Plan Review Notes
Plan Review Notes For Permit 19040009
Permit Number 19040009
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-17 10:46:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCC = WEST PALM BEACH CROSS CONNECTION CONTROL
 MANUAL
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW
 PLUMBING COMMEMTS: DENIED
 1. PROVIDE SPEC AND DETAIL OF FIRE RATED ASSEMBLIES FOR
 FLOOR AND WALL PENETRATIONS TO SUPPORT PLUMBING GENERAL
 NOTE 13 PER WPB FBC 107.2.1.
 2. P0.1, PLUMBING MATERIALS-DOMESTIC WATER, NOTE 3;
 REVISE NOTE TO REFLECT 2017 FBC PER WPB FBC 107.2.1.
 3. PER WPB FBC 107.3.5.3, THIS OCCUPANCY DOES NOT MEET
 THE CRITERIA FOR RESIDENTIAL (ONE AND TWO FAMILY) AND
 MUST COMPLY WITH THE REQUIREMENTS OF FBC PL, NOT FBC
 RES.PER WPB FBC 107.2.1, ON P0.1, REVISE PLUMBING
 FIXTURE LIST NOTES 4 AND 5 TO REFLECT 2017 FBC PL CODE
 WITH APPLICABLE SECTIONS.
 4. PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR TYPICAL
 SHOWER PAN SHOWING COMPLIANCE WITH FBC PL 417.5.
 5. RE P1.1:
 A. HER BATHROOM; PER WPB FBC 107.2.1, PROVIDE LOCATION
 AND TYPE OF STACK(S) OR HORIZONTAL BRANCH INTO WHICH
 THE BATHTUB DRAINS AND SHOW THAT THE FIXTURE DRAIN IS
 PROPERLY VENTED. THE CHANGED FOOTPRINT OF WHAT APPEARS
 TO BE A CHASE WALL FOR THE PLUMBING INDICATES THAT THE
 STACK(S) ARE TO BE RELOCATED (OFFSET). PLEASE BE
 ADVISED THAT IF THIS IS A WASTE STACK VENT AS DESCRIBED
 IN FBC PL 913, THAT SUCH STACKS ARE NOT PERMITTED TO
 OFFSET VERTICALLY OR HORIZONTALLY PER FBC PL 913.2 AND
 THE CHASE LAYOUT WILL BE REQUIRED TO ACCOMMODATE THAT
 REQUIREMENT.
 B. STAFF BATHROOM;
 1) PROVIDE LOCATION AND TYPE OF STACK(S) OR HORIZONTAL
 BRANCH INTO WHICH THE LAVATORIES DRAIN. PLEASE BE
 ADVISED THAT IF THIS IS A WASTE STACK VENT AS DESCRIBED
 IN FBC PL 913, THAT SUCH STACKS ARE NOT PERMITTED TO
 RECEIVE THE DISCHARGE OF ANYTHING OTHER THAN FIXTURE
 DRAINS PER FBC PL 913.2. TO COMPLY, EACH LAVATORY WOULD
 HAVE TO CONNECT SEPARATELY TO THE STACK.
 2) PER FBC PL 912.1, THE LAUNDRY TUB SHALL NOT BE USED
 TO WET VENT THE WATER CLOSET. PROVIDE COMPLETE CLARITY
 ON SANITARY ISO AND FLOOR PLAN SHOWING HOW WATER
 CLOSETS ARE CONNECTED TO STACK AND HOW VENTED. SHOW HOW
 LAUNDRY TUB IS TO CONNECT TO STACK WITHOUT IMPACTING
 THE WATER CLOSETS.
 C. LAUNDRY; FLOOR PLAN SHOWS CLOTHES WASHER CONNECTING
 TO STACK AND SANITARY ISO SHOWS CONNECTING TO EXISTING
 HORIZONTAL BRANCH. RECONCILE THE TWO AND IF CONNECTED
 TO STACK, SHOW VENTING COMPLYING WITH FBC CHAPTER 9 ON
 THE SANITARY ISO. DO THESE STACKS EVEN EXIST. ON THE
 DEMO PLAN A-0001, THERE DID NOT APPEAR TO BE ANY
 PLUMBING FIXTURES IN THE VICINITY.
  
 END OF COMMENTS
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  