| 2019-10-29 06:04:34 | PLUMBING 3RD REVIEW**DENIED**PLEASE SUPPLIED A |
| | NARRATIVE. FL STATUE 553.80 (2) (B) WITH RESPECT TO |
| | EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A |
| | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | LAST REVIEW COMMENTS STILL NOT ANSWERED AGAIN. |
| | 1-PROVIDE CLEAR FLOOR SPACE AND TURNING SPACE FOR THE |
| | TRAINING ROOM/ BREAK ROOM SINK WITH CABINET DETAIL |
| | SHOWING MAX 34?. FBC-ACC 606.2, 606.3 |
| | 2- PROVIDE NOTE ON PLAN SEPARATE BACKFLOW AND |
| | INTERCEPTOR PERMIT REQUIRED. FBC 107.1 |
| | 3-SHT. A-106 IS CALLING OUT ROOF DRAIN CALCULATIONS |
| | BASED ON 2010 FBC-PLB CODE. THE CODE CURRENTLY IS THE |
| | 2017 6TH ED. PLEASE CORRECT AND SHOW THE CORRECT CODE. |
| | PROVIDE SIZING OF THE STORM SYSTEM PER FBC-PLB 1105.2, |
| | 1106.2 |
| | 4- SHT. A-106 CALL OUT PIPE PITCHED PER FBC-PLB 553.10. |
| | PLEASE CLARIFY. FBC 107.1 |
| | 5-SHT. A-301 SHOWS ROOF PITCH AS 1/4? PER FOOT BUT |
| | DRAIN DETAIL CALLS OUT ?? PER FOOT. PLEASE CLARIFY. FBC |
| | 107.1 |
| | 6-SHT. A-401 MIRROR DETAIL SHOWS MOUNTING AT 3?4? (40?) |
| | TO THE BOTTOM OF THE MIRROR. MAX MEASUREMENT SHALL BE |
| | TO THE REFLECTING SURFACE. FBC-ACC 603.3 |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | THUNT@CGASOLUTIONS |
| | 561-248-2703 |
| | |
| | |