| Date |
Text |
| 2019-05-06 08:58:35 | RESIDENTIAL (R3) RE-ROOF, SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL1654-R22 |
| | SUBMITTED: |
| | A) SELECTED ASSEMBLY W-104 DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES. NEED TO PROVIDE SIGNED |
| | AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY |
| | LIMITATION #5.7 ON PAGE 5 OF 6 OF PRODUCT APPROVAL |
| | SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN |
| | PRESSURES REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. |
| | NOTE: CONTRACTOR MAY SELECT ANOTHER ASSEMBLY THAT MEETS |
| | THE DESIGN PRESSURES FOR ALL ROOF ZONES AND RAS 117 |
| | CALCULATIONS ARE NOT REQUIRED. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | B) PROVIDE CURRENT FLORIDA PRODUCT APPROVAL. CURRENT |
| | FLORIDA PRODUCT APPROVAL IS FL1654-R23 NOT FL1654-R22. |
| | FAC 61G20-3.001. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | C) PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL. PRODUCT |
| | APPROVAL SUBMITTED IS MISSING THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE. THIS PAGE IS REQUIRED BECAUSE IT |
| | SHOWS THE CURRENT CODE VERSION AND THE PRODUCT APPROVAL |
| | STATUS. CHAPTER 553 F.S. AND FAC 61G20-3.001. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 2- METAL ROOFING PANELS WERE CHANGED TO SHINGLES |
| | BECAUSE HISTORIC DOESN'T ALLOW METAL ROOFING PANELS. |
| | THE FOLLOWING REQUIRED INFORMATION WAS NOT SUBMITTED AS |
| | REQUESTED ON PREVIOUS CHECKLIST: |
| | |
| | A) SPECIFY ROOF PITCH AND ROOF MEAN ROOF HEIGHT AS |
| | REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS AND |
| | SEC. R905.10.2 FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | B) PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL. PRODUCT |
| | APPROVAL SUBMITTED IS MISSING THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE. THIS PAGE IS REQUIRED BECAUSE IT |
| | SHOWS THE CURRENT CODE VERSION AND THE PRODUCT APPROVAL |
| | STATUS. CHAPTER 553 F.S. AND FAC 61G20-3.001. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 3- ROOF UNDERLAYMENT FL21895-R2 SUBMITTED: PROVIDE |
| | COMPLETE FLORIDA PRODUCT APPROVAL. PRODUCT APPROVAL |
| | SUBMITTED IS MISSING THE FLORIDA PRODUCT APPROVAL COVER |
| | PAGE. THIS PAGE IS REQUIRED BECAUSE IT SHOWS THE |
| | CURRENT CODE VERSION AND THE PRODUCT APPROVAL STATUS. |
| | CHAPTER 553 F.S. AND FAC 61G20-3.001. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 4- THERE IS MORE THAN ONE STRUCTURE IN THIS PROPERTY. |
| | PROVIDE MAP OR SKETCH SHOWING LOCATION OF AREA OF WORK |
| | AND SQUARE FOOTAGE OF EACH AREA (PITCH AND FLAT) AS |
| | REQUIRED BY CITY POLICY FOR ALL ROOFING PERMITS AND |
| | SEC. 107.02.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. VALUATION WILL BE RE-EVALUATED ONCE THE |
| | ROOFING AREAS ARE PROVIDED. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |