Plan Review Notes
Plan Review Notes For Permit 19031394
Permit Number 19031394
Review Stop P
Sequence Number 2
Notes
Date Text
2019-06-26 15:06:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 30A
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMEMTS:
 1. REGARDING ORIGINAL COMMENTS NOTE THAT PER WPB FBC
 107.2.1,THE SUBMITTED GREASE TRAP CALCULATIONS SHALL
 REFER TO RULE 64E-6, FLORIDA ADMINISTRATIVE CODE AND
 NOT TO TABLE 1003.5.1 FLORIDA PLUMBING
 CODE.
 NEW COMMENTS:
 1. P200/DETAIL 7 CREATES A HAZARDOUS CONDITION. IN
 ACCORDANCE WITH FBC PL 608.7, 608.8.1 AND 608.8.2,
 PROVIDE A BACKFLOW PREVENTER FOR THE DEDICATED SUPPLY;
 SIGNAGE AT THE HYDRANT AND EXPOSED PIPING SHALL BE
 COLOR PURPLE AND LABELED. PER WPB FBC 107.2.1, SHOW
 LOCATION OF THIS EXTERIOR POST YARD HYDRANT ON THE
 PLAN.
 2. P001. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THE
 INSTALLATION OF THE INSTANTANEOUS GAS FIRED WATER
 HEATERS. INCLUDE PIPE, VALVES, FITTINGS AND OTHER
 APPURTENANCES IN SCHEMATIC. INCLUDE WATER AND GAS
 SYSTEMS AS WELL AS SEALED COMBUSTION AND DIRECT
 VENT.
 3. P101: TRAP SEAL PROTECTION IS ONLY NOTED FOR FD-1
 FLOOR DRAINS. PROVIDE TRAP SEAL PROTECTION FOR FD-2
 FLOOR DRAINS IN ACCORDANCE WITH FBC PL
 1002.4.
 4. C-600 SHOWS WATER TO THE DUMPSTER ENCLOSURE. IS THIS
 FOR A HOSE BIB? PER WPB FBC 107.2.1, PROVIDE
 DETAIL.
 5. C-601/2? DOMESTIC METER INSTALLATION DETAIL: RP
 SHOWN IN DETAIL; PER WPB FBC 107.2.1, PROVIDE DETAIL OF
 RP SHOWING COMPLIANCE WITH WPB CCCM STD. DETAIL
 WS-11.
 6. C-601: PER WPB FBC 107.2.1, REMOVE DETAIL FOR 5/8? X
 ?? & 1? METER INSTALLATION DETAIL
 6. C-602/IRRIGATION PRESSURE VACUUM BREAKER BACKFLOW
 ASSEMBLY DETAIL: PER WPB CCCM STD DETAIL WS-12, THIS
 DEVICE IS ONLY APPROVED FOR RESIDENTIAL APPLICATION.
 PROVIDE REDUCED PRESSURE BACKFLOW PREVENTER AND PROVIDE
 DETAIL OF RP SHOWING COMPLIANCE WITH WPB CCCM STD
 DETAIL WS-11
 7. C-602: A SEPARATE PERMIT IS REQUIRED FOR
 IRRIGATION
 8. P001: THERE ARE TWO DIFFERENT MODEL NUMBERS LISTED
 IN THE WATER HEATER SCHEDULE. PLEASE CLARIFY PER WPB
 FBC 107.2.1
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  