| 2019-12-23 09:41:10 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19040094 |
| | 12/23/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW STILL |
| | EXIST. |
| | |
| | 1) THE MECHANICAL PLANS FOR THE NEW AC SYSTEMS ARE |
| | INCOMPLETE- SECTION 107.2.1 WPB. PLEASE PROVIDE: |
| | |
| | A) DUCT LAYOUT PLANS FOR EACH OF THE THREE APARTMENTS- |
| | SECTION 603 FBC M. (INCOMPLETE AC PLANS HAVE BEEN |
| | SUBMITTED. PROVIDE- AC EQUIPMENT SCHEDULES ON THE |
| | PLANS, SHOW THE SUPPLY CFMS AT EACH DIFFUSER, AND SHOW |
| | RETURN AIR FROM THE BEDROOMS. |
| | B) AC COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | SYSTEMS- SECTION R503.2 FBC EC. (NOT PROVIDED) |
| | C) ENERGY CALCULATIONS FOR THE NEW CONDITIONED SPACES- |
| | SECTION R403.6.1 FBC EC. (NOT PROVIDED) |
| | D) VENTILATION CALCULATIONS PER TABLE 403.3.1.1 FOR |
| | EACH APARTMENT, AND INDICATE HOW OUTDOOR AIR IS BEING |
| | PROVIDED AND AUTOMATICALLY CONTROLLED- SECTION |
| | C403.2.4.3 FBC EC. (NOT PROVIDED) |
| | D) EXTERIOR CONDENSER MOUNTING DETAILS- SECTION 301.15 |
| | FBC M. (OK) |
| | E) CONDENSATE DISPOSAL PLANS- SECTION 307.2.1 FBC M. |
| | (NOT PROVIDED) |
| | |
| | 2) PLEASE NOTE THAT LOUVERED AC CLOSET DOORS USED FOR |
| | RETURN AIR SHALL BE NON-COMBUSTIBLE PER SECTION 602 FBC |
| | M. (OK) |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |