| Date |
Text |
| 2019-11-08 17:00:22 | SEE ITEM #6 ON 3RD BUILDING REVIEW DONE BY JULIO GOMEZ. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 3RD REQUEST. THE SUBMITTED NOA: 14-0827.18TAMKO |
| | MODIFIED BITUMEN ROOF SYSTEM OVER STEEL DECK HAS |
| | VARIOUS SUB-SYSTEMS LISTED WITHIN THE REPORT BUT NONE |
| | OF THE SUB-SYSTEMS WERE IDENTIFIED AS THE ONE BEING |
| | INSTALLED. : FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED |
| | (LIMITATION #7 ALLOWS ENHANCED FASTENING, LIMITATION # |
| | 9 DOES NOT ALLOW ENHANCED FASTENING) FOR ROOF ZONES 2 & |
| | 3. FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| | INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE |
| | WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION |
| | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | |
| | RESPONSE: |
| | APPROVED ASSEMBLY WAS NOT SELECTED. AND, NEED SIGNED |
| | AND SEALED RAS 117 CALCULATIONS FOR SELECTED ASSEMBLY |
| | (GENERAL LIMITATION #7 ONLY). IF THE SELECTED ASSEMBLY |
| | IS LIMITED BY GENERAL LIMITATION #9 AND THE ASSEMBLY |
| | DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, |
| | THEN IT CAN NOT BE USED. |
| | NOTE: ALL PRODUCT APPROVALS CAN BE SUBMITTED LATER AS |
| | DEFERRED SUBMITTAL. ADVICE IF PREFER TO SUBMIT PRODUCT |
| | APPROVALS AS DEFERRED SUBMITTAL. |