Plan Review Notes
Plan Review Notes For Permit 19040317
Permit Number 19040317
Review Stop P
Sequence Number 4
Notes
Date Text
2019-07-19 10:18:43PLUMBING PROVISO:
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S
 APPROVAL.
 2. ALL PLUMBING WORK SHALL COMPLY WITH FBC PLUMBING 6TH
 EDITION 2017
 4. THE CENTER OF THE TOILET SHALL BE 16" MIN 18 MAX OFF
 THE SIDE WALL. PER FBC ACC 604.2
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.PER FBC PL 416.5
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]