Plan Review Notes
Plan Review Notes For Permit 19040094
Permit Number 19040094
Review Stop E
Sequence Number 1
Notes
Date Text
2019-04-23 15:52:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 BE ADVISED THAT THE CURRENT PLAN IS SUBSTANTIALLY
 LACKING OF INFORMATION. THEREFORE, THERE MAY BE
 ADDITIONAL COMMENTS FOR SECOND REVIEW THAT ARE NOT
 ADDRESSED IN THIS REVIEW.
  
 1. PROVIDE COMPLETE ELECTRICAL PLAN FOR REVIEW,
 DETAILING ALL WORK AS DESCRIBED IN PROVIDED CONTRACT.
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A LICENSED
 DESIGN PROFESSIONAL OR SIGNED BY THE ELECTRICAL
 CONTRACTOR QUALIFIER. FS 471.003(2)(H); 471.025; WPB
 FBC 107.2.1, 107.3.5
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 4. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 210.19, 210.20, 215.5, 408.4
 5. PLAN SEEMS TO INDICATE THERE WILL BE A NEW
 ELECTRICAL SERVICE. PROVIDE AVAILABLE SHORT CIRCUIT
 CALCULATION FOR SERVICE INCLUDING INFORMATION FROM THE
 POWER COMPANY STATING WHAT THE AVAILABLE SHORT CIRCUIT
 CURRENT IS FOR THE SERVICE TO CONFIRM THE STATED AIC
 RATING OF THE SERVICE EQUIPMENT IS ADEQUATE. PROVIDE
 AIC RATING OF ALL ELECTRICAL SERVICE EQUIPMENT AND
 PANELS. NEC 110.3, 110.9, 110.10
 6. THE WEST PALM BEACH AMENDMENTS TO THE FBC 2017 6TH
 ED, CHAPTER 1, STATE THE FOLLOWING: QUALITY OF BUILDING
 PLANS. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8
 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER
 ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE
 SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY,
 OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT. PROVIDE
 PLANS PER THIS REQUIREMENT. WPB FBC 107.2.1.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  