2019-08-05 11:29:371) MIRROR SHALL BE MOUNTED 40" TO THE REFLECTIVE
 SURFACE.
  
 2) PIPING INSULATION SHALL BE MIN 1" WALL THICKNESS
  
 3) BACKFLOW FOR COMMERCIAL IRRIGATION SYSTEMS SHALL BE
 RPZ AND LEAD FREE
  
 4) 4 COMPARTMENT SINK SHALL DISCHARGE WITH MIN 3" PIPE
 TO A MIN 3" FLOOR SINK.
  
 5) PLB, GAS, INTERCEPTOR, BACKFLOWS, AND IRRIGATION ALL
 REQUIRE SEPARATE PERMITS.
  
  
 REVIEWED REMOTELY BY T.HUNT
  