| 2019-05-03 15:23:52 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19040126 |
| | 5/3/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M1.1 & M1.2: AN EXHAUST VENTILATION SYSTEM AT |
| | A RATE OF 0.6 CFMS PER SQUARE FOOT IS REQUIRED FOR THE |
| | BEAUTY SALON PER TABLE 403.3.1.1 FBC M. PLEASE REVISE |
| | THE PLANS TO SHOW THE REQUIRED SYSTEM, AND PROVIDE |
| | CALCULATIONS, SPECIFICATIONS AND EQUIPMENT SCHEDULES. |
| | |
| | 2) M1.1 & M1.2: PROVIDE OUTDOOR AIR CALCULATIONS FOR |
| | ALL OCCUPIED ROOMS AND SPACES OF THE SALON PER TABLE |
| | 403.3.1.1. FBC M. DUE TO THE AMOUNT OF EXHAUST REQUIRED |
| | FOR THE SALON, ALONG WITH THE LAUNDRY EXHAUST PLEASE |
| | PROVIDE AIR BALANCE CALCULATIONS. |
| | |
| | 3) M1.1 & M1.2: PROVIDE AUTOMATICALLY CONTROLLED |
| | SHUTOFF DAMPERS FOR THE O/A INTAKES- SECTION C403.2.4.3 |
| | FBC-17 ENERGY CONSERVATION. |
| | |
| | 4) M1.1 & M1.2: DUCT SMOKE DETECTORS ARE REQUIRED IN |
| | THE SUPPLY AIR SYSTEMS OF EACH 5-TON AC SYSTEM PER |
| | SECTION 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION |
| | CAN BE APPLIED IF THE MANUFACTURER'S SPECIFICATIONS |
| | INDICATE SYSTEMS ARE NOT CAPABLE OF PRODUCING OVER 2000 |
| | CFMS OF SUPPLY AIR. |
| | |
| | 5) M1.1 & M1.2: THE PLAN APPEARS TO INDICATE AN ABOVE |
| | CEILING PLENUM. PLEASE PLACE A NOTE ON THE PLAN TO |
| | CLARIFY, AND ALSO NOTE THAT THE CORRIDORS SHALL NOT BE |
| | USED AS A MEANS OF RETURN AIR VIA TRANSFER DUCTS OR |
| | JUMPERS FORM THE ROOMS. |
| | |
| | 6) M1.1 & M1.2: SUBMIT MANUFACTURER?S SPECIFICATIONS |
| | FOR THE DRYESR, AND PROVIDE A DRYER EXHAUST DIAGRAM |
| | SHOWING THE TOTAL RUN LENGTH OF THE DUCTS FROM THE |
| | DRYER OUTLEST TO THE TERMINATION LOCATION- SECTIONS |
| | 504.1 AND 504.8.4 FBC M. PLEASE NOTE THAT MAKEUP AIR IS |
| | REQUIRED FOR DRYERS EXHAUSTING MORE THAN 200 CFMS- |
| | SECTION 504.6 FBC M. |
| | |
| | 7) M1.1 & M1.2: PLEASE VERIFY THE INSTALLATION |
| | LOCATIONS OF THE GAS-FRIED WATER HEATERS ARE NOT IN A |
| | RETURN AIR PLENUM SPACE- SECTION 602.1 FBC M. A) |
| | INDICATE HOW COMBUSTION AIR WILL BE PROVIDED FOR THE |
| | WATER HEATERS AND PROVIDE CALCU;LATIONS- SECTION 304 |
| | FBC FG. B) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | WATER HEATERS AND FLUE VENT- SECTION 624.1 FBC FG. |
| | |
| | 8) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC. |
| | |
| | 9) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF |
| | THE RTU'S- SECTION 310.15 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |