| 2019-04-10 11:48:49 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19040288 |
| | 4/10/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: AS-BUILT MECHANICAL DRAWINGS |
| | DENIED. |
| | |
| | 1) SHEETS M01, M02, M03, M04: THE AS-BUILT DRAWINGS |
| | HAVE COFLICTING DETAILS AND NOTES REGARDING THE SMOKE |
| | DAMPERS. THERE IS A NOTE ON M-01 STATING THEY ARE NOT |
| | REQUIRED, HOWEVER ON THAT SAME SHEET AND ON THE OTHERS, |
| | THEY ARE CALLED OUT TO BE INSTALLED AT DUCT |
| | PENETRATIONS AT COMMON CORRIDOR/ROOM WALLS. PLEASE |
| | CORRECT THESE CONFLICTS. |
| | |
| | 2) M01, M02, M03, & M04: THE AS-BUILT DRAWINGS SHOW THE |
| | DUCTED RETURNS FROM THE ROOMS AND THE MAIN DUCT TRUNK |
| | IN THE CORRIDOR HAVE BEEN REMOVED AND REPLACED WITH A |
| | SYSTEM OF RETUN AIR THAT USES TRANSFER DUCTS FROM THE |
| | ROOMS AND THE CORRIDOR AS A MEANS OF RETURNING AIR TO |
| | THE AIR HANDLERS. PLEASE NOTE THAT CORRIDORS SHALL NOT |
| | BE USED AS RETURN AIR DUCTS PER SECTION 601.2 FBC M. |
| | |
| | 3) PLEASE PROVIDE AS-BUILT ARCHITECTURAL PLANS SHOWING |
| | THE CHANGES MADE TO THE CORRIDOR AND ROOM SEPARATION |
| | WALLS. APPARENTLY THESE SMOKE PARTITION WALLS THAT WERE |
| | DESIGNED AND APPROVED TO EXTEND FROM FLOOR TO UNDERSIDE |
| | OF SLAB HAVE BEEN CHANGED TO EXTEND ONLY TO CEILING |
| | LEVEL- SEE SECTION 710.4 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |