Plan Review Notes
Plan Review Notes For Permit 19040126
Permit Number 19040126
Review Stop B
Sequence Number 2
Notes
Date Text
2019-07-24 09:42:34PLAN
 REVIEW COMMENTS
 1500 ELIZABETH AVE. SUITE A
 LEVEL 3 ALTERATION
 CHANGE OF OCCUPANCY (S-2 TO B)
 FLOOD ZONE "AE", BFE 12.1' NAVD
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT COMPLIED. THE ELEVATION CERTIFICATE THAT WAS
 SUBMITTED IS NOT ACCEPTABLE. SUBMIT AN ELECTRONIC
 ELEVATION CERTIFICATE THAT HAS BEEN DIGITALLY SIGNED BY
 THE SURVEYOR OR A PAPER ONE WITH THE SURVEYOR'S
 ORIGINAL HANDWRITTEN SIGNATURE.
 THE PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA.
 BASED ON THE PBC PROPERTY APPRAISER'S IMPROVEMENT VALUE
 ($456,220.00) OF THE BUILDING, THE COST OF THE PROPOSED
 WORK ($835,735.00) EXCEEDS 50 PERCENT OF THE MARKET
 VALUE OF THE STRUCTURE AND IS A SUBSTANTIAL
 IMPROVEMENT. THEREFORE, THE RENOVATED BUILDING IS
 REQUIRED TO COMPLY WITH THE CURRENT CITY FLOOD
 ORDINANCE. THE LOWEST FLOOR ELEVATION AND ANY EQUIPMENT
 SERVICING THE BUILDING IS REQUIRED TO BE AT OR ABOVE
 12.1' + 2' FREE BOARD= 14.1" NAVD 88. BECAUSE THIS IS A
 COMMERCIAL BUILDING, IT CAN BE DRY FLOODPROOFED. SEE
 FEMA PUBLICATION FEMA P-758. FBC 1612.1
  
 2) NOT COMPLIED. THE ENERGY CODE COMPLIANCE FORM THAT
 WAS SUBMITTED IS NOT ACCEPTABLE. SUBMIT AN ENERGY CODE
 COMPLIANCE FORM THAT HAS BEEN DIGITALLY SIGNED BY THE
 SURVEYOR OR A PAPER ONE WITH THE ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE. SUBMIT THE REQUIRED DOCUMENTS TO
 SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION C401.2.
  
 3) NOT COMPLIED. PROVIDE A SURVEY OF THE PROPERTY TO
 CLARIFY THE ORIENTATION OF THE STRUCTURE AND VERIFY
 DISTANCES TO LOT LINES. FBC 107.2
  
 4) COMPLIED.
  
 5) NOT COMPLIED. THE UPLOADED PLAN SHEETS FOR S-1 AND
 S-2 ARE INCORRECTLY LABELED IN PROJECT DOX. THE PLANS
 ARE THE REVERSE OF THEIR PROJECT DOX TITLES. THE
 FOUNDATION PLAN ON THE ACTUAL PLAN SHEET S-1 IS NOT
 ORIENTED WITH THE COMPASS ROSE.
 ON SHEET S-1 THE COMPASS ROSE DOES NOT APPEAR TO BE
 ACCURATE. THE FRONT OF THE BUILDING FACES WEST AND ON
 SHEET S-1 IT IS INDICATED AS FACING SOUTH. FBC 107.2.1
  
 6) NOT COMPLIED. I MADE A MISTAKE AND TYPED IN THE
 WRONG PLAN SHEET. THE ELEVATIONS THAT NEED CORRECTIONS
 ARE ON SHEET A-3.0.1
 THE ELEVATIONS ON SHEET SP-1.0.0 APPEAR TO BE REVERSED.
 THE WEST ELEVATION SHOULD BE THE FRONT OF THE BUILDING
 WHICH FACES TOWARDS ELIZABETH AVE. FBC 107.2.1
  
 7) COMPLIED.
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10) COMPLIED.
  
 11) NOT COMPLIED. THE COMMON PATH OF TRAVEL IS SHOWN
 STARTING IN THE HALL. IT SHOULD START IN STUDIO 21 AT
 THE SAME PLACE THE TRAVEL DISTANCE STARTS. THIS WILL
 ADD APPROXIMATELY 17' TO THE 40'-4" THAT IS SHOWN.
 THE COMMON PATH OF TRAVEL IS NOT SHOWN CORRECTLY ON THE
 LIFE SAFETY PLAN. FBC 107.2 & CHAPTER 2 DEFINITIONS
 COMMON PATH OF EGRESS TRAVEL. THAT PORTION OF THE EXIT
 ACCESS TRAVEL DISTANCE MEASURED FROM THE MOST REMOTE
 POINT WITHIN A STORY TO THAT POINT WHERE THE OCCUPANTS
 HAVE SEPARATE AND DISTINCT ACCESS TO TWO EXITS OR EXIT
 ACCESS DOORWAYS.
  
 12) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 13) NEW COMMENT. WITHOUT THE SURVEY REQUESTED IN
 COMMENT NUMBER 3, IT IS NOT POSSIBLE FOR ME TO
 DETERMINE THAT THE REAR EXIT DISCHARGE PROVIDES A
 DIRECT AND UNOBSTRUCTED ACCESS TO A PUBLIC WAY AS
 REQUIRED BY FBC 1028.5. INDICATE HOW COMPLIANCE WILL BE
 ACHIEVED.
  
  