| | RESIDENTIAL (R3) SUBMITTAL SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS. |
| | |
| | |
| | NOTE: A MEETING WITH THE PERSON COMPLETING THE |
| | INSTALLATION SCHEDULE IS PREFERRED AT THIS TIME. IT |
| | WILL SAVE TIME AND ALL THE QUESTIONS CAN BE ADDRESSED |
| | THEN. PLEASE CONTACT ME SO WE CAN SET UP A MEETING. |
| | |
| | |
| | |
| | 1- HURRICANE FABRIC SHUTTERS INSTALLATION SCHEDULE |
| | SUBMITTED: |
| | A) INSTALLATION SCHEDULE CALLS FOR 2-1/2" SHUTTER GLASS |
| | SEPARATION. GLASS SEPARATION DOESN'T COMPLY WITH THE |
| | GLASS SEPARATION REQUIRED ON PRODUCT APPROVAL PAGE 2 OF |
| | 11 OF NOA 15-0316.09 SUBMITTED. REVISE AS REQUIRED. FAC |
| | 61G20-3.001 AND SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | B) CLARIFY WHICH ANCHOR SCHEDULE FROM NOA SUBMITTED WAS |
| | USED TO DETERMINE THE ANCHOR SPACING. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | C) CLARIFY SHUTTER INSTALLATION (VERTICAL/HORIZONTAL) |
| | AND SHUTTERS SPAN. BASED ON THE OPENINGS SIZE GIVEN AND |
| | THE PROPOSED INSTALLATION IT DOESN'T LOOK LIKE THE |
| | REQUIRED MINIMUM EDGE DISTANCE IS MET. THE EDGE |
| | DISTANCE CAN NOT INCLUDE THE STUCCO THICKNESS. BASED ON |
| | THE SHUTTER SPAN IT LOOKS LIKE THE STUCCO THICKNESS WAS |
| | NOT CONSIDERED. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | NOTE: A MEETING WITH THE PERSON COMPLETING THE |
| | INSTALLATION SCHEDULE IS PREFERRED AT THIS TIME IT WILL |
| | SAVE TIME AND ALL THE QUESTIONS MAY BE ANSWERED. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |