2019-04-30 08:02:01BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE APPEARS LOW FOR SCOPE OF WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 2. PROVIDE SECOND SET OF PRODUCT APPROVALS.
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
 3. REF. PLAN PAGE A-1, NOTE 9,LEVEL OF ALTERATION
 SHOULD STATE LEVEL 3.
 505.1 SCOPE.
 LEVEL 3 ALTERATIONS APPLY WHERE THE WORK AREA EXCEEDS
 50 PERCENT OF THE BUILDING AREA.
  
 505.2 APPLICATION.
 LEVEL 3 ALTERATIONS SHALL COMPLY WITH THE PROVISIONS OF
 CHAPTERS 7 AND 8 FOR LEVEL 1 AND 2 ALTERATIONS,
 RESPECTIVELY, AS WELL AS THE PROVISIONS OF CHAPTER 9.
  
 4. IDENTIFY ROOF SLOPE. STATE NUMBER OF LAYERS OF
 UNDERLAYMENT REQUIRED.
  
 RAS 115. R905.2.2 SLOPE.
 ASPHALT SHINGLES SHALL BE USED ONLY ON ROOF SLOPES OF
 TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) OR
 GREATER. FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12
 UNITS HORIZONTAL (2:12) AND LESS THAN FOUR UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (4:12), DOUBLE
 UNDERLAYMENT APPLICATION IS REQUIRED IN ACCORDANCE WITH
 SECTION R905.2.7.
  
 5. RAMP SHALL COMPLY WITH FBC R311.8. IDENTIFY LOCATION
 OF RAMP ON SITE PLAN. IDENTIFY SLOPE OF RAMP ON DETAIL.
 SLOPE SHALL BE BASED ON LOCATION. I.E. EGRESS DOOR -
 1/12. NON-EGRESS DOOR 1/8.
  
 R311.8.1MAXIMUM SLOPE.
 RAMPS SERVING THE EGRESS DOOR REQUIRED BY SECTION
 R311.2 SHALL HAVE A SLOPE OF NOT MORE THAN 1 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (8.3-PERCENT SLOPE).
 ALL OTHER RAMPS SHALL HAVE A MAXIMUM SLOPE OF 1 UNIT
 VERTICAL IN 8 UNITS HORIZONTAL (12.5 PERCENT).
 EXCEPTION: WHERE IT IS TECHNICALLY INFEASIBLE TO COMPLY
 BECAUSE OF SITE CONSTRAINTS, RAMPS SHALL HAVE A SLOPE
 OF NOT MORE THAN 1 UNIT VERTICAL IN 8 UNITS HORIZONTAL
 (12.5 PERCENT).
  
 6. ROOFING PERMIT REQUIRED.
  
 7. PROVIDE NORTH CARDINAL ARROW.
 PROVIDE A NORTH CARDINAL DIRECTIONAL ARROW ON THE PLANS
 THAT INDICATES THE ORIENTATION OF THE STRUCTURE. FBC
 107.2.1 & FBC ENERGY CONSERVATION R405.4.2.1
  
 R405.4.2.1 COMPLIANCE REPORT FOR PERMIT APPLICATION.
 A COMPLIANCE REPORT SUBMITTED WITH THE APPLICATION FOR
 BUILDING PERMIT SHALL INCLUDE THE FOLLOWING:
 1.BUILDING STREET ADDRESS, OR OTHER BUILDING SITE
 IDENTIFICATION.
 2.A STATEMENT INDICATING THAT THE PROPOSED DESIGN
 COMPLIES WITH SECTION R405.3.
 3.AN INSPECTION CHECKLIST DOCUMENTING THE BUILDING
 COMPONENT CHARACTERISTICS OF THE PROPOSED DESIGN AS
 INDICATED IN TABLE R405.5.2(1). THE INSPECTION
 CHECKLIST SHALL SHOW RESULTS FOR THE PROPOSED DESIGN
 WITH USER INPUTS TO THE COMPLIANCE SOFTWARE TO GENERATE
 THE RESULTS.
 4.A SITE-SPECIFIC ENERGY ANALYSIS REPORT THAT IS IN
 COMPLIANCE WITH SECTION R405.3.
 5.THE NAME OF THE INDIVIDUAL PERFORMING THE ANALYSIS
 AND GENERATING THE REPORT.
 6.THE NAME AND VERSION OF THE COMPLIANCE SOFTWARE TOOL.
  
 EXCEPTION: MULTIPLE ORIENTATIONS. WHEN AN OTHERWISE
 IDENTICAL BUILDING MODEL IS OFFERED IN MULTIPLE
 ORIENTATIONS, COMPLIANCE FOR ANY ORIENTATION SHALL BE
 PERMITTED BY DOCUMENTING THAT THE BUILDING MEETS THE
 PERFORMANCE REQUIREMENTS IN EACH OF THE FOUR CARDINAL
 (NORTH, EAST, SOUTH AND WEST) ORIENTATIONS, OR THE
 ?WORST? ORIENTATION. COMPLIANCE SOFTWARE TOOLS MAY
 CALCULATE THE ?WORST CASE? ORIENTATION BY ROTATING THE
 BUILDING THROUGH THE 4 OR 8 CARDINAL ORIENTATIONS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  
  
  