| 2019-04-23 15:52:08 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | BE ADVISED THAT THE CURRENT PLAN IS SUBSTANTIALLY |
| | LACKING OF INFORMATION. THEREFORE, THERE MAY BE |
| | ADDITIONAL COMMENTS FOR SECOND REVIEW THAT ARE NOT |
| | ADDRESSED IN THIS REVIEW. |
| | |
| | 1. PROVIDE COMPLETE ELECTRICAL PLAN FOR REVIEW, |
| | DETAILING ALL WORK AS DESCRIBED IN PROVIDED CONTRACT. |
| | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A LICENSED |
| | DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL |
| | CONTRACTOR QUALIFIER. FS 471.003(2)(H); 471.025; WPB |
| | FBC 107.2.1, 107.3.5 |
| | 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| | 250.50, 250.94, 408.30 |
| | 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30 |
| | 4. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY |
| | NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR |
| | THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE |
| | APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12, |
| | 210.19, 210.20, 215.5, 408.4 |
| | 5. PLAN SEEMS TO INDICATE THERE WILL BE A NEW |
| | ELECTRICAL SERVICE. PROVIDE AVAILABLE SHORT CIRCUIT |
| | CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE |
| | POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT |
| | CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC |
| | RATING OF THE SERVICE EQUIPMENT IS ADEQUATE. PROVIDE |
| | AIC RATING OF ALL ELECTRICAL SERVICE EQUIPMENT AND |
| | PANELS. NEC 110.3, 110.9, 110.10 |
| | 6. THE WEST PALM BEACH AMENDMENTS TO THE FBC 2017 6TH |
| | ED, CHAPTER 1, STATE THE FOLLOWING: QUALITY OF BUILDING |
| | PLANS. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 |
| | INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER |
| | ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH |
| | THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS |
| | AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO |
| | ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE |
| | SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, |
| | OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT. PROVIDE |
| | PLANS PER THIS REQUIREMENT. WPB FBC 107.2.1.3 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |