| 2019-06-26 15:06:49 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 30A |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMEMTS: |
| | 1. REGARDING ORIGINAL COMMENTS NOTE THAT PER WPB FBC |
| | 107.2.1,THE SUBMITTED GREASE TRAP CALCULATIONS SHALL |
| | REFER TO RULE 64E-6, FLORIDA ADMINISTRATIVE CODE AND |
| | NOT TO TABLE 1003.5.1 FLORIDA PLUMBING |
| | CODE. |
| | NEW COMMENTS: |
| | 1. P200/DETAIL 7 CREATES A HAZARDOUS CONDITION. IN |
| | ACCORDANCE WITH FBC PL 608.7, 608.8.1 AND 608.8.2, |
| | PROVIDE A BACKFLOW PREVENTER FOR THE DEDICATED SUPPLY; |
| | SIGNAGE AT THE HYDRANT AND EXPOSED PIPING SHALL BE |
| | COLOR PURPLE AND LABELED. PER WPB FBC 107.2.1, SHOW |
| | LOCATION OF THIS EXTERIOR POST YARD HYDRANT ON THE |
| | PLAN. |
| | 2. P001. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THE |
| | INSTALLATION OF THE INSTANTANEOUS GAS FIRED WATER |
| | HEATERS. INCLUDE PIPE, VALVES, FITTINGS AND OTHER |
| | APPURTENANCES IN SCHEMATIC. INCLUDE WATER AND GAS |
| | SYSTEMS AS WELL AS SEALED COMBUSTION AND DIRECT |
| | VENT. |
| | 3. P101: TRAP SEAL PROTECTION IS ONLY NOTED FOR FD-1 |
| | FLOOR DRAINS. PROVIDE TRAP SEAL PROTECTION FOR FD-2 |
| | FLOOR DRAINS IN ACCORDANCE WITH FBC PL |
| | 1002.4. |
| | 4. C-600 SHOWS WATER TO THE DUMPSTER ENCLOSURE. IS THIS |
| | FOR A HOSE BIB? PER WPB FBC 107.2.1, PROVIDE |
| | DETAIL. |
| | 5. C-601/2? DOMESTIC METER INSTALLATION DETAIL: RP |
| | SHOWN IN DETAIL; PER WPB FBC 107.2.1, PROVIDE DETAIL OF |
| | RP SHOWING COMPLIANCE WITH WPB CCCM STD. DETAIL |
| | WS-11. |
| | 6. C-601: PER WPB FBC 107.2.1, REMOVE DETAIL FOR 5/8? X |
| | ?? & 1? METER INSTALLATION DETAIL |
| | 6. C-602/IRRIGATION PRESSURE VACUUM BREAKER BACKFLOW |
| | ASSEMBLY DETAIL: PER WPB CCCM STD DETAIL WS-12, THIS |
| | DEVICE IS ONLY APPROVED FOR RESIDENTIAL APPLICATION. |
| | PROVIDE REDUCED PRESSURE BACKFLOW PREVENTER AND PROVIDE |
| | DETAIL OF RP SHOWING COMPLIANCE WITH WPB CCCM STD |
| | DETAIL WS-11 |
| | 7. C-602: A SEPARATE PERMIT IS REQUIRED FOR |
| | IRRIGATION |
| | 8. P001: THERE ARE TWO DIFFERENT MODEL NUMBERS LISTED |
| | IN THE WATER HEATER SCHEDULE. PLEASE CLARIFY PER WPB |
| | FBC 107.2.1 |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19010472 2841 VILLAGE BLVD |
| | |
| | |
| | |