| 2020-08-10 16:02:21 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19040094 |
| | ADD: 905 9TH ST. / PCN: 74-43-43-16-01-140-0130 |
| | CONT: SUNRISE CITY |
| | TEL: 561-350-5866 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: MON. AUGUST 10TH/2020 |
| | ACTION: DENIED |
| | |
| | 1-6) SEMI- COMPLIED. THIS IS THE 3RD REVIEW WITH A SET |
| | OF PLANS THAT ARE ORIGINAL SIGNED AND SEALED PLANS. |
| | THE SHEET A-0.3 INDICATES BETWEEN THE R2 OCCUPANCIES |
| | THERE IS A ONE HOUR FIRE RATED WALL ALL THE WAY TO THE |
| | ROOF DECK. THE PLANS ARE SILENT AS TO WHAT MATERIALS |
| | ARE GOING TO MAKE UP THE ONE HOUR FIRE RATING. SHEET |
| | A-3.1 INDICATES THE TENANT SEPARATION WALLS WITH A WALL |
| | TYPE IDENTIFICATION TAG, (F) 1 5/8 METAL FURRING WALL. |
| | NOT METAL STUD WALL BUT ONLY METAL FURRING, METAL |
| | FURRING IS USUALLY APPLIED TO CONCRETE BLOCK |
| | WALLSPLEASE PROVIDE EITHER A UL WALL LISTING AND SHOW |
| | THE WALL COMPONENTS OR GYPSUM ASSOCIATION WALL LISTING |
| | AND THEIR COMPONENTS AND HOURLY FIRE RATING. PLEASE |
| | SHOW COMPLIANCE WITH THE 2017 FBC-B SECTION 420.2 |
| | SEPARATION WALLS/ FIRE PARTITIONS. THE COMMON WALL |
| | BETWEEN THE R-2 UNITS NEEDS TO SHOW COMPLIANCE WITH THE |
| | 2017 FBC-B SECTION 708, FIRE PARTITIONS. PLEASE SHOW |
| | COMPLIANCE WITH 2017 FBC-B SECTION: |
| | 708.3 FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL |
| | HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR. |
| | 708.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM THE |
| | TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW |
| | TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB |
| | OR DECK ABOVE OR TO THE FIRE-RESISTANCE-RATED |
| | FLOOR/CEILING OR ROOF/CEILING ASSEMBLY ABOVE, AND SHALL |
| | BE SECURELY ATTACHED THERETO. |
| | |
| | 6) 3RD REQUEST. THERE SEEMS TO BE A DISCREPANCY WITHIN |
| | THE SET OF PLANS. SHEET A-0.4 THE DEMO PLAN STATES ALL |
| | EXTERIOR WINDOWS AND DOORS TO REMAIN. IDENTIFIED THE |
| | COMMENT WITH RED CIRCLEE. WHEREAS SHEET A-3.1 NOTE # 2 |
| | IN THE LOWER LEFT HAND CORNER OF THE SHEET INDICATES |
| | THE EXISTING WINDOWS AND DOORS ARE TO BE REPLACED |
| | IDENTIFIED WITH RED CIRCLE. . 107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED, DISCREPANCY. |
| | |
| | 6A) 3RD REQUEST. THE WIND DESIGN CRITERIA HAS BEEN |
| | PROVIDED AND ASSOCIATED VULT PRESSURES. PLEASE PROVIDE |
| | THE ASSOCIATED PRESSURES IN VASD SINCE THE PRODUCT |
| | APPROVALS HAVE ALL BEEN TESTED IN VASD AND RECORDED |
| | RESULT ARE IN VASD. 1609.3.1 WIND SPEED CONVERSION VULT |
| | TO VASD. |
| | |
| | 6B) 3RD REQUEST. IF WINDOWS AND DOORS ARE TO BE |
| | REPLACED PLEASE SHOW COMPLIANCE WITH: 2017 FBC-B |
| | 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| | NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (E) SHUTTERS |
| | |
| | 6C) 3RD REQUEST. IDENTIFY GLAZING/ MULLIONS. THE |
| | SUBMITTED PRODUCT APPROVALS THE ELEMENTS LISTED BELOW |
| | ARE NOT IDENTIFIED. PLEASE IDENTIFY ON THE PRODUCT |
| | APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND |
| | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL |
| | PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING |
| | WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH |
| | IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING |
| | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| | THE TESTS. |
| | |
| | 6D)3RD REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| | ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |