Plan Review Notes
Plan Review Notes For Permit 19040463
Permit Number 19040463
Review Stop M
Sequence Number 1
Notes
Date Text
2019-05-07 17:02:591ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040463
 5/7/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTIONS 202, C101.4.1, C101.5, R101.4.1
 AND R101.5 FBC EC. THE RESIDENTIAL PORTION OF THE
 PROPOSED PROJECT SHALL COMPLY WITH THE FLORIDA ENERGY
 CODE RESIDENTIAL PROVISIONS, AND THE COMMERCIAL PORTION
 SHALL COMPLY WITH THE FLORIDA ENERGY CODE COMMERCIAL
 PROVISIONS. NEITHER THE SUBMITTED ENERGYGAUGE SUMMIT
 FLA/COM REPORT OR THE TRACE 700 HEAT LOAD CALCULATION
 SOFTWARE CAN BE USED TO SHOW COMPLIANCE FOR THE
 RESIDENTIAL PORTION. PLEASE SEE SECTION R101.5.1 FOR
 ACCEPTABLE RESIDENTIAL ENERGY COMPLIANCE SUBMITTAL
 MATERIALS, AND SECTION R403.7.1 WHICH REQUIRES SYSTEM
 SIZINGS TO BE PERFORMED IN ACCORDANCE WITH ACCA MANUAL
 S AND J. PLEASE NOTE THAT ALL CALUCALTIONS PERFORMED BY
 THE ENGINEER SHALL BE ELECTRONICALLY SIGNED AND SEALED-
 SECTION 61G15-23.005 FAC.
  
 2) BASED ON COMMENT #1, THE COMMERCIAL PORTION OF THE
 BUILDING MUST BE SEPARATED FROM THE RESIDENTIAL PORTION
 AND SEPARATE ENERGY COMPLIANCE AND HEAT LOAD
 CALCULCATIONS IN ACCORDANCE WITH THE FLORIDA ENERGY
 CODE COMMERCIAL PROVISONS SHALL BE SUBMITTED.
  
 3) SHEET M2.1.1: PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR THE GARAGES, AND THE SEQUENCE OF
 OPERATION FOR THE FANS- SEE TABLE 403.3.1.1 AND 501.4
 FBC M. A) SHOW THE REQUIRED CLEARANCE DISTANCES FOR THE
 EXHAUST OUTLET TO OPERABLE AND MECHANICAL AIR INTAKES,
 AND FROM GRADE- SECTION 501.3.1 FBC M.
  
 4) M5.1.1: PLEASE CORRECT THE FBC MINIMUM VENTILATION
 CALCULATIONS AND REMOVE OR CORRECT THE NOTES SPECIFYING
 RATES BASED ON THE TABLES IN THE FBC R, THE FBC R CODE
 IS APPLICABLE ONLY FOR SINGLE FAMILY HOMES, DUPLEXES,
 AND TOWNHOUSES. REFER TO SECTION 403.3.2.1 FBC M COPIED
 BELOW, AND INDICATE COMPLIANCE:
  
 403.3.2.1 OUTDOOR AIR FOR DWELLING UNITS.
 AN OUTDOOR AIR VENTILATION SYSTEM CONSISTING OF A
 MECHANICAL EXHAUST SYSTEM, SUPPLY SYSTEM OR COMBINATION
 THEREOF SHALL BE INSTALLED FOR EACH DWELLING UNIT.
 LOCAL EXHAUST OR SUPPLY SYSTEMS, INCLUDING OUTDOOR AIR
 DUCTS CONNECTED TO THE RETURN SIDE OF AN AIR HANDLER,
 ARE PERMITTED TO SERVE AS SUCH A SYSTEM. THE OUTDOOR
 AIR VENTILATION SYSTEM SHALL BE DESIGNED TO PROVIDE THE
 REQUIRED RATE OF OUTDOOR AIR CONTINUOUSLY DURING THE
 PERIOD THAT THE BUILDING IS OCCUPIED. THE MINIMUM
 CONTINUOUS OUTDOOR AIRFLOW RATE SHALL BE DETERMINED IN
 ACCORDANCE WITH EQUATION 4-9.
  
 (EQUATION 4-9)
 WHERE:
  
 QOA = OUTDOOR AIRFLOW RATE, CFM
  
 AFLOOR = FLOOR AREA, FT2
  
 NBR = NUMBER OF BEDROOMS; NOT TO BE LESS THAN ONE
  
 EXCEPTION: THE OUTDOOR AIR VENTILATION SYSTEM IS NOT
 REQUIRED TO OPERATE CONTINUOUSLY WHERE THE SYSTEM HAS
 CONTROLS THAT ENABLE OPERATION
 FOR NOT LESS THAN 1 HOUR OF EACH 4-HOUR PERIOD. THE
 AVERAGE OUTDOOR AIR FLOW RATE OVER THE 4-HOUR PERIOD
 SHALL BE NOT LESS THAN THAT PRESCRIBED BY EQUATION 4-9.
  
 5) SHEETS M4.1.1, 4.1.2, AND 4.1.3: LOCAL EXHAUST
 SYSTEMS ARE REQUIRED FOR THE KITCHENS AT A RATE OF 100
 CFMS INTERMITTENT OR 25 CFMS CONTINUOUS. INDICATE HOW
 COMPLIANCE WILL BE MET.
  
 6) A4.1.5, M4.1.1, 4.1.2, AND 4.1.3: THE CITY OF WPB
 BUILDING DEPARTMENT REQUIRES EITHER THE DESIGN
 PROFESSIONAL OF RECORD OR THE INTUMESCENT PAINT
 MANUFACTURER TO CERTIFY THE APPLICATION OF THE PAINT ON
 THE INTERIOR SIDES OF THE AC CLOSET DOORS- SECTION
 107.2.1 WPB. FINAL MECHANICAL APPROVAL IS CONTINGENT ON
 RECEIPT OF A SIGNED AND SEALED LETTER OR REPORT BY THE
 DESIGN PROFESSIONAL OF RECORD, OR A MANUFACTURER'S
 CERTIFICATION LETTER WITH AN APPROVAL STAMP BY THE
 DESIGN PROFESSIONAL. PLEASE PLACE NOTES ON THE PLANS
 ACCORDINGLY.
  
 7) M4.1.1, 4.1.2, AND 4.1.3: SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE CLOTHES DRYERS- SECTION 504.1
 FBC M.
  
 8) M6.1.2- AC CLOSET DETAIL: INDICATE THEY TYPE AND
 SIZE OF CONDENSATE PIPING FOR THE AIR HANDLER- SECTIONS
 307.2.1 AND 602.2.1 FBC M.
  
 9) FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S
 ARE REQUIRED FOR THE ROOFTOP CONDENSER STANDS AND
 EXHAUST AND O/A INLET LOUVERS. THESE MAY BE SUBMITTED
 NOW WITH THE ENGINEER OF RECORD'S SHOP DRAWING STAMP OF
 APPROVAL, OR MAY BE DEFERRED SUBMITTALS- SEE SECTION
 107.3.4.1 WPB. PLEASE NOTE THAT THE O/A LOUVERS SHALL
 BE AMCA 550 RATED PER SECTION 401.5 FBC M.
  
 10) CLARIFY IF THERE WILL BE AN ELEVATOR MACHINERY OR
 CONTROL ROOM AND SHOW THE LOCATION IF APPLICABLE-
 SECTION 3005.1. PLEASE NOTE THAT ELEVATOR MACHINE OR
 CONTROL ROOMS REQUIRE INDEPENDENT VENTILATION SYSTEMS-
 SECTION 3005.2. FBC B.
  
 11) CLARIFY IF THE HOISTWAY WILL BE VENTED AND PROVIDE
 DETAILS- LOCATION OF VENT, TYPE AND SIZE OF VENT AND
 DAMPER ETC . PLEASE NOTE THAT PLUMBING AND MECHANICAL
 SYSTEMS SHALL NOT BE LOCATED IN THE HOISTWAY ENCLOSURE-
 SECTION 3002.9 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  