2019-04-30 08:05:32BUILDING PLAN REVIEW - ROOFING
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. IDENTIFY ROOF SLOPE. STATE NUMBER OF LAYERS OF
 UNDERLAYMENT REQUIRED.
  
 RAS 115. R905.2.2 SLOPE.
 ASPHALT SHINGLES SHALL BE USED ONLY ON ROOF SLOPES OF
 TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) OR
 GREATER. FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12
 UNITS HORIZONTAL (2:12) AND LESS THAN FOUR UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (4:12), DOUBLE
 UNDERLAYMENT APPLICATION IS REQUIRED IN ACCORDANCE WITH
 SECTION R905.2.7.
  