| 2019-07-11 12:32:18 | 2ND REVIEW: 19040126 |
| | |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS |
| | |
| | 1. A MIN OF 1 SINKS IN THE STUDIO ROOMS AND THE BREAK |
| | ROOM SINK SHALL COMPLY WITH FBC ACC 212.2/3 AND 606.2/3 |
| | SHT. A1.7 SHOWS DETAIL #2A AS COMPLIANT PLEASE INDICATE |
| | ON FLOOR PLAN WHICH STUDIO HAS COMPLIANT SINK WITH |
| | CLEAR FLOOR SPACE CLEAR OF SHAMPOO STATION. |
| | |
| | |
| | 5. SHT. P1.2 DETAIL FOR WASHING MACHINE BOX AIR HAMMER |
| | ARRESTORS REQUIRED AND REPLACE NOTE ON DETAIL CONFORMS |
| | TO FBC PL 2017 6TH EDITION NOT 2015 IPC |
| | PLEASE NOTE ON WATER ISOMETRIC AIR HAMMER ARRESTOR |
| | REQUIRED AT WASHING MACHINE AND QUICK CLOSING VALVES. |
| | |
| | 6.SHT. P1.3 SPLIT THE WATER AND SANITARY ISOMETRIC |
| | DRAWING AND ENLARGE IN ORDER TO DETERMINE CODE |
| | COMPLIANCE. PER WPB AMEND TO FBC 107.2.1 |
| | LABEL HOT AND COLD AND SHOW DIRECTION OF FLOW ON WATER |
| | ISOMETRIC DRAWING. |
| | |
| | |
| | 9. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PLACE NOT ON WATER |
| | ISOMETRIC. PER FBC PL 416.5 |
| | VALVE SHOWN ON SHT P1.1 PLUMBING EQUIPMENT SCHEDULE |
| | WATTS USG-B-M1 IS NOT LEAD FREE IT SHALL BE LFUSG-B-M1 |
| | OR EQUIVALENT |
| | |
| | NEW COMMENT: |
| | |
| | 1. LENT TRAP REQUIRED ON WASHING MACHINE DRAIN. PER FBC |
| | PL 1003.6 |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |