Plan Review Notes
Plan Review Notes For Permit 19040126
Permit Number 19040126
Review Stop P
Sequence Number 1
Notes
Date Text
2019-05-01 14:00:091ST REVIEW: 19040126
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. A MIN OF 1 SINKS IN THE STUDIO ROOMS AND THE BREAK
 ROOM SINK SHALL COMPLY WITH FBC ACC 212.2/3 AND 606.2/3
  
 2. SHT. A1.7 SHOW THE CLEAR FLOOR SPACES WITH
 DIMENSIONS FOR THE TOILET AND LAVATORY, PER FBC PL
 604.3.1 AND 606.2
  
 3. PLEASE SHOW COMPLIANCE FOR WATER FOUNTAIN PER FBC
 ACC 602
  
 4. SHT. A2.0 PLACE NOTE ON PLANS ALL VENT AND EXHAUST
 SHALL BE A MIN. OF 10' FROM ANY AIR INTAKES. FBC PL
 903.5 FBC M 501.3.1
  
 5. SHT. P1.2 DETAIL FOR WASHING MACHINE BOX AIR HAMMER
 ARRESTORS REQUIRED AND REPLACE NOTE ON DETAIL CONFORMS
 TO FBC PL 2017 6TH EDITION NOT 2015 IPC
  
 6.SHT. P1.3 SPLIT THE WATER AND SANITARY ISOMETRIC
 DRAWING AND ENLARGE IN ORDER TO DETERMINE CODE
 COMPLIANCE. PER WPB AMEND TO FBC 107.2.1
  
 7. SHT. P1.3 THE FLOOR DRAINS IN THE BATHROOMS AND IN
 FRONT OF WASHING MACHINES ARE NOT VENTED PROPERLY THE
 BUILDING DRAIN IS NOT A VENTED LINE THEY SHOULD CONECT
 TO WET VENT SYSTEM, BE VENTED SEPARATELY OR VENTED BY A
 SINK BRANCH THEY CANNOT BE VENTED BY WASHING MACHINE
 EITHER. PER FBC PL 901.2.1
  
 8. SHT. P1.3 PLEAS SHOW THE SHUT OFF VALVES ON THE
 DROPS AS REQUIRED. PER FBC PL 606.1(5)
  
 9. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PLACE NOT ON WATER
 ISOMETRIC. PER FBC PL 416.5
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]