| 2019-07-09 18:00:27 | 2ND REVIEW: 19040464 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH |
| | |
| | 3) SHT. A-10.4.1, A-10.4.2 AND A-10.4.3 THE LEGEND |
| | REFERENCED IN THE RESPONSE LETTER DOES NOT SHOW THE |
| | REQUIRED 56" X48" CLEAR FLOOR SPACE FOR THE TOILET |
| | PLEASE ADD TO LEGEND PER FHA DESIGN MANUAL REQUIREMENT |
| | #7 |
| | |
| | 8) PLEASE PROVIDE MANUFACTURE SPECIFICATION FOR SUB |
| | METER IT SHALL SHOW THAT METER IS RATED FOR AIR PLENUM |
| | NON COMBUSTIBLE MATERIAL. |
| | |
| | NEW COMMENTS; |
| | |
| | 1. SEPARATE PERMIT REQUIRED FOR ALL BACK FLOWS PLACE |
| | NOTE ON PLAN.PER WPB UTILITIES DEPARTMENT |
| | |
| | 2. PROVIDE ROOF DRAIN SIZING CALCULATIONS. PER FBC PL |
| | 1106.2 |
| | |
| | PLANS MARKED AS 75% COMPLETE PROVIDE 100% COMPLETE |
| | PLANS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |