| 2019-07-10 16:11:32 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19040463 |
| | 7/10/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE ENERGYGAUGE TOTAL BUILDING PERFORMANCE |
| | COMPLIANCE SUBMITTAL DOES NOT PROVIDE ANY COMPLIANCE |
| | DATA FOR THE RETAIL PORTIONS OF THE BUILDING SHOWN ON |
| | THE GROUND FLOOR, INCLUDING THE CONSTRUCTS AND SQUARE |
| | FOOTAGE OF THOSE PORTIONS- SECTIONS C407.1 & C407.2 FBC |
| | EC. A) THE REQUESTED MINIMUM VENTILATION FOR THE RETAIL |
| | SPACES AND CORRIDOR HAVE NOT BEEN PROVIDED IN THE TABLE |
| | ON SHEET M-5.1.1. |
| | |
| | 2) SHEETS M-2.1.1 & M-5.1.1: COMMENT #3 FROM THE 1ST |
| | REVIEW HAS NOT BEEN COMPLETELY ADDRESSED. ON SHEET |
| | M-2.1.1. PLEASE PLACE A NOTE TO INDICAET THAT THE |
| | GARAGE EXHAUST OUTLETS ARE A MINIMUM 3' AWAY FROM |
| | OPERABLE OPENINGS INTO THE BUILDING- SECTION 501.3.1 |
| | (3) FBC M. M-5.1.1: THE GARAGES HAVE BEEN CLASSIFIED AS |
| | PARKING GARAGES ON SHEET LS-0.1.0 WHICH REQUIRES THE |
| | EXHAUST SYSTEMS TO EITHER RUN CONTINOUSLY (SECTION |
| | 502.13 FBC M), OR OPERATE INTERMITTENTLY BY MEANS OF |
| | CARBON MONOXIDE AND NITROGEN DIOXIDE SENSORS- SECTION |
| | 404.1 FBC M. PLEASE NOTE THAT AUTOMATIC OPERATION OF |
| | THE SYSTEM SHALL NOT REDUCE THE VENTILATION AIRFLOW |
| | RATE BELOW 0.05 CFM PER SQ. FT.- SECTION 404.2 FBC M. |
| | |
| | 3) SHEET M-5.1.1: COMMENT #4 FROM THE 1ST REVIEW COPIED |
| | BELOW STILL EXISTS. |
| | 403.3.2.1 OUTDOOR AIR FOR DWELLING UNITS. |
| | AN OUTDOOR AIR VENTILATION SYSTEM CONSISTING OF A |
| | MECHANICAL EXHAUST SYSTEM, SUPPLY SYSTEM OR COMBINATION |
| | THEREOF SHALL BE INSTALLED FOR EACH DWELLING UNIT. |
| | LOCAL EXHAUST OR SUPPLY SYSTEMS, INCLUDING OUTDOOR AIR |
| | DUCTS CONNECTED TO THE RETURN SIDE OF AN AIR HANDLER, |
| | ARE PERMITTED TO SERVE AS SUCH A SYSTEM. THE OUTDOOR |
| | AIR VENTILATION SYSTEM SHALL BE DESIGNED TO PROVIDE THE |
| | REQUIRED RATE OF OUTDOOR AIR CONTINUOUSLY DURING THE |
| | PERIOD THAT THE BUILDING IS OCCUPIED. THE MINIMUM |
| | CONTINUOUS OUTDOOR AIRFLOW RATE SHALL BE DETERMINED IN |
| | ACCORDANCE WITH EQUATION 4-9. |
| | |
| | (EQUATION 4-9) |
| | WHERE: |
| | QOA = OUTDOOR AIRFLOW RATE, CFM |
| | AFLOOR = FLOOR AREA, FT2 |
| | NBR = NUMBER OF BEDROOMS; NOT TO BE LESS THAN ONE |
| | EXCEPTION: THE OUTDOOR AIR VENTILATION SYSTEM IS NOT |
| | REQUIRED TO OPERATE CONTINUOUSLY WHERE THE SYSTEM HAS |
| | CONTROLS THAT ENABLE OPERATION |
| | FOR NOT LESS THAN 1 HOUR OF EACH 4-HOUR PERIOD. THE |
| | AVERAGE OUTDOOR AIR FLOW RATE OVER THE 4-HOUR PERIOD |
| | SHALL BE NOT LESS THAN THAT PRESCRIBED BY EQUATION 4-9. |
| | |
| | 4) M-6.1.2: COMMENT #8 FROM THE 1ST REVIEW HAS NOT |
| | ADDRESSED. PLEASE INDICATE THE TYPE AND SIZE OF |
| | CONDENSATE PIPING TO BE INSTALLED IN THE PLENUM RATED |
| | AC CLOSETS- SECTIONS 307.2.1 & 602.2.1 FBC M. |
| | |
| | 5) M-4.1.3: THE 16X6 RETURN FROM THE MASTER SUITE IS |
| | UNDERSIZED PER SECTION 601.6(3) FBC M. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |