Plan Review Notes For Permit 19040111
Permit Number 19040111
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-04-11 15:00:49THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 301 - WITHIN THE INTERIOR FINSIHES BOX THERE
 ARE INCORRECT REFERNECES TO MERCANTILE &
 NON-SPRINKLERED
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 DETAILS.
  
  
  
 2) SHEET A 301 & 302 - THERE ARE NO INDICATIONS OF FIRE
 SPRINKLER WORK DUE TO RECONSTRUCTION.
  
 ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS BY CERTIFIED
 FIRE SPRINKLER CONTRACTORS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 3) ELECTRICAL SHEETS - THERE ARE NO INDICATIONS OF FIRE
 ALARM EQUIPMENT OR RELOCATION DUE TO CONSTRUCTION.
  
 ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS BY CERTIFIED FIRE
 ALARM CONTRACTORS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 4) ELECTRICAL SHEETS - THERE ARE NO INDICATIONS OF EXIT
 SIGN LOCATIONS/INSTALLATIONS THAT COINCIDE WITH THE
 LIFE SAFETY SHEETS.
  
 PLEASE REVIEW AND CORRECT AND/OR NOTE WHETHER EXXISTING
 OR NEW.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL