Plan Review Notes
Plan Review Notes For Permit 19040126
Permit Number 19040126
Review Stop E
Sequence Number 1
Notes
Date Text
2019-05-06 11:57:49FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PG.E1.1
  
 AIC RATING FOR SERVICE SHOW CALCULATION.
  
 110.24 AVAILABLE FAULT CURRENT
 ( A) FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN
 DWELLING
 UNITS SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE
 MAXIMUM
 AVAILABLE FAULT CURRENT. THE FIELD MARKING(S) SHALL
 INCLUDE THE DATE
 THE FAULT-CURRENT CALCULATION WAS PERFORMED AND BE OF
 SUFFICIENT
 DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED.
  
 SWITCHGEAR TO CONTAIN ARC FLASH INFORMATION AND LABELS
 110.16 ARC-FLASH HAZARD WARNING
 ELECTRICAL EQUIPMENT, SUCH AS SWITCHBOARDS, SWITCHGEAR,
 PANELBOARDS,
 INDUSTRIAL CONTROL PANELS, METER SOCKET ENCLOSURES,
 AND MOTOR CONTROL CENTERS, THAT ARE IN OTHER THAN
 DWELLING UNITS,
 AND ARE LIKELY TO REQUIRE EXAMINATION, ADJUSTMENT,
 SERVICING, OR
 MAINTENANCE WHILE ENERGIZED, SHALL BE FIELD OR FACTORY
 MARKED
 TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC
 FLASH HAZARDS.
 THE MARKING SHALL MEET THE REQUIREMENTS IN 110.21(B)
 AND
 SHALL BE LOCATED SO AS TO BE CLEARLY VISIBLE TO
 QUALIFIED PERSONS
 BEFORE EXAMINATION, ADJUSTMENT, SERVICING, OR
 MAINTENANCE OF
 THE EQUIPMENT.
  
  
 PG.E1.2
  
 ALL OUTLETS WITHIN 6' OF A SINK TO BE GFCI RPOTECTED.
  
 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION
 FOR PERSONNEL
 (B) OTHER THAN DWELLING UNITS. ALL 125-VOLT,
 SINGLE-PHASE,
 15- AND 20-AMPERE RECEPTACLES INSTA LLED IN THE
 LOCATIONS SPECIFIED
 IN 210.8(B)(1) THROUGH (8) SHALL HAVE GROUND-FAULT
 CIRCUITINTERRUPTER
 PROTECTION FOR PERSONNEL.
 (5) SINKS ? WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8
 M (6 FT)
 OF THE OUTSIDE EDGE OF THE SINK.
  
 ALL LOW VOLTAGE WORK TO BE PERMITTED SEPARATELY.
 CCTV
  
  
 PG. E1.4
  
 EACH ROOM HAS A BLACK SQUARE WHAT DOES THIS STAND FOR?
 SYMBOL
  
 PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FBC ENERGY CODE. FBC CE 405.5
  
 PROVIDE THE ADDITIONAL LIGHTING CONTROLS STIPULATED IN
 THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 OCCUPANCY SENSORS REQUIRED. FBC CE 405.2.2, 405.2.2.2