2019-04-24 17:24:081ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040317
 4/24/19
  
 APPLICABLE CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS WERE SUBMITTED. PLEASE PROVIDE
 MECHANICAL PLANS AND SPECIFICATIONS INCLUDING:
 A) AC PLAN SHOWING THE LOCATIONS OF THE AIR HANDLER AND
 CONDENSER, AND DUCT LAYOUT- SECTION 107.2.1 WPB.
 B) AC EQUIPMENT SCHEDULE- SECTION 107.2.1 WPB
 C) AC COOLING AND HEATING SYSTEM SIZING CALCULATIONS-
 SECTION C403.2.1 FBC EC
 D) ENERGY CALCULATIONS FOR THE NEW CONDITIONED OFFICE
 SPACE- SECTION C503.2 FBC EC.
 E) VENTILATION CALULATIONS INDICATING THE REQUIRED AND
 PROVIDED OUTDOOR AIR CFMS- TABLE 403.3.1.1 FBC M.
 F) CONDENSATE DISPOSAL PLAN- SECTION 307.2.1 FBC M.
 G) CONDENSER INSTALLATION DETAILS- SECTION 301.15 FBC
 M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  