Plan Review Notes
Plan Review Notes For Permit 19031394
Permit Number 19031394
Review Stop M
Sequence Number 1
Notes
Date Text
2019-04-29 10:45:361ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19031394
 4/29/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW RTU'S IN COMPLIANCE WITH SECTION C403.2.1 FBC EC.
  
 2) PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS FOR
 THE O/A INTAKES- SECTION C403.2.4.3 FBC-17 ENERGY
 CONSERVATION.
  
 3) SEPERATE PERMITS ARE REQUIRED FOR THE KITCHEN HOODS,
 FIRE SUPPRESSION SYSTEMS, AND THE WALKIN COOLER AND
 FREEZER- SECTION 107.2.1 WPB. PLEASE PLACE NOTES ON THE
 PLAN ACCORDINGLY.
  
 4) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS
 OF THE RTU'S, MUA, WALKIN CONDENSERS, AND THE GREASE
 EXHAUST AND MAKEUP AIR FANS. PROVIDE CLEARANCE DISTANCE
 MEASUREMENTS FROM EXHAUST AIR OUTLETS TO AIR INTAKES,
 AND DISTANCES OF SERVICEABLE EQUIPMENT TO ROOF EDGES-
 SEE SECTIONS 304.11 & 501.3.1 FBC M.
  
 5) CLARIFY HOW ACCESS TO THE ROOF TO SERVICE EQUIPMENT
 WILL BE PROVIDED- SEE SECTION 306.5 FBC M.
  
 6) SHEET M200: PROVIDE WIND DESIGN CRITERIA AND
 COMPLETE ENGINEERED DETAILS FOR INSTALLATION OF THE
 RTU'S, CONDENSERS, AND FANS- SECTION 301.15 FBC M &
 SECTION 1609 FBC B.
  
 7) M100: PROVIDE A GAS PIPING PLAN FOR THE NEW RTU'S-
 SECTION
  
 8) M000: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 NEW GAS-FIRED COOKING APPLIANCES AND SUBMIT A PRODUCT
 DATA SHEET FOR EACH APPLIANCE- SECTIONS 304 AND 623.1
 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  