| Plan Review Notes For Permit 19040317 |
| Permit Number |
19040317 |
|
| Review Stop |
P |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2019-07-19 10:18:43 | PLUMBING PROVISO: | | | 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR?S | | | APPROVAL. | | | 2. ALL PLUMBING WORK SHALL COMPLY WITH FBC PLUMBING 6TH | | | EDITION 2017 | | | 4. THE CENTER OF THE TOILET SHALL BE 16" MIN 18 MAX OFF | | | THE SIDE WALL. PER FBC ACC 604.2 | | | 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET | | | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | | CONFORMS TO ASSE 1070 OR CSA B125.3.PER FBC PL 416.5 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] |
|