| Date |
Text |
| 2019-06-26 15:08:42 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 96-08 |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 2ND REVIEW |
| | GAS COMMEMTS: DENIED |
| | A SEPARATE GAS PERMIT IS REQUIRED |
| | 1. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR THE |
| | INSTALLATION OF THE INSTANTANEOUS GAS FIRED WATER |
| | HEATERS. INCLUDE PIPE, VALVES, FITTINGS AND OTHER |
| | APPURTENANCES IN SCHEMATIC. INCLUDE WATER AND GAS |
| | SYSTEMS |
| | 2. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR SEALED |
| | COMBUSTION AND DIRECT VENT SHOWING THE TYPE, LOCATION, |
| | SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND |
| | ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL |
| | GAS SECS. 502 THRU 505. |
| | 3. P101/PLUMBING KEY NOTE 24; PER WPB FBC 107.2.1, |
| | PROVIDE SPECIFICATION FOR THE VENTLESS GAS PRESSURE |
| | REGULATOR INDICATED IN NOTE. |
| | 4. P101/PLUMBING KEY NOTES 13 AND 23; PER WPB FBC |
| | 107.2.1, PROVIDE SPECIFICATION FOR THE GAS PRESSURE |
| | REGULATOR INDICATED IN NOTE. PR SHALL BE RATED FOR |
| | OUTDOOR APPLICATION AND SHALL BE NOTED AS SUCH IN THE |
| | SPECIFICATION. |
| | 5. PER WPB FBC 107.2.1, SUBMIT AN ISOMETRIC DRAWING |
| | THAT CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF |
| | PIPE PER FBC FG, SECS. 402.4.1, 402.4.2. SHOW ALL |
| | SIZING, VALVES AND PRESSURE REGULATORS. EMERGENCY HOOD |
| | SHUT DOWN SHUT OFF VALVE SHALL BE BELOW THE CEILING. |
| | THE MANUAL SHUTOFF VALVE SHALL BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. SECS. 10.4, 10.5 OF NFPA |
| | 96-08. |
| | 6. PER WPB FBC 107.2.1, LIST THE BTU LOAD OF EACH |
| | APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER |
| | TO THE FBC FG SECS.401.8, 402.2, AND TABLES 402.4 (1) |
| | THRU 402.4 (37). |
| | 7. PER WPB FBC 107.2.1, CLEARLY INDICATE THE TYPE OF |
| | GAS (LP OR NATURAL). |
| | 8. PER WPB FBC 107.2.1, SHOW THE DISTANCE FROM THE |
| | POINT OF DELIVERY, (GAS METER / MP REGULATOR TO THE |
| | MOST REMOTE OUTLET IN THE BUILDING AND / OR SYSTEM PER |
| | FBC FG SEC.402.4.1, 402.4.2. NOTE THAT THERE IS A 2PSI |
| | SYSTEM AND LOW PRESSURE SYSTEM(S). CLEARLY INDICATE THE |
| | DELIVERY PRESSURE (PSI) OF THE SYSTEM(S) ON THE PLAN. |
| | 9. PER WPB FBC 107.2.1, PROVIDE SIZING OF ALL PIPING |
| | REFERENCING THE APPLICABLE FBC FG TABLES 402.4 (1) THRU |
| | 402.4 (37). SUBMIT TWO COPIES OF THE APPLICABLE SIZING |
| | TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON |
| | THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) |
| | FROM FBC FG THAT WERE USED IN THE DESIGN OF THIS GAS |
| | SYSTEM. |
| | 10. PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR |
| | MANUAL GAS SHUTOFF VALVES AND THE EMERGENCY HOOD SHUT |
| | DOWN SHUT OFF VALVE. |
| | 11. PER WPB FBC 107.2.1, PROVIDE DETAIL OF GAS |
| | CONNECTION TO RTU INCLUDING MP REGULATOR, SHUT OFF |
| | VALVE, UNION AND DIRT LEG. |
| | 12. PER WPB FBC 107.2.1, PROVIDE DETAIL OF EMERGENCY |
| | HOOD SHUT DOWN SHUT OFF VALVE, MANUAL SHUTOFF VALVE, MP |
| | REGULATOR AND UNION. PROVIDE DIRT LEG. COMPLY WITH |
| | SECS. 10.4, 10.5 OF NFPA 96-08. |
| | 13. PER WPB FBC 107.2.1, PROVIDE DETAIL OF GAS |
| | CONNECTION TO FS ITEM 11, DEEP FAT FRYER INCLUDING SHUT |
| | OFF VALVE AND UNION. IF FLEXIBLE CONNECTORS ARE TO BE |
| | USED, PROVIDE SPECIFICATION. |
| | 14. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC FG SEC. 402.2, AND 301.3. GAS |
| | APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC FG 305.1 |
| | 15. P001: THERE ARE TWO DIFFERENT MODEL NUMBERS LISTED |
| | IN THE WATER HEATER SCHEDULE. PLEASE CLARIFY PER WPB |
| | FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 19031394 1345 N CONGRESS AVE |
| | |