| 2019-07-16 08:14:38 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | |
| | NEW COMMENTS: |
| | |
| | 7. SMOKE ALARMS ARE SHOWN ON DIFFERENT CIRCUITS. |
| | PROVIDE CORRECTION. FBC RE R314 |
| | 8. SEVERAL SHEETS FROM THE FIRST SUBMISSION THAT STATE |
| | THEY ARE 95% DOCUMENTS HAVE NOT BEEN REPLACED WITH THIS |
| | SUBMISSION. PROVIDE A FULL SET FOR REVIEW. WPB FBC |
| | 107.2.1 |
| | 9. PROVIDE GFCI PROTECTION FOR DISHWASHERS. NEC |
| | 210.8(D) |
| | 10. AS THIS IS NOT A 100% SUBMITTAL, FURTHER COMMENTS |
| | NOT ADDRESSED IN THIS REVIEW MAY BE POSSIBLE UPON NEXT |
| | REVIEW. WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |