Plan Review Notes
Plan Review Notes For Permit 19040018
Permit Number 19040018
Review Stop P
Sequence Number 1
Notes
Date Text
2019-07-09 09:54:12PLUMBING HAS PASSED FINAL INSPECTION.
2019-04-09 15:51:361ST REVIEW: 19031092
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. 3.1P THE SANITARY FOR THE SINKS IN TREATMENT
 ROOM 11+12 IS STILL SHOWING BACK TO BACK SINKS IT
 SHOULD MATCH FLOOR PLAN WITH TO SINGLE SINK PLEASE
 CLARIFY. PER WPB AMEND TO FBC107.2.1
 2. SHT. 3.2P THE SANITARY ISOMETRIC IS SHOWING BACK TO
 BACK SINKS FOR ROOM 11+12 IT SHOULD BE SHOWING SINGLE
 SINKS. TO MATCH FLOOR PLAN PLEASE CLARIFY. PER WPB
 AMEND TO FBC107.2.1
 3. SHT. 3.2P THE WATER ISOMETRIC IS MISSING PIPING FOR
 A SINK FOR ROOM 12 IT SHOULD BE SHOWING 2 SINGLE SINKS.
 TO MATCH FLOOR PLAN PLEASE CLARIFY. PER WPB AMEND TO
 FBC107.2.1
 4. THE LAVATORY,S IN THE BATHROOMS ARE REQUIRED TI HAVE
 TEMPERED WATER WITH A TEMPERATURE BELOW 110 DEQ. THE
 WASHING MACHINE AND THE OTHER SINKS ARE REQUIRED TO
 HAVE HOT WATER ABOVE 110 DEQ. THE PLAN SHOWS A SINGLE
 TEMPERING VALVE HOW WILL THIS BE ACHIEVED WITH A SINGLE
 TEMPERATURE LIMITING DEVICE AND A SINGLE LINE SYSTEM
 PLEASE CLARIFY.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]