2019-06-26 15:08:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 96-08
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 GAS COMMEMTS: DENIED
 A SEPARATE GAS PERMIT IS REQUIRED
 1. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THE
 INSTALLATION OF THE INSTANTANEOUS GAS FIRED WATER
 HEATERS. INCLUDE PIPE, VALVES, FITTINGS AND OTHER
 APPURTENANCES IN SCHEMATIC. INCLUDE WATER AND GAS
 SYSTEMS
 2. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR SEALED
 COMBUSTION AND DIRECT VENT SHOWING THE TYPE, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL
 GAS SECS. 502 THRU 505.
 3. P101/PLUMBING KEY NOTE 24; PER WPB FBC 107.2.1,
 PROVIDE SPECIFICATION FOR THE VENTLESS GAS PRESSURE
 REGULATOR INDICATED IN NOTE.
 4. P101/PLUMBING KEY NOTES 13 AND 23; PER WPB FBC
 107.2.1, PROVIDE SPECIFICATION FOR THE GAS PRESSURE
 REGULATOR INDICATED IN NOTE. PR SHALL BE RATED FOR
 OUTDOOR APPLICATION AND SHALL BE NOTED AS SUCH IN THE
 SPECIFICATION.
 5. PER WPB FBC 107.2.1, SUBMIT AN ISOMETRIC DRAWING
 THAT CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF
 PIPE PER FBC FG, SECS. 402.4.1, 402.4.2. SHOW ALL
 SIZING, VALVES AND PRESSURE REGULATORS. EMERGENCY HOOD
 SHUT DOWN SHUT OFF VALVE SHALL BE BELOW THE CEILING.
 THE MANUAL SHUTOFF VALVE SHALL BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. SECS. 10.4, 10.5 OF NFPA
 96-08.
 6. PER WPB FBC 107.2.1, LIST THE BTU LOAD OF EACH
 APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER
 TO THE FBC FG SECS.401.8, 402.2, AND TABLES 402.4 (1)
 THRU 402.4 (37).
 7. PER WPB FBC 107.2.1, CLEARLY INDICATE THE TYPE OF
 GAS (LP OR NATURAL).
 8. PER WPB FBC 107.2.1, SHOW THE DISTANCE FROM THE
 POINT OF DELIVERY, (GAS METER / MP REGULATOR TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND / OR SYSTEM PER
 FBC FG SEC.402.4.1, 402.4.2. NOTE THAT THERE IS A 2PSI
 SYSTEM AND LOW PRESSURE SYSTEM(S). CLEARLY INDICATE THE
 DELIVERY PRESSURE (PSI) OF THE SYSTEM(S) ON THE PLAN.
 9. PER WPB FBC 107.2.1, PROVIDE SIZING OF ALL PIPING
 REFERENCING THE APPLICABLE FBC FG TABLES 402.4 (1) THRU
 402.4 (37). SUBMIT TWO COPIES OF THE APPLICABLE SIZING
 TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON
 THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S)
 FROM FBC FG THAT WERE USED IN THE DESIGN OF THIS GAS
 SYSTEM.
 10. PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR
 MANUAL GAS SHUTOFF VALVES AND THE EMERGENCY HOOD SHUT
 DOWN SHUT OFF VALVE.
 11. PER WPB FBC 107.2.1, PROVIDE DETAIL OF GAS
 CONNECTION TO RTU INCLUDING MP REGULATOR, SHUT OFF
 VALVE, UNION AND DIRT LEG.
 12. PER WPB FBC 107.2.1, PROVIDE DETAIL OF EMERGENCY
 HOOD SHUT DOWN SHUT OFF VALVE, MANUAL SHUTOFF VALVE, MP
 REGULATOR AND UNION. PROVIDE DIRT LEG. COMPLY WITH
 SECS. 10.4, 10.5 OF NFPA 96-08.
 13. PER WPB FBC 107.2.1, PROVIDE DETAIL OF GAS
 CONNECTION TO FS ITEM 11, DEEP FAT FRYER INCLUDING SHUT
 OFF VALVE AND UNION. IF FLEXIBLE CONNECTORS ARE TO BE
 USED, PROVIDE SPECIFICATION.
 14. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC FG SEC. 402.2, AND 301.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC FG 305.1
 15. P001: THERE ARE TWO DIFFERENT MODEL NUMBERS LISTED
 IN THE WATER HEATER SCHEDULE. PLEASE CLARIFY PER WPB
 FBC 107.2.1
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19031394 1345 N CONGRESS AVE
  