| 2019-05-28 07:45:16 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 19040464 |
| | REVIEWED: MAY 28, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH |
| | ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES |
| | TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH |
| | THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND |
| | THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| | GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS |
| | ORDINANCE. PER CITY OF WEST PALM BEACH ORDINANCE NO. |
| | 4504-14, AND CITY OF WEST PALM BEACH CODE OF |
| | ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. PER CITY OF |
| | WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, ART IN |
| | PUBLIC PLACES, SECTION 78-122, RENOVATION AND NEW |
| | CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO THE |
| | ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. SEC. 78-129. - PUBLIC ART ASSESSMENT FOR |
| | PRIVATE DEVELOPMENT. (A) APPLICABILITY. THE PROVISIONS |
| | OF THIS ARTICLE AND THE PUBLIC ART ASSESSMENT SECTION |
| | SHALL APPLY TO ALL PRIVATE DEVELOPMENT PROJECTS, |
| | INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR |
| | IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL |
| | CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| | $750,000.00. ALL BUILDINGS WITHIN NEW PLANNED |
| | DEVELOPMENTS SHALL BE ASSESSED CUMULATIVELY TOWARDS |
| | THIS ART IN PUBLIC PLACES REQUIREMENT, EVEN IF THE |
| | BUILDINGS ARE PERMITTED SEPARATELY OR DEVELOPED IN |
| | PHASES. THE PROVISIONS OF THIS SECTION APPLY TO NEW |
| | DEVELOPMENT OR NEW CONSTRUCTION WITHIN EXISTING PLANNED |
| | DEVELOPMENTS. |
| | - THIS PROJECT MEETS THE CRITERIA TO PROVIDE AIPP. |
| | PLEASE CONTACT: MS. SYBILLE WELTER ART IN PUBLIC PLACES |
| | COORDINATOR 822-1515 E-MAIL: [email protected] |
| | |
| | 2) 109.3 FBC[AMENDED] PROVIDE COST ESTIMATING METHOD |
| | AND CALCULATIONS THAT WERE USED FOR PERMIT VALUATION. |
| | - THE VALUE APPEARS TO BE BASED AT AROUND 100 DOLLARS |
| | PER SQUARE FOOT. CURRENT CONSTRUCTION COSTS FOR ANY |
| | TYPE OF NEW CONSTRUCTION WOULD EXCEED THAT AMOUNT. |
| | PLEASE EVALUATE CONSTRUCTION COSTS. THE COSTS WOULD |
| | EXCLUDE LAND AND ITEMS THAT WILL BE PERMITTED SEPARATLY |
| | (FIRE ALARM AND FIRE SPRINKLERS) |
| | |
| | 3) 107.5.3 FBC[AMENDED] CODE EDITIONS. |
| | - SHEET LS-0.4.0 JUST BELOW FAIR HOUSING EDITION. |
| | PLEASE REMOVE REFERENCES TO FT. LAUDERDALE. |
| | |
| | 4) F.S. 553.79(5) THRESHOLD BUILDING. |
| | THIS PROJECT MEETS THE DEFINITION OF A THRESHOLD |
| | BUILDING. THE FOLLOWING IS REQUIRED PRIOR TO |
| | COMMENCEMENT. |
| | A) COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT |
| | OF UNDERSTANDING; IF PDF OF AGREEMENT IS NEEDED PLEASE |
| | CONTACT THE BUILDING PLAN REVIEWER AND THEY WILL |
| | PROVIDE VIA E-MAIL. [email protected] |
| | B) PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL |
| | PROPOSED INSPECTORS. PLEASE INCLUDE AS MANY ADDITIONAL |
| | INSPECTORS AS POSSIBLE BECAUSE THESE ARE THE ONLY |
| | PEOPLE THAT THE CHIEF BUILDING INSPECTOR WILL ALLOW TO |
| | BE ON-SITE. |
| | C) ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT |
| | REQUIRED BY FS553.79(7)(D). ?ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECTS OR ENGINEERS |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE |
| | FIRE SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS CHAPTER 553 AND |
| | CHAPTER 633.? |
| | D) OK-FOUND SHEET S-1.1 THRESHOLD INSPECTION PLAN |
| | REQUIRED, FS553.79(5)A). |
| | - THERE IS A SIMILAR STATEMENT LIKE ITEM C IN THE |
| | COMMENT ABOVE, BUT IT NEEDS TO BE THE STATEMENT IN |
| | QUOTES FROM ITEM C ABOVE. |
| | |
| | 5)319 FBC[R] ADDRESSES ARE NEEDED FOR THIS PROJECT. THE |
| | PERMIT CANNOT BE ISSUED UNTIL AND ADDRESS HAS BEEN |
| | ASSIGNED TO THE BUILDING. |
| | - PLEASE CALL MICHAEL ORIO BY PHONE AT 561-494-1080, OR |
| | BY E-MAIL [email protected] |
| | |
| | 6) REQUIREMENT 2 - ACCESSIBLE AND USABLE PUBLIC AND |
| | COMMON USE AREAS |
| | - SHOW ACCESSIBLE PATH TO TRASH COLLECTION AREA. |
| | |
| | 7) REQUIREMENT 3 - USABLE DOORS. THE DOORS IN COMMON |
| | SPACES AND THE SIDE ENTERING INTO DWELLING UNITS NEED |
| | TO HAVE USABLE HARDWARE THAT CAN BE USED WITHOUT TIGHT |
| | GRASPING OR TWISTING. |
| | - TYPICALLY THE HARDWARE WOULD BE A LEVER TYPE. THIS |
| | TYPE OF HARDWARE WOULD NOT BE REQUIRED ONCE INSIDE THE |
| | UNIT. YOU MAY WANT TO CLARIFY HARDWARE ON THE DOOR |
| | SCHEDULE. |
| | |
| | 8) REQUIREMENT 5 - LIGHT SWITCHES, OUTLETS, THERMOSTATS |
| | AND OTHE CONTROLS IN ACCESSIBLE LOCATIONS. (SIDE |
| | REACHES OVER OBSTRUCTIONS) |
| | - PLEASE VERIFY THAT A NOTE OR REFERENCE TO THE |
| | REQUIRED HEIGHTS CAN BE FOUND IN ELECTRICAL PAGES WHERE |
| | THE CONTRACTOR WILL SEE THEM. |
| | |
| | 9) 1011.12 FBC[B] STAIRWAY TO ROOF. IN BUILDINGS FOUR |
| | OR MORE STORIES ABOVE GRADE PLANE, ONE STAIRWAY SHALL |
| | EXTEND TO THE ROOF SURFACE UNLESS THE ROOF HAS A SLOPE |
| | STEEPER THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL |
| | (33-PERCENT SLOPE). |
| | - PROVIDE STAIRWAY TO ROOF, OR PROVIDE CODE SECTION |
| | THAT EXEMPTS 1011.12 FOR BUILDINGS OVER 4 STORIES. |
| | |
| | 10) 401.4 FBC[R] PROVIDE SOIL REPORT TO SHOW BEARING |
| | CAPACITY AND FOUNDATION RECOMMENDATIONS. |
| | - PLEASE UPLOAD GEOTECHNICAL REPORT INTO SUPPORTING |
| | DOCUMENTS IN PROJECTDOX |
| | |
| | 11) 107.3.5 FBC[AMENDED] |
| | - STRUCTURAL S-2.4.1 NOTE 1 SHOULD NOT REFERENCE NAVD |
| | SINCE IT CONFLICTS WITH CIVIL PLANS. JUST A REFERENCE |
| | TO SEE CIVIL PLANS WOULD SUFFICE. |
| | |
| | 12) 1803.6 FBC[B] REPORTING. WHERE GEOTECHNICAL |
| | INVESTIGATIONS ARE REQUIRED, A WRITTEN REPORT OF THE |
| | INVESTIGATIONS SHALL BE SUBMITTED TO THE BUILDING |
| | OFFICIAL BY THE PERMIT APPLICANT AT THE TIME OF PERMIT |
| | APPLICATION. THIS GEOTECHNICAL REPORT SHALL INCLUDE, |
| | BUT NEED NOT BE LIMITED TO, THE FOLLOWING INFORMATION: |
| | - (SEE 1803.6 FOR REQUIREMENTS) |
| | |
| | 13) 3002.4 FBC[B] ELEVATOR CAR TO ACCOMMODATE AMBULANCE |
| | STRETCHER. ANY BUILDING THAT IS MORE THAN THREE STORIES |
| | HIGH OR IN WHICH THE VERTICAL DISTANCE BETWEEN THE |
| | BOTTOM TERMINAL LANDING AND THE TOP TERMINAL LANDING |
| | EXCEEDS 25 FEET (7620 MM), MUST BE CONSTRUCTED TO |
| | CONTAIN AT LEAST ONE PASSENGER ELEVATOR THAT IS |
| | OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE DEPARTMENT |
| | EMERGENCY ACCESS TO ALL FLOORS. THE ELEVATOR CAR SHALL |
| | BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE AN |
| | AMBULANCE STRETCHER 24 INCHES BY 76 INCHES (610 MM BY |
| | 1950 MM) WITH NOT LESS THAN 5-INCH (127 MM) RADIUS |
| | CORNERS, IN THE HORIZONTAL, OPEN POSITION AND SHALL BE |
| | IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY |
| | MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL BE |
| | NOT LESS THAN 3 INCHES (76 MM) IN HEIGHT AND SHALL BE |
| | PLACED INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME. |
| | - SHOW HOW STRECHER WILL FIT IN ONE OF THE ELEVATORS. A |
| | SGRAPHIC REPRESENTAION OF 24X74 INCH RECTANGLE WITH |
| | MAXIMUM 5 INCH RADIUS CORNERS FROM ENTRY TO FINAL |
| | POSITION ON PLAN VIEW WILL SUFFICE. |
| | |
| | 14) 107.3.4.1 FBC[AMENDED] DEFERRED SUBMITTALS. FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE |
| | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | - PLEASE PROVIDE A LIST OF DEFERRED SUBMITTALS SO THAT |
| | I WILL NOT ASK FOR ITEMS THAT WILL BE SUPPLIED AT A |
| | LATER DATE, OR INDICATE WHICH PAGE A LIST CAN BE FOUND. |
| | |
| | 15) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS |
| | FOR WINDOWS, WINDOW MULL (IF APPLICABLE), DOORS, |
| | TRANSOMS, SLIDERS OR INDICATE THAT YOU WOULD LIKE THEM |
| | DEFERED. |
| | |
| | 16) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT |
| | APPROVAL(P.A.) FOR ROOFING, OR INDICATE THAT YOU WOULD |
| | LIKE THEM DEFERED. INCLUDE P.A. FOR RIDGE VENTS IN |
| | ROOFING SUBMITTAL |
| | |
| | 17) 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS |
| | TO THE BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | - THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN |
| | SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE |
| | DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE |
| | REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION. |
| | |
| | 18) 107.2.1.2 FBC[AMENDED] PROVIDE STAIRCASE AND GUARD |
| | RAIL ENGINEERING, OR INDICATE THAT IT WILL BE DEFERRED. |
| | |
| | 19) 1014 FBC [B] GUARDS AND HANDRAILS. 1607.8 FBC [B] |
| | LOADS ON HANDRAILS AND GUARDRAILS. PROVIDE HANDRAIL AND |
| | GUARDRAIL ENGINEERING, OR INDICATE THAT YOU WOULD LIKE |
| | IT DEFERRED. |
| | |
| | 20) 107.3.4. FBC[AMENDED] A CONSTRUCTION GUARDRAIL |
| | DETAIL, PREPARED BY A DESIGN PROFESSIONAL LICENSED |
| | UNDER FS471 OR FS481, IS REQUIRED TO BE SUBMITTED, |
| | REVIEWED AND ISSUED BY THE CITY OF WEST PALM BEACH, OR |
| | INDICATE THAT IT WILL BE DEFERRED. *SUBJECT TO THE |
| | INSPECTORS DISCRETION, THIS MAY BE ACCEPTED IN THE |
| | FIELD AT TIME OF INSPECTION. |
| | |
| | 21) 1207.2 FBC[B] PLEASE ADVISE ,VIA EMAIL, WHAT |
| | FLOORING AND UNDERLAYMENT ARE PROPOSED? IF THE |
| | UNDERLAYMENT PRODUCT PROPOSED IS NOT ONE FOR WHICH WE |
| | HAVE TEST REPORTS ON FILE, THE FOLLOWING REPORTS WILL |
| | BE REQUIRED: |
| | 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND |
| | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND |
| | SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF |
| | NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E90. |
| | 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR |
| | BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR |
| | NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E492. |
| | 603.1 FBC[B] ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | 22) 804.1 FBC[B] GENERAL. INTERIOR FLOOR FINISH AND |
| | FLOOR COVERING MATERIALS SHALL COMPLY WITH SECTIONS |
| | 804.2 THROUGH 804.4.2. EXCEPTION: FLOOR FINISHES AND |
| | COVERINGS OF A TRADITIONAL TYPE, SUCH AS WOOD, VINYL, |
| | LINOLEUM OR TERRAZZO, AND RESILIENT FLOOR COVERING |
| | MATERIALS THAT ARE NOT COMPRISED OF FIBERS. |
| | |
| | 103.1.1.2 FBC[CE] CODE COMPLIANCE CERTIFICATION. THE |
| | BUILDINGS OWNER, THE OWNERS ARCHITECT, OR OTHER |
| | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL |
| | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE |
| | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR |
| | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR |
| | RENOVATION. |
| | -PLEASE HAVE APPROPRIATE PARTIES SIGN THE ENERGY |
| | CALCULATIONS. |
| | |
| | NOTES: |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |