| 2019-04-30 06:57:36 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 19040009 |
| | ADD: 525 S. FLAGLER DR. SUITE 29 A-B |
| | CONT: CAMBRIDGE CONSTRUCTION LLC |
| | TEL: 561-784-3722 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. APRIL 30/ 2019 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-002 THE PROPOSED FLOOR PLAN UNDER THE |
| | HEADING GENERAL NOTE # 10 THE PLAN STATES NEW STRUCTURE |
| | AND BUILDING ELEMENTS SHALL BE DESIGNED TO RESIST 140 |
| | MPH. THE PLANS SHOULD BE UPDATED TO THE 2017 FBC-B WIND |
| | SPEEDS. SEE 1609.3 ULTIMATE WIND DESIGN AND FIGURE |
| | 1609.3(1), ULTIMATE DESIGN WIND SPEED, VULT FOR RISK |
| | CATEGORY II BUILDINGS AND STRUCTURES. 1609.3.1 WIND |
| | SPEED CONVERSION VULT TO VASD. 170 VULT = 132 VASD |
| | (PRODUCT APPROVALS ARE IN VASD). THIS LOCATION EXPOSURE |
| | D LOCATION. |
| | |
| | 2) SHEET A-002 THE PROPOSED FLOOR PLAN UNDER THE |
| | HEADING GENERAL NOTE # 13 THE PLAN STATES NEW FLOOR |
| | FINISHES. BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION |
| | (FBC-B 2017) FOR TILE, STONE, MARBLE, AND WOOD FLOORING |
| | ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED |
| | FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET |
| | THE QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS |
| | FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED |
| | CEILING. PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE |
| | WITH: |
| | |
| | 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |