| 2019-04-19 16:17:42 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. TANKLESS WATER HEATER LOCATION IS NOT SHOWN ON |
| | ELECTRICAL PLAN, PROVIDE LOCATION. FBC 107.2.1 |
| | |
| | 2. PROVIDE CUT SHEETS FOR TANKLESS WATER HEATER FOR |
| | PRODUCT APPROVAL. MUST BE LISTED UL OR ANOTHER (NRTL). |
| | FBC 107.2.1 NEC 90.7, 110.2, 110.3B |
| | |
| | 3. SERVICE DISCONNECT NOT SHOWN ON PLAN. PROVIDE |
| | LOCATION. FBC 107.2.1 |
| | |
| | 4. AHU OVERCURRENT PROTECTION IS SHOWN AS 20 AMPS. HEAT |
| | STRIP IN AHU IS SHOWN AS 7.5KW. PROVIDE CORRECT PANEL |
| | SCHEDULE WITH PROPER OVERCURRENT PROTECTION AND WIRE |
| | SIZE. FBC 107.2.1 |
| | |
| | 5. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |