| 2019-07-17 16:52:32 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | 3 STORY MIXED USE ( R-2, M & S-2 ) |
| | TYPE III-B, SPRINKLERED |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) WILL COMPLY. |
| | |
| | 2) PURSUANT TO FBC 109.3, THE VALUATION HAS BEEN |
| | ADJUSTED TO $4,471,531.00, WHICH IS THE CALCULATED |
| | VALUE FOR THIS MIXED USE BUILDING. |
| | IN ORDER TO AVOID BEING CHARGED FOR DUPLICATE PERMIT |
| | FEES, PLEASE PROVIDE A LIST OF THE ITEMS THAT REQUIRE A |
| | SEPARATE PERMIT AND THE COST FOR EACH OF THEM. THIS |
| | WILL ALLOW ME TO REMOVE THEIR COSTS FROM THE BUILDING |
| | VALUATION FOR THIS PERMIT. ALL OTHER PERMITS FIRE |
| | SPRINKLER, FIRE ALARM, RACK STORAGE, EXHAUST HOODS, |
| | ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC |
| | FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & FREEZERS, |
| | ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL TANKS, GAS |
| | PERMIT, POOL, JACUZZI AND ASSOCIATED SUB-PERMITS, |
| | AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, LANDSCAPE, |
| | IRRIGATION, AUGER CAST PILE AND OR FOUNDATION OR |
| | STRUCTURE ONLY PERMIT WILL BE SEPARATE REVIEWS AND |
| | ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL EFFECTIVELY BE THE VALUE OF THE |
| | BUILDING THAT THE PERMIT FEES WILL BE BASED ON FOR THIS |
| | PERMIT. THE BUILDING DEPARTMENT DOES NOT WANT TO |
| | COLLECT TWICE FOR THE VALUE OF THESE SUB-PERMITS NOT |
| | COVERED UNDER THE PRIME OR MASTER PERMIT. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) PRODUCT APPROVALS WILL BE DEFERRED. |
| | |
| | 5) THE TESTING REPORTS FOR THE SOUND INSULATION FOR THE |
| | FLOORING FOR SOUND, FLAME SPREAD AND SMOKE DEVELOPED |
| | WILL BE DEFERRED. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) COMPLIED. |
| | |
| | 8) NOT COMPLIED. NOTE IS STILL ON SOME OF THE PLAN |
| | SHEETS. THE NOTE THAT STATES 95% PERMIT SET NEEDS TO BE |
| | REMOVED FROM THE PLANS. PLANS SUBMITTED FOR PERMIT ARE |
| | REQUIRED TO BE 100% COMPLETE. FBC 107.2.1 |
| | |
| | 9) SHOP DRAWINGS FOR THE BALCONY AND STAIR GUARDS WILL |
| | BE DEFERRED. |
| | |
| | 10) ROOF TRUSS DRAWINGS AND LAYOUT PLANS WILL BE |
| | DEFERRED. |
| | |
| | 11) COMPLIED. |
| | |
| | 12) DEFERRED. WILL COMPLY. |
| | |
| | 13) DEFERRED. WILL COMPLY. |
| | |
| | 14) COMPLIED. |
| | |
| | 15) COMPLIED. |
| | |
| | 16) COMPLIED. |
| | |
| | 17) COMPLIED. |
| | |
| | 18) COMPLIED. |
| | |
| | 19) COMPLIED. |
| | |
| | 20) COMPLIED. |
| | |
| | 21) COMPLIED. |
| | |
| | 22) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 23) NEW COMMENT: SHEET S-1.1 HAS A THRESHOLD INSPECTION |
| | PLAN. THIS BUILDING IS NOT A "THRESHOLD BUILDING", IT |
| | WILL BE YOUR DECISION TO REMOVE THIS SHEET OR LEAVE IT |
| | IN THE PLANS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |