| 2019-07-09 09:54:12 | PLUMBING HAS PASSED FINAL INSPECTION. |
| 2019-04-09 15:51:36 | 1ST REVIEW: 19031092 |
| | |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. 3.1P THE SANITARY FOR THE SINKS IN TREATMENT |
| | ROOM 11+12 IS STILL SHOWING BACK TO BACK SINKS IT |
| | SHOULD MATCH FLOOR PLAN WITH TO SINGLE SINK PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC107.2.1 |
| | 2. SHT. 3.2P THE SANITARY ISOMETRIC IS SHOWING BACK TO |
| | BACK SINKS FOR ROOM 11+12 IT SHOULD BE SHOWING SINGLE |
| | SINKS. TO MATCH FLOOR PLAN PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC107.2.1 |
| | 3. SHT. 3.2P THE WATER ISOMETRIC IS MISSING PIPING FOR |
| | A SINK FOR ROOM 12 IT SHOULD BE SHOWING 2 SINGLE SINKS. |
| | TO MATCH FLOOR PLAN PLEASE CLARIFY. PER WPB AMEND TO |
| | FBC107.2.1 |
| | 4. THE LAVATORY,S IN THE BATHROOMS ARE REQUIRED TI HAVE |
| | TEMPERED WATER WITH A TEMPERATURE BELOW 110 DEQ. THE |
| | WASHING MACHINE AND THE OTHER SINKS ARE REQUIRED TO |
| | HAVE HOT WATER ABOVE 110 DEQ. THE PLAN SHOWS A SINGLE |
| | TEMPERING VALVE HOW WILL THIS BE ACHIEVED WITH A SINGLE |
| | TEMPERATURE LIMITING DEVICE AND A SINGLE LINE SYSTEM |
| | PLEASE CLARIFY. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |