| 2019-04-16 10:13:26 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | JOSEAN A. DUPREY E.I., BN, PX |
| | BUILDING PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6716 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. THE DRAWING SHEET CF-6 UNDER SPECIFICATIONS THE NOTE |
| | #1 INDICATE "THESE DRAWINGS COMPLY WITH THE MINIMUM |
| | REQUIREMENTS OF THE FBC 2014 EDITION". THE CURRENT FBC |
| | IS THE 2017 6TH EDITION. PLEASE REVISED AND RE-SUBMIT. |
| | FBC 107 |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH |
| | EDITION |
| | FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 2. NONE OF THE DOCUMENTS SUBMITTED ARE SIGNED BY THE |
| | ENGINEER. PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER |
| | AND SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE ORIGINAL |
| | SIGNATURE, DATE AND SEAL OF THE ENGINEER PER FL ADMIN. |
| | CODE RULE 61G15-23.001. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |