| 2019-12-17 14:54:21 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19040094 |
| | ADD: 905 9TH ST. / PCN: 74-43-43-16-01-140-0130 |
| | CONT: SUNRISE CITY |
| | TEL: 561-350-5866 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. DEC. 17/2019 |
| | ACTION: DENIED |
| | |
| | 1-6) SEMI- COMPLIED. THIS IS THE 1ST REVIEW WITH A SET |
| | OF PLANS THAT ARE ORIGINAL SIGNED AND SEALED PLANS. |
| | THE SHEET A-0.3 INDICATES BETWEEN THE R2 OCCUPANCIES |
| | THERE IS A ONE HOUR FIRE RATED WALL ALL THE WAY TO THE |
| | ROOF DECK. THE PLANS ARE SILENT AS TO WHAT MATERIALS |
| | ARE GOING TO MAKE UP THE ONE HOUR FIRE RATING. SHEET |
| | A-3.1 INDICATES THE TENANT SEPARATION WALLS WITH A WALL |
| | TYPE IDENTIFICATION TAG, (F) 1 5/8 METAL FURRING. |
| | PLEASE PROVIDE EITHER A UL WALL LISTING AND SHOW THE |
| | WALL COMPONENTS OR GYPSUM ASSOCIATION WALL LISTING AND |
| | THEIR COMPONENTS AND HOURLY FIRE RATING. PLEASE SHOW |
| | COMPLIANCE WITH THE 2017 FBC-B SECTION 420.2 SEPARATION |
| | WALLS/ FIRE PARTITIONS. THE COMMON WALL BETWEEN THE R-2 |
| | UNITS NEEDS TO SHOW COMPLIANCE WITH THE 2017 FBC-B |
| | SECTION 708, FIRE PARTITIONS. PLEASE SHOW COMPLIANCE |
| | WITH 2017 FBC-B SECTION: |
| | 708.3 FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL |
| | HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR. |
| | 708.4 CONTINUITY. FIRE PARTITIONS SHALL EXTEND FROM THE |
| | TOP OF THE FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW |
| | TO THE UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB |
| | OR DECK ABOVE OR TO THE FIRE-RESISTANCE-RATED |
| | FLOOR/CEILING OR ROOF/CEILING ASSEMBLY ABOVE, AND SHALL |
| | BE SECURELY ATTACHED THERETO. |
| | |
| | 6) THERE SEEMS TO BE A DISCREPANCY WITHIN THE SET OF |
| | PLANS. SHEET A-0.4 THE DEMO PLAN STATES ALL EXTERIOR |
| | WINDOWS AND DOORS TO REMAIN. WHEREAS SHEET A-3.2 NOTE # |
| | 2 IN THE LOWER LEFT HAND CORNER OF THE SHEET INDICATES |
| | THE EXISTING WINDOWS AND DOORS ARE TO BE REPLACED. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED, |
| | DISCREPANCY. |
| | |
| | 6A) THE WIND DESIGN CRITERIA HAS BEEN PROVIDED AND |
| | ASSOCIATED VULT PRESSURES. PLEASE PROVIDE THE |
| | ASSOCIATED PRESSURES IN VASD SINCE THE PRODUCT |
| | APPROVALS HAVE ALL BEEN TESTED IN VASD AND RECORDED |
| | RESULT ARE IN VASD. 1609.3.1 WIND SPEED CONVERSION VULT |
| | TO VASD. |
| | |
| | 6B) IF WINDOWS AND DOORS ARE TO BE REPLACED PLEASE SHOW |
| | COMPLIANCE WITH: 2017 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (E) SHUTTERS |
| | |
| | 6C) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT |
| | APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED. |
| | PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| | SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| | TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| | OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 6D) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |