| Date |
Text |
| 2019-05-06 11:57:49 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | PG.E1.1 |
| | |
| | AIC RATING FOR SERVICE SHOW CALCULATION. |
| | |
| | 110.24 AVAILABLE FAULT CURRENT |
| | ( A) FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN |
| | DWELLING |
| | UNITS SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE |
| | MAXIMUM |
| | AVAILABLE FAULT CURRENT. THE FIELD MARKING(S) SHALL |
| | INCLUDE THE DATE |
| | THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE OF |
| | SUFFICIENT |
| | DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. |
| | |
| | SWITCHGEAR TO CONTAIN ARC FLASH INFORMATION AND LABELS |
| | 110.16 ARC-FLASH HAZARD WARNING |
| | ELECTRICAL EQUIPMENT, SUCH AS SWITCHBOARDS, SWITCHGEAR, |
| | PANELBOARDS, |
| | INDUSTRIAL CONTROL PANELS, METER SOCKET ENCLOSURES, |
| | AND MOTOR CONTROL CENTERS, THAT ARE IN OTHER THAN |
| | DWELLING UNITS, |
| | AND ARE LIKELY TO REQUIRE EXAMINATION, ADJUSTMENT, |
| | SERVICING, OR |
| | MAINTENANCE WHILE ENERGIZED, SHALL BE FIELD OR FACTORY |
| | MARKED |
| | TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC |
| | FLASH HAZARDS. |
| | THE MARKING SHALL MEET THE REQUIREMENTS IN 110.21(B) |
| | AND |
| | SHALL BE LOCATED SO AS TO BE CLEARLY VISIBLE TO |
| | QUALIFIED PERSONS |
| | BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR |
| | MAINTENANCE OF |
| | THE EQUIPMENT. |
| | |
| | |
| | PG.E1.2 |
| | |
| | ALL OUTLETS WITHIN 6' OF A SINK TO BE GFCI RPOTECTED. |
| | |
| | 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION |
| | FOR PERSONNEL |
| | (B) OTHER THAN DWELLING UNITS. ALL 125-VOLT, |
| | SINGLE-PHASE, |
| | 15- AND 20-AMPERE RECEPTACLES INSTA LLED IN THE |
| | LOCATIONS SPECIFIED |
| | IN 210.8(B)(1) THROUGH (8) SHALL HAVE GROUND-FAULT |
| | CIRCUITINTERRUPTER |
| | PROTECTION FOR PERSONNEL. |
| | (5) SINKS ? WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 |
| | M (6 FT) |
| | OF THE OUTSIDE EDGE OF THE SINK. |
| | |
| | ALL LOW VOLTAGE WORK TO BE PERMITTED SEPARATELY. |
| | CCTV |
| | |
| | |
| | PG. E1.4 |
| | |
| | EACH ROOM HAS A BLACK SQUARE WHAT DOES THIS STAND FOR? |
| | SYMBOL |
| | |
| | PROVIDE INTERIOR LIGHTING CALCULATION SHOWING |
| | COMPLIANCE WITH THE FBC ENERGY CODE. FBC CE 405.5 |
| | |
| | PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED IN |
| | THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE |
| | OCCUPANCY SENSORS REQUIRED. FBC CE 405.2.2, 405.2.2.2 |