2019-05-20 07:25:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
 2. SHEET E-3.1.0 AND E-5.1.0 SHOW A SERVICE FOR PANEL
 S. SITE LIGHTING AND SERVICE SHOULD BE A SEPARATE
 SUBMITTAL. IF THIS IS ATTACHED TO THE BUILDING, THEN
 THE SERVICE SHOULD BE TIED TO THE GROUNDING ELECTRODE
 SYSTEM OF THAT BUILDING. IT SHOULD ALSO BE LABELED AS
 AN ADDITIONAL SERVICE, OR AN ADDITIONAL MAIN. MAINS
 NEED TO BE GROUPED. ADDITIONAL SERVICES NEED TO BE
 LABELED PROPERLY. PROVIDE CLARIFICATIONS AND
 CORRECTIONS AS NEEDED. WPB FBC 107.2.1; NEC 215.5,
 230.2, 230.72, 250.50
 3.PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. PROVIDE COMPLIANCE WITH NEC 240.87.
 5. NOTE FOR AIC CALCULATION NOTED AS A DEFERRED
 SUBMITTAL. PROVIDE WHEN AVAILABLE. NEC 110.9, 110.10
 6. PROVIDE NOTE FOR LABELING OF UNIT PANELS. THE
 CURRENT PLAN SHOWS THE PANELS NAMED AFTER THE TYPE OF
 UNIT. THE IDENTIFICATION SHALL INCLUDE AN APPROVED
 DEGREE OF DETAIL THAT ALLOWS EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. NEC 408.4
  
 AS THIS IS NOT A 100% SUBMITTAL, FURTHER COMMENTS NOT
 ADDRESSED IN THIS REVIEW MAY BE POSSIBLE UPON NEXT
 REVIEW.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved