| Plan Review Notes For Permit 19040257 |
| Permit Number |
19040257 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-04-10 14:32:32 | GAS 1ST REVIEW**DENIED** | | | | | | 1) GENERATORS ARE REQUIRED TO HAVE THERE OWN PERMIT AND | | | NOT BE A SUB OFF OF MASTER PERMIT. NOTE MASTER PLAN | | | DOES NOT SHOW GENERATOR | | | | | | 2) VALUE SEEMS LOW AND MUST INCLUDE THE COST OF THE | | | GENERATOR. WPB AMEND TO THE FBC 109.3 | | | | | | 3) STEEL PIPING IS NOT PERMITTED UNDERGROUND. FBC-G | | | 404.11.1 | | | | | | 4) PRIVATE PROVIDER PAPERWORK HAS NOT BEEN INCLUDE IN | | | THIS SUBMITTAL. FBC 107.3.5 | | | | | | 5) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE | | | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL | | | GAS, SECS. 402.4.1, 402.4.2. | | | | | | 6) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE | | | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR | | | EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1. | | | | | | 7) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 | | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FGC SEC.305.1 | | | | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | | | | |
|