Plan Review Notes
Plan Review Notes For Permit 19031394
Permit Number 19031394
Review Stop E
Sequence Number 1
Notes
Date Text
2019-04-26 11:01:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10
 2. SHEET E101, GENERAL NOTE 2 STATES THAT INTERIOR
 LIGHTING WILL BE CONTROLLED BY LOCAL SWITCHES. PROVIDE
 THE ADDITIONAL INTERIOR LIGHTING CONTROLS STIPULATED IN
 THE FBC ENERGY CODE. MANY AREAS DO NOT SHOW THE
 AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 4. BE ADVISED THAT FIRE ALARM, PV SYSTEMS, LOW VOLTAGE
 SYSTEMS, DAS, LIGHTNING PROTECTION, GENERATORS,
 COMMERCIAL HOOD SYSTEMS, WALK IN COOLERS, SIGNS, SITE
 LIGHTING, AND SWIMMING POOLS (WHERE APPLICABLE) ARE NOT
 INCLUDED IN THE SCOPE OF THIS PLAN REVIEW. PROVIDE A
 BLOCK NOTE INDICATING THE REQUIRED SEPARATE PERMITS AND
 PLAN SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB
 FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  