2019-04-29 11:35:47THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 0.1 - THERE IS NO INDCATION OF INFORMATION
 UNDER SECTION, FIRE ALARM. THERE ARE, HOWEVER,
 INDICATIONS OF FIRE ALARM ON OTHER PLAN SHEETS.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 1A) SHEET LS 0.01 - UNDER THE PROJECT NARRATIVE THERE
 ARE INDICATIONS OF "ENCLOSED PARKING GARAGE AND
 "HIGHEST OCCUPIED FLOOR LEVEL ABOVE FIRE DEPARTMENT
 ACCESS 317'-6", AS WELL AS, OTHER HIGH RISE REFERENCES.
  
 PLEASE REVIEW AND CLARIFY/CORRECT.
  
  
  
  
 2) SHEET C 6.00 - THEREARE INDICATION OF FIRE MAINS AND
 UNDERGROUND FIRE LINES.
  
 ALL UNDERGROUND FIRE LINE AND FIRE MAINS SHALL BE
 INSTALLED AND INSPECTED PER NFPA 24.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS
 PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT,
  
  
 2A) SHEET C 6.00 - WATER SUPPLY SHALL BE INSTALLED AND
 MAINTAINED PRIOR TO ANY WORK ON A STRUCTURE.
  
 PER NFPA 241, SAFEGUARDING CONSTRUCTION, ALTERATION,
 AND DEMOLITION OPERATIONS
  
 8.7.2 WATER SUPPLY.
 8.7.2.1* AWATER SUPPLY FOR FIRE PROTECTION, EITHER
 TEMPORARY OR
 PERMANENT, SHALL BE MADE AVAILABLE AS SOON AS
 COMBUSTIBLE
 MATERIAL ACCUMULATES.
 8.7.2.2 THERE SHALL BE NO DELAY IN THE INSTALLATION OF
 FIRE PROTECTION
 EQUIPMENT. (SEE A.8.2.5.)
 8.7.2.3* WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE
 TO
 BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND IN
 SERVICE
 PRIOR TO COMMENCING CONSTRUCTION WORK ON ANY STRUCTURE.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS
 PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT,
  
  
 3) SHEET LS 0.1.1 - THERE ARE INDICATION OF EYE SENSOR
 RELAEASE AT EACH EXIT AS WELL AS PUSH TO EXIT BUTTONS.
  
 ALL EXITING EQUIPMENT AND DEVICES SHALL COMPLY WITH
 NFPA 101, CH 7 MEANS OF EGRESS AND SHALL BE INSTALLED
 AND INSPECTED UNDER SEPARATE SHOP DRAWINGS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS
 PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT,
  
  
  
 4) SHEET E 2.1.0 - THERE INDICATIONS OF FIRE ALARM
 DEVICES AND EQUIPMENT.
  
 ALL FIRE ALARM EQUIPMENT AND DEVICES SHALL BE INSTALLED
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS
 PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT,
  
  
  
 5) SHEET E 2.1.1 - THERE IS AN INDICATION OF A FACP
 WITHIN THE LOBBY; HOWEVER, THERE IN NO INDICATION OF A
 SMOKE DETECTOR OVER IT.
  
 PER NFPA 72
  
 10.4.4* IN AREAS THAT ARE NOT CONTINUOUSLY OCCUPIED,
 AUTOMATIC
 SMOKE DETECTION SHALL BE PROVIDED AT THE LOCATION OF
 EACH FIRE ALARM CONTROL UNIT(S), NOTIFICATION APPLIANCE
 CIRCUIT
 POWER EXTENDERS, AND SUPERVISING STATION TRANSMITTING
 EQUIPMENT
 TO PROVIDE NOTIFICATION OF FIRE AT THAT LOCATION.
 EXCEPTION: WHERE AMBIENT CONDITIONS PROHIBIT
 INSTALLATION OF AUTOMATIC
 SMOKE DETECTION, AUTOMATIC HEAT DETECTION SHALL BE
 PERMITTED.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 6) SHEET A 2.1.1 - THERE IS GATE, G8, INDICATED WITHIN
 AN EXIT PATH/DISCHARGE. THIS GATE MUST PROVIDE FREE
 EXIT.
  
 THERE IS NO EXIT HARDWARE PROVIDED/INDICATED FOR THIS
 GATE. ANY EXIT HARDWARE SHALL COMPLY WITH NFPA 101, CH
 7, MEANS OF EGRESS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AS WELL AS
 PROVIDING AN APPLICABLE NOTE OF ACKNOWLEDGEMENT,
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  