Plan Review Notes
Plan Review Notes For Permit 19031394
Permit Number 19031394
Review Stop P
Sequence Number 1
Notes
Date Text
2019-04-26 15:57:591ST REVIEW: 19031394
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR
  
 2. SHT. A111 PROVIDE OVERALL DIMENSIONS OF THE
 BATHROOMS TO VERIFY COMPLIANCE WITH FBC ACC 604.3.1,
 606.2
  
 3.WHAT IS THE WH ON THE BACK WALL NEXT TO CO2 IT IS NOT
 CONNECTED WATER SYSTEM PLEASE CLARIFY. PER WPB AMEND TO
 FBC 107.2.1
  
 4. PLEASE PROVIDE WATER ISOMETRIC PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 5. PROVIDE GREASE TRAP SIZING CALCULATIONS. FBC PL
 1003.1
  
 6. SHT. SHT P100 NOTES ON THE PLAN CALLS OUT THE CIVIL
 DRAWING FOR THE SEWER AND GREASE INTERCEPTOR CIVIL
 SHEETS NOT INCUDED IN PLAN SET. PER WPB AMEND TO FBC
 107.2.1
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]