Plan Review Notes
Plan Review Notes For Permit 19031394
Permit Number 19031394
Review Stop M
Sequence Number 2
Notes
Date Text
2019-07-01 15:56:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19031394
 7/1/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENTS #6 & #8 FROM THE 1ST REVIEW HAVE ONLY BEEN
 PARTIALLY ADDRESS. SEE COMMENTS AND REMARKS BELOW.
  
 6) SHEET M200: PROVIDE WIND DESIGN CRITERIA AND
 COMPLETE ENGINEERED DETAILS FOR INSTALLATION OF THE
 RTU'S, CONDENSERS, AND FANS- SECTION 301.15 FBC M &
 SECTION 1609 FBC B.
  
 REMARK: THE NARRATIVE RESPONSE FROM THE ARCHITECT
 INDICATES THE ENGINEERING HAS BEEN PROVIDED HOWEVER IT
 IS INCOMPLETE.
 A) THE SUBMITTED PRODUCT APPROVAL FOR THE ROOF STAND IS
 MISSING INSTALLATION PAGES 3-10.
 B) THE PRODUCT APPROVAL FOR THE CURB DOES NOT PROVIDE
 RTU ATTACHMENT.
 C) THE WINDLOAD DESIGN CRITERIA HAS NOT BEEN PROVIDED.
 D) NO FASTENING DETAILS HAVE BEEN PROVIDED FOR
 ATTACHING THE RTU'S TO THE CURBS, OR THE CONDENSER TO
 THE STANDS.
  
 8) M000: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 NEW GAS-FIRED COOKING APPLIANCES AND SUBMIT A PRODUCT
 DATA SHEET FOR EACH APPLIANCE- SECTIONS 304 AND 623.1
 FBC FG.
  
 REMARK: THE REQUESTED CUT SHEETS FOR THE GAS-FIRED
 COOKING APPLIANCES HAVE NOT BEEN PROVIDED.
  
 PLEASE NOTE THAT THE MISSING ITEMS ADDRESSED ABOVE MAY
 BE DEFERRED SUBMITTALS BY REQUEST.
  
 PLEASE NOTE: THE DIGITALLY SIGNED PLANS SHALL ALSO BEAR
 THIS STATEMENT IN ACCORDANCE WITH SECTION 61G15-23.005-
 "THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY
 _________ON DATE________USING A SHA-1 AUTHENTICATION
 CODE." THE CURRENT MECHANICAL PLANS INDICATE THEY ARE
 SIGNED ONLY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  