| 2019-06-17 11:12:58 | PLUMBING 3RD REVIEW**DENIED**ERIC FROM BUILD PRO WAS |
| | CONTACTED AND ADVISED OF ISSUES AND ACKNOWLEDGE OF LAST |
| | PLAN REVIEWERS COMMENTS REQUESTING A MEETING BUT DUE TO |
| | DESIGN PROFESSIONALS SCHEDULE SHE WAS NOT ABLE TO COME |
| | IN.BOTH ERIC AND DESIGN PROFESSIONAL ARE NOW ADVISING |
| | THIS PROJECT WILL MEET THE 2017 FLORIDA ACCESSIBILITY |
| | CODE IN FULL |
| | |
| | |
| | 1) PROVIDE A CODE COMPLYING SANITARY ISOMETRIC DRAWING. |
| | THE WASHING MACHINE SHALL CONNECT TO A MIN 3" BRANCH/ |
| | STACK. FBC-P 709.1, 406.2 |
| | |
| | 2) TANKLESS WATER HEATER LOCATION HAS BEEN MOVED TO |
| | UNDER THE KITCHEN SINK. THE INSTALLATION MANUAL DOES |
| | NOT PERMIT THE INSTALLATION OF THIS UNIT IN AREA'S THAT |
| | ARE DIFFICULT TO ACCESS, MAINTAIN, SERVICE, REPAIR, OR |
| | REPLACE OF THE UNIT SHOULD IT BE REQUIRED.. FBC-P 502.1 |
| | |
| | 3) PER ERIC (GC) IT IS YOUR INTENTION TO 100% COMPLY |
| | WITH 2017 FLORIDA ACCESSIBILITY. IT SO PLEASE ADDRESS |
| | THE FOLLOWING COMMENTS OTHERWISE REMOVE ALL ADA ITEMS |
| | FROM PLAN AS I WILL NOT PUT MY SIGNATURE ON A PLAN THAT |
| | DOES NOT SHOW CODE COMPLIANT ACCESSIBILITY. |
| | 1. SHOW ON ALL SHEETS THE MIN SIZE PERMITTED FOR THE |
| | SHOWER ALT ROLL IN AS 36" X 60". SEE FBC-ACC 608.2.3 |
| | 2. GRAB BARS SHALL BE 33"-36" TO THE TOP OF THE |
| | GRIPPING SURFACE AND NOT THE CENTER OF THE BAR. FBC-ACC |
| | 608.4 |
| | 3. SHOW WASHING MACHINE AS COMPLYING WITH FBC-ACC 611. |
| | CLEAR FLOOR SPACE, OPERABLE PARTS HEIGHT, ETC |
| | 4. PROVIDE CLEAR FLOOR SPACE FOR THE ALT ROLL IN |
| | SHOWER. FBC-ACC 608.2.2.1 |
| | 5. PROVIDE KITCHEN DETAIL TO INCLUDE CLEAR FLOOR SPACE, |
| | COUNTER TOP HEIGHT, AND TUNING SPACE. FBC-ACC 606.2, |
| | 606.3 |
| | 6. MIRROR SHALL BE MAX 40?"TO THE BOTTOM OF THE |
| | REFLECTIVE SURFACE. |
| | 7. LIST 2017 FLORIDA ACCESSIBILITY CODE AS APPLICABLE |
| | CODE ON SHT. A-1 |
| | 8,SHOW DETAIL LOCATION OF ALL GRAB BARS. FBC-ACC |
| | 608.3.3, 604.5.1, 604.5.2 |
| | 9 PROVIDE DETAIL OF SHOWER VALVE LOCATION MEETING |
| | FBC-ACC 608.5.3 |
| | |
| | |