Plan Review Notes
Plan Review Notes For Permit 19040460
Permit Number 19040460
Review Stop B
Sequence Number 3
Notes
Date Text
2019-04-24 12:28:55 
 RESIDENTIAL (R3) SUBMITTAL SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
  
  
 NOTE: A MEETING WITH THE PERSON COMPLETING THE
 INSTALLATION SCHEDULE IS PREFERRED AT THIS TIME. IT
 WILL SAVE TIME AND ALL THE QUESTIONS CAN BE ADDRESSED
 THEN. PLEASE CONTACT ME SO WE CAN SET UP A MEETING.
  
  
  
 1- HURRICANE FABRIC SHUTTERS INSTALLATION SCHEDULE
 SUBMITTED:
 A) INSTALLATION SCHEDULE CALLS FOR 2-1/2" SHUTTER GLASS
 SEPARATION. GLASS SEPARATION DOESN'T COMPLY WITH THE
 GLASS SEPARATION REQUIRED ON PRODUCT APPROVAL PAGE 2 OF
 11 OF NOA 15-0316.09 SUBMITTED. REVISE AS REQUIRED. FAC
 61G20-3.001 AND SEC. R301.1 FBC-RESIDENTIAL.
  
 B) CLARIFY WHICH ANCHOR SCHEDULE FROM NOA SUBMITTED WAS
 USED TO DETERMINE THE ANCHOR SPACING. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 C) CLARIFY SHUTTER INSTALLATION (VERTICAL/HORIZONTAL)
 AND SHUTTERS SPAN. BASED ON THE OPENINGS SIZE GIVEN AND
 THE PROPOSED INSTALLATION IT DOESN'T LOOK LIKE THE
 REQUIRED MINIMUM EDGE DISTANCE IS MET. THE EDGE
 DISTANCE CAN NOT INCLUDE THE STUCCO THICKNESS. BASED ON
 THE SHUTTER SPAN IT LOOKS LIKE THE STUCCO THICKNESS WAS
 NOT CONSIDERED. REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 NOTE: A MEETING WITH THE PERSON COMPLETING THE
 INSTALLATION SCHEDULE IS PREFERRED AT THIS TIME IT WILL
 SAVE TIME AND ALL THE QUESTIONS MAY BE ANSWERED.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  