLOOCK.
  
 PLEASE REVIEW AND COORECT AND PROVIDE THE APPLICABLE
 LIFE SAFETY SHEETS.
  
  
  
  
 5) SHEET E 2.4.0 - THERE INDICATIONS OF FIRE ALARM
 DEVICES AND EQUIPMENT.
  
 ALL FIRE ALARM EQUIPMENT AND DEVICES SHALL BE INSTALLED
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS
 PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT,
  
  
  
 5) SHEET E 2.4.1 - THERE IS AN INDICATION OF A FACP
 WITHIN A FOYER AREA; HOWEVER, THERE IN NO INDICATION OF
 A SMOKE DETECTOR OVER IT.
  
 PER NFPA 72
  
 10.4.4* IN AREAS THAT ARE NOT CONTINUOUSLY OCCUPIED,
 AUTOMATIC
 SMOKE DETECTION SHALL BE PROVIDED AT THE LOCATION OF
 EACH FIRE ALARM CONTROL UNIT(S), NOTIFICATION APPLIANCE
 CIRCUIT
 POWER EXTENDERS, AND SUPERVISING STATION TRANSMITTING
 EQUIPMENT
 TO PROVIDE NOTIFICATION OF FIRE AT THAT LOCATION.
 EXCEPTION: WHERE AMBIENT CONDITIONS PROHIBIT
 INSTALLATION OF AUTOMATIC
 SMOKE DETECTION, AUTOMATIC HEAT DETECTION SHALL BE
 PERMITTED.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 6) SHEET A 7.4.1 - A 42" GUARD RAIL IS INDICATED AT THE
 EXTERIOR OF THE STAIRWELLS. DETAILS OF THIS PROPOSED
 RAILING IS LIMITED.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS.
  
 7.2.2.6.2* VISUAL PROTECTION. OUTSIDE STAIRS SHALL BE
 ARRANGED TO
 AVOID ANY IMPEDIMENTS TO THEIR USE BY PERSONS HAVING A
 FEAR OF HIGH
 PLACES. OUTSIDE STAIRS MORE THAN 36 FT (11 M) ABOVE THE
 FINISHED
 GROUND LEVEL, OTHER THAN PREVIOUSLY APPROVED EXISTING
 STAIRS, SHALL BE
 PROVIDED WITH AN OPAQUE VISUAL OBSTRUCTION NOT LESS
 THAN 48. IN.
 (1220 MM) IN HEIGHT.
  
 PLEASE REVIEW AND CORRECT/PROVIDE DETAILS OF
 COMPLIANCE.
  
  
  
 7)WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL