| 2019-04-24 17:24:08 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19040317 |
| | 4/24/19 |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) NO MECHANICAL PLANS WERE SUBMITTED. PLEASE PROVIDE |
| | MECHANICAL PLANS AND SPECIFICATIONS INCLUDING: |
| | A) AC PLAN SHOWING THE LOCATIONS OF THE AIR HANDLER AND |
| | CONDENSER, AND DUCT LAYOUT- SECTION 107.2.1 WPB. |
| | B) AC EQUIPMENT SCHEDULE- SECTION 107.2.1 WPB |
| | C) AC COOLING AND HEATING SYSTEM SIZING CALCULATIONS- |
| | SECTION C403.2.1 FBC EC |
| | D) ENERGY CALCULATIONS FOR THE NEW CONDITIONED OFFICE |
| | SPACE- SECTION C503.2 FBC EC. |
| | E) VENTILATION CALULATIONS INDICATING THE REQUIRED AND |
| | PROVIDED OUTDOOR AIR CFMS- TABLE 403.3.1.1 FBC M. |
| | F) CONDENSATE DISPOSAL PLAN- SECTION 307.2.1 FBC M. |
| | G) CONDENSER INSTALLATION DETAILS- SECTION 301.15 FBC |
| | M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |