| 2019-05-01 14:00:09 | 1ST REVIEW: 19040126 |
| | |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. A MIN OF 1 SINKS IN THE STUDIO ROOMS AND THE BREAK |
| | ROOM SINK SHALL COMPLY WITH FBC ACC 212.2/3 AND 606.2/3 |
| | |
| | 2. SHT. A1.7 SHOW THE CLEAR FLOOR SPACES WITH |
| | DIMENSIONS FOR THE TOILET AND LAVATORY, PER FBC PL |
| | 604.3.1 AND 606.2 |
| | |
| | 3. PLEASE SHOW COMPLIANCE FOR WATER FOUNTAIN PER FBC |
| | ACC 602 |
| | |
| | 4. SHT. A2.0 PLACE NOTE ON PLANS ALL VENT AND EXHAUST |
| | SHALL BE A MIN. OF 10' FROM ANY AIR INTAKES. FBC PL |
| | 903.5 FBC M 501.3.1 |
| | |
| | 5. SHT. P1.2 DETAIL FOR WASHING MACHINE BOX AIR HAMMER |
| | ARRESTORS REQUIRED AND REPLACE NOTE ON DETAIL CONFORMS |
| | TO FBC PL 2017 6TH EDITION NOT 2015 IPC |
| | |
| | 6.SHT. P1.3 SPLIT THE WATER AND SANITARY ISOMETRIC |
| | DRAWING AND ENLARGE IN ORDER TO DETERMINE CODE |
| | COMPLIANCE. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 7. SHT. P1.3 THE FLOOR DRAINS IN THE BATHROOMS AND IN |
| | FRONT OF WASHING MACHINES ARE NOT VENTED PROPERLY THE |
| | BUILDING DRAIN IS NOT A VENTED LINE THEY SHOULD CONECT |
| | TO WET VENT SYSTEM, BE VENTED SEPARATELY OR VENTED BY A |
| | SINK BRANCH THEY CANNOT BE VENTED BY WASHING MACHINE |
| | EITHER. PER FBC PL 901.2.1 |
| | |
| | 8. SHT. P1.3 PLEAS SHOW THE SHUT OFF VALVES ON THE |
| | DROPS AS REQUIRED. PER FBC PL 606.1(5) |
| | |
| | 9. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PLACE NOT ON WATER |
| | ISOMETRIC. PER FBC PL 416.5 |
| | |