| Date |
Text |
| 2019-04-25 15:22:21 | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) LIFE SAFETY SHEETS - THERE ARE NO INDICATIONS OF |
| | OCCUPANCY LOADS ON EACH FLOOR. |
| | |
| | PER NFPA 101 CH 38 |
| | |
| | 38.1.7 OCCUPANT LOAD. THE OCCUPANT LOAD, IN NUMBER OF |
| | PERSONS FOR |
| | WHOM MEANS OF EGRESS AND OTHER PROVISIONS ARE REQUIRED, |
| | SHALL BE |
| | DETERMINED ON THE BASIS OF THE OCCUPANT LOAD FACTORS |
| | THAT ARE |
| | CHARACTERISTIC OF THE USE OF THE SPACE OR SHALL BE |
| | DETERMINED AS THE |
| | MAXIMUM PROBABLE POPULATION OF THE SPACE UNDER |
| | CONSIDERATION, |
| | WHICHEVER IS GREATER. |
| | |
| | PLEASE CORRECT AND PROVIDE. |
| | |
| | |
| | |
| | 2) SHEET G 101 - THERE IS ONLY ONE EXIT INDICATED FROM |
| | THE 2ND FLOOR. |
| | |
| | PER NFPA 101, CH 38 NEW BUSINESS: SEE (3) (A). THERE |
| | ARE TWO DOOR OPENINGS INDICATED TO OTHER PARTS OF THE |
| | BUILDING; PARTS WAREHOUSE & ELEVATOR LOBBY. |
| | |
| | 38.2.4 NUMBER OF MEANS OF EGRESS. |
| | 38.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE |
| | FOLLOWING, EXCEPT |
| | AS OTHERWISE PERMITTED BY 38.2.4.2 THROUGH 38.2.4.6: |
| | (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 7.4. |
| | (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED |
| | ON EVERY STORY. |
| | (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE |
| | ACCESSIBLE FROM EVERY |
| | PART OF EVERY STORY. |
| | 38.2.4.2 EXIT ACCESS, AS REQUIRED BY 38.2.4.1(3), SHALL |
| | BE PERMITTED TO |
| | INCLUDE A SINGLE EXIT ACCESS PATH FOR THE DISTANCES |
| | PERMITTED AS COMMON |
| | PATHS OF TRAVEL BY 38.2.5.3. |
| | 38.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR |
| | AREA WITH A TOTAL |
| | OCCUPANT LOAD OF LESS THAN 100 PERSONS, PROVIDED THAT |
| | ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT |
| | THE LEVEL OF EXIT |
| | DISCHARGE FOR THE BUILDING. |
| | (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT, |
| | INCLUDING TRAVEL WITHIN |
| | THE EXIT, SHALL NOT EXCEED 100 FT (30 M). |
| | (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN |
| | 38.2.4.3(2) SHALL BE ON THE |
| | SAME STORY, OR, IF TRAVERSING OF STAIRS IS NECESSARY, |
| | SUCH STAIRS SHALL |
| | NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND BOTH OF THE |
| | FOLLOWING |
| | ALSO SHALL APPLY: |
| | (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE |
| | ENCLOSURES TO |
| | SEPARATE THEM FROM ANY OTHER PART OF THE BUILDING, WITH |
| | NO |
| | DOOR OPENINGS THEREIN. |
| | (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2 |
| | SHALL BE |
| | PERMITTED TO SERVE ALL STORIES PERMITTED WITHIN THE 15 |
| | FT (4570 |
| | MM) VERTICAL TRAVEL LIMITATION. |
| | |
| | **********************OR********************** |
| | |
| | 38.2.4.4 ANY BUSINESS OCCUPANCY THREE OR FEWER STORIES |
| | IN HEIGHT, AND |
| | NOT EXCEEDING AN OCCUPANT LOAD OF 30 PEOPLE PER STORY, |
| | SHALL BE |
| | PERMITTED A SINGLE SEPARATE EXIT TO EACH STORY, |
| | PROVIDED THAT ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE. |
| | (2) THE TOTAL TRAVEL DISTANCE TO THE OUTSIDE OF THE |
| | BUILDING SHALL NOT |
| | EXCEED 100 FT (30 M). |
| | (3) THE EXIT SHALL BE ENCLOSED IN ACCORDANCE WITH |
| | 7.1.3.2, AND BOTH OF |
| | THE FOLLOWING ALSO SHALL APPLY: |
| | (A) THE STAIR SHALL SERVE AS AN EXIT FROM NO OTHER |
| | STORIES. |
| | (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2 |
| | SHALL BE |
| | PERMITTED TO SERVICE ALL STORIES. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES AND NARRATIVE. |
| | |
| | |
| | |
| | |
| | 3) SHEET A 602 - DOOR 117A IS NOT INDICATED AS HAVING A |
| | FIRE RATING. THIS DOOR IS REQUIRED TO BE RATED TO |
| | MAINTAIN THE 2 HR OCCUPANCY SEPARATION. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES AND NARRATIVE. |
| | |
| | |
| | |
| | 4) SHEETS A 101, 102 & 501 - THERE ARE NO INDICATIONS |
| | OF ANY FIRE RATINGSOF LISTINGS ON ANY OF THE WALLS OR |
| | CALL OUTS WHERE FIRE RATING IS REQUIRED. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES AND NARRATIVE. |
| | |
| | |
| | |
| | 5) SHEET A 101 & 602 - DOOR 118 IS NOT INDICATED AS |
| | HAVING A FIRE RATING. THIS DOOR IS REQUIRED TO BE RATED |
| | TO MAINTAIN THE 2 HR OCCUPANCY SEPARATION. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES AND NARRATIVE. |
| | |
| | |
| | |
| | |
| | 6) SHEET A 101 - THE IS AN AREA/ROOM IN THE MIDDLE OF |
| | THE 1ST FLOOR INDICATED AS ELEVATOR LOBBY & HALL. |
| | |
| | THIS AREA DOES NOT APPEAR EITHER A ELEVATOR LOBBY NOR |
| | HALL AND IS LABLED DIFFERENTLY THAN ON SHEET G 101. |
| | |
| | PLEASE REVIEW AND CLARIFY/CORRECT. |
| | |
| | |
| | |
| | 7) SHEET A 101 & 602 - WINDOW DIAMOND 9 IS INDICATED AS |
| | A ROLL DOWN FIRE CURTAIN. |
| | |
| | |
| | |
| | |
| | 8) SHEET A 102 - THE 2ND FLOOR WALL ALONG THE OPEN |
| | SHOWROOM IS NOT INDICATED AS HAVING A FIRE RATING. |
| | |
| | IS THIS A RATED WALL? IT HAS FIRE DROP DOWN DOORS |
| | INDICATED. |
| | |
| | PLEASE CLARIFY AND PROVIDE A APPLICABLE LISTED WALL |
| | CALLOUT. |
| | |
| | |
| | |
| | 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | |
| | 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |