| 2019-05-07 17:43:55 | |
| | 1ST REVIEW: 19040463 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THIS PROJECT SHALL COMPLY WITH FBC ACC 233.3.1 AND |
| | |
| | 233.3.1.1 RESIDENTIAL DWELLING UNITS WITH MOBILITY |
| | FEATURES. IN FACILITIES WITH RESIDENTIAL DWELLING |
| | UNITS, AT LEAST 5 PERCENT, BUT NO FEWER THAN ONE UNIT, |
| | OF THE TOTAL NUMBER OF RESIDENTIAL DWELLING UNITS SHALL |
| | PROVIDE MOBILITY FEATURES COMPLYING WITH 809.2 THROUGH |
| | 809.4 AND SHALL BE ON AN ACCESSIBLE ROUTE AS REQUIRED |
| | BY 206. |
| | |
| | 233.3.1.2 RESIDENTIAL DWELLING UNITS WITH COMMUNICATION |
| | FEATURES. IN FACILITIES WITH RESIDENTIAL DWELLING |
| | UNITS, AT LEAST 2 PERCENT, BUT NO FEWER THAN ONE UNIT, |
| | OF THE TOTAL NUMBER OF RESIDENTIAL DWELLING UNITS SHALL |
| | PROVIDE COMMUNICATION FEATURES COMPLYING WITH 809.5. |
| | PLEASE CLEARLY INDICATE WHICH UNITS COMPLY. PER WPB |
| | AMEND TO FBC 107.2 |
| | |
| | 2. THE LAVATORY'S IN THE B BATHROOMS SHALL BE MAX 34" |
| | OFF FINISH FLOOR. PER FHA DESIGN MANUAL REQ.. #7 |
| | |
| | 3. SHT. A-10.4.1, A-10.1.1 AND A-10.1.2 SHOW DIMENSIONS |
| | ON THE CLEAR FLOOR SPACE FOR THE TOILET, LAVATORY, |
| | SHOWER AND KITCHEN PER FHA DESIGN MANUAL REQ. #7 |
| | |
| | 4.SHT. P-2.0.0 IN THE MIDDLE OF THE PAGE THERE IS A |
| | NOTE UNDER SEPARATE PERMIT WHAT IS THIS NOTE FOR PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. SHT. A-10.1.1 UNIT A1-B DOES NOT SHOW DESIGN SPEC |
| | FOR THE BATHROOM PLEASE CLARIFY. PER FHA DESIGN MANUAL |
| | REQ. #7 |
| | |
| | 6. SHT. P-2.4.6 OVER FLOW DRAIN ARE REQUIRED ON ROOFS |
| | THE CAN COLLECT WATER IF THE MAIN DRAIN FAILS PLEASE |
| | SHOW OVERFLOW DRAIN LOCATIONS. PER FBC PL 1108.1 |
| | |
| | 7. PLEASE PROVIDE A PAN DRAIN RISER. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 8. PROVIDE MANUFACTURE SPECIFICATIONS FOR SUB METER. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. SHOW SIZE AND MANUFACTURE OF THE GREASE INTERCEPTOR |
| | AND PIPING DETAIL. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |