| 2019-05-20 07:25:09 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| | INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC |
| | 105.1, 107.2.1 |
| | 2. SHEET E-3.1.0 AND E-5.1.0 SHOW A SERVICE FOR PANEL |
| | S. SITE LIGHTING AND SERVICE SHOULD BE A SEPARATE |
| | SUBMITTAL. IF THIS IS ATTACHED TO THE BUILDING, THEN |
| | THE SERVICE SHOULD BE TIED TO THE GROUNDING ELECTRODE |
| | SYSTEM OF THAT BUILDING. IT SHOULD ALSO BE LABELED AS |
| | AN ADDITIONAL SERVICE, OR AN ADDITIONAL MAIN. MAINS |
| | NEED TO BE GROUPED. ADDITIONAL SERVICES NEED TO BE |
| | LABELED PROPERLY. PROVIDE CLARIFICATIONS AND |
| | CORRECTIONS AS NEEDED. WPB FBC 107.2.1; NEC 215.5, |
| | 230.2, 230.72, 250.50 |
| | 3.PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 4. PROVIDE COMPLIANCE WITH NEC 240.87. |
| | 5. NOTE FOR AIC CALCULATION NOTED AS A DEFERRED |
| | SUBMITTAL. PROVIDE WHEN AVAILABLE. NEC 110.9, 110.10 |
| | 6. PROVIDE NOTE FOR LABELING OF UNIT PANELS. THE |
| | CURRENT PLAN SHOWS THE PANELS NAMED AFTER THE TYPE OF |
| | UNIT. THE IDENTIFICATION SHALL INCLUDE AN APPROVED |
| | DEGREE OF DETAIL THAT ALLOWS EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS. NEC 408.4 |
| | |
| | AS THIS IS NOT A 100% SUBMITTAL, FURTHER COMMENTS NOT |
| | ADDRESSED IN THIS REVIEW MAY BE POSSIBLE UPON NEXT |
| | REVIEW. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |