2019-05-03 15:23:521ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19040126
 5/3/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M1.1 & M1.2: AN EXHAUST VENTILATION SYSTEM AT
 A RATE OF 0.6 CFMS PER SQUARE FOOT IS REQUIRED FOR THE
 BEAUTY SALON PER TABLE 403.3.1.1 FBC M. PLEASE REVISE
 THE PLANS TO SHOW THE REQUIRED SYSTEM, AND PROVIDE
 CALCULATIONS, SPECIFICATIONS AND EQUIPMENT SCHEDULES.
  
 2) M1.1 & M1.2: PROVIDE OUTDOOR AIR CALCULATIONS FOR
 ALL OCCUPIED ROOMS AND SPACES OF THE SALON PER TABLE
 403.3.1.1. FBC M. DUE TO THE AMOUNT OF EXHAUST REQUIRED
 FOR THE SALON, ALONG WITH THE LAUNDRY EXHAUST PLEASE
 PROVIDE AIR BALANCE CALCULATIONS.
  
 3) M1.1 & M1.2: PROVIDE AUTOMATICALLY CONTROLLED
 SHUTOFF DAMPERS FOR THE O/A INTAKES- SECTION C403.2.4.3
 FBC-17 ENERGY CONSERVATION.
  
 4) M1.1 & M1.2: DUCT SMOKE DETECTORS ARE REQUIRED IN
 THE SUPPLY AIR SYSTEMS OF EACH 5-TON AC SYSTEM PER
 SECTION 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION
 CAN BE APPLIED IF THE MANUFACTURER'S SPECIFICATIONS
 INDICATE SYSTEMS ARE NOT CAPABLE OF PRODUCING OVER 2000
 CFMS OF SUPPLY AIR.
  
 5) M1.1 & M1.2: THE PLAN APPEARS TO INDICATE AN ABOVE
 CEILING PLENUM. PLEASE PLACE A NOTE ON THE PLAN TO
 CLARIFY, AND ALSO NOTE THAT THE CORRIDORS SHALL NOT BE
 USED AS A MEANS OF RETURN AIR VIA TRANSFER DUCTS OR
 JUMPERS FORM THE ROOMS.
  
 6) M1.1 & M1.2: SUBMIT MANUFACTURER?S SPECIFICATIONS
 FOR THE DRYESR, AND PROVIDE A DRYER EXHAUST DIAGRAM
 SHOWING THE TOTAL RUN LENGTH OF THE DUCTS FROM THE
 DRYER OUTLEST TO THE TERMINATION LOCATION- SECTIONS
 504.1 AND 504.8.4 FBC M. PLEASE NOTE THAT MAKEUP AIR IS
 REQUIRED FOR DRYERS EXHAUSTING MORE THAN 200 CFMS-
 SECTION 504.6 FBC M.
  
 7) M1.1 & M1.2: PLEASE VERIFY THE INSTALLATION
 LOCATIONS OF THE GAS-FRIED WATER HEATERS ARE NOT IN A
 RETURN AIR PLENUM SPACE- SECTION 602.1 FBC M. A)
 INDICATE HOW COMBUSTION AIR WILL BE PROVIDED FOR THE
 WATER HEATERS AND PROVIDE CALCU;LATIONS- SECTION 304
 FBC FG. B) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 WATER HEATERS AND FLUE VENT- SECTION 624.1 FBC FG.
  
 8) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC.
  
 9) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE RTU'S- SECTION 310.15 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  