| 2019-04-30 14:00:25 | NEW RESTAURANT (A2 ASSEMBLY) BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | SEC. 107.2.5 CITY AMENDMENTS (SITE PLAN). |
| | SEC. 110.9 CITY AMENDMENTS (IMPACT OF CONSTRUCTION). |
| | |
| | 2- REVISE OCCUPANT LOAD SHOWN ON THE LIFE SAFETY PLAN |
| | AND COVER SHEET |
| | A)NUMBER OF PEOPLE IN KITCHEN AREA IS BASED ON THE |
| | TOTAL GROSS AREA AS REQUIRED BY TABLE 1004.1.2 |
| | FBC-BUILDING. THIS INCLUDES THE WALK-IN FREEZER AND |
| | COOLER. ALSO, NUMBER OF PEOPLE SHOWN ON THE LIFE SAFETY |
| | PLAN DOESN'T MATCH NUMBER SHOWN ON THE COLUMN WHEN |
| | ADDING THE TOTAL NUMBER OF PEOPLE. REVISE AS REQUIRED |
| | TO MATCH. |
| | |
| | B) NUMBER OF PEOPLE ON THE ROUND BOOTH NEEDS TO BE |
| | REVISED CONSIDERING A 24 INCH PER PERSON OF SEATING |
| | LENGTH AS REQUIRED BY SEC. 1004.4 FBC-BUILDING. ALSO, |
| | NEED TO ADD THE ADDITIONAL SPACE SHOWN FOR THE |
| | WHEELCHAIR. |
| | |
| | C) NUMBER OF PEOPLE SHOWN ON THE QUEUE LINE NEEDS TO BE |
| | REVISED. THIS AREA IS MORE THAN 80S.F. TABLE 1004.1.2 |
| | FBC-BUILDING. |
| | |
| | 3- THE BUILDING THERMAL ENVELOPE NEEDS TO BE CLEARLY |
| | DEPICTED ON PLANS AS REQUIRED BY SEC. C103.2.1 |
| | FBC-ENERGY CONSERVATION. ARCHITECTURAL WALL SECTIONS |
| | SHOW FURRING STRIPS ON CMU WALLS UP TO 6 INCHES ABOVE |
| | THE SUSPENDED CEILING. WHAT HAPPENS TO THE REST OF THE |
| | WALL. ARCHITECT TO SHOW COMPLETE THERMAL ENVELOPE AND |
| | SPECIFY R-VALUE OF WALL. COORDINATE WITH ENERGY |
| | CALCULATIONS TO AVOID CONFLICTS/DELAYS. |
| | |
| | 4- ENERGY CALCULATIONS: |
| | A) A/C AREA SPECIFIED ON THE ENERGY CALCULATIONS |
| | DOESN'T MATCH PLANS. REVISE AS REQUIRED TO MATCH. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | B) CEILING R-VALUE INSULATION AND WALL R-VALUE |
| | INSULATION DOESN'T MATCH ARCHITECTURAL PLANS. REVISE |
| | ASD REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | C) BUILDING ADDRESS SHOWN ON THE ENERGY CALCULATIONS IS |
| | INCORRECT. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 5- DOORS AND WINDOWS BUCK DETAILS DON'T PROVIDE |
| | SPECIFICATIONS FOR THE FASTENING OF THE STRUCTURAL |
| | BUCK. PROVIDE COMPLETE SPECIFICATIONS. SEC. 1609.1 |
| | FBC-BUILDING. |
| | |
| | 6- PRODUCT APPROVALS SUBMITTED:FAC 61G20-3.001 |
| | A) PROVIDE THE FLORIDA PRODUCT APPROVAL COVER PAGE FOR |
| | EACH FLORIDA PRODUCT APPROVAL SUBMITTED. THIS IS |
| | REQUIRED BECAUSE THE COVER PAGE SHOWS THE STATUS OF THE |
| | PRODUCT APPROVAL AND THE CODE IN EFFECT. |
| | |
| | B) PROVIDE LATEST REVISION OF FLORIDA PRODUCT APPROVAL |
| | FOR: |
| | (1)FL1559. CURRENT REVISION IS R-12 NOT R-11. |
| | (2) FL8787. CURRENT REVISION IS R-9 NOT R-8. |
| | (3)FL4553. CURRENT REVISION IS R-11 NOT R-10. |
| | |
| | |
| | C) FLAT ROOF MEMBRANE ROOFING FLORIDA PRODUCT APPROVAL |
| | FL1559-R12: CLEARLY MARK WHICH APPROVED ASSEMBLY IS |
| | GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES. NOTE: RAS 117 CALCULATIONS NEED TO BE |
| | SIGNED AND SEALED AS REQUIRED BY CHAPTER 471 F.S. WHEN |
| | SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. |
| | |
| | 7- CONTRACTOR TO CONTACT KEN CONRAD (CHIEF BUILDING |
| | INSPECTOR ) FOR COORDINATION OF SPECIAL INSPECTIONS |
| | LISTED ON SHEET S002. |
| | KEN CONRAD |
| | CHIEF BUILDING INSPECTOR |
| | DEVELOPMENT SERVICES |
| | BUILDING INSPECTIONS |
| | 401 CLEMATIS STREET |
| | P.O.BOX 3366 |
| | WEST PALM BEACH, FL 33402 |
| | PHONE: 805-6666 EXT: 6666 |
| | FAX: 659-8026 |
| | E-MAIL: [email protected] |
| | SERVING SINCE SEP 30, 2001 |
| | EMPLOYMENT CATEGORY: FR |
| | SUPERVISOR: GATHRIGHT, RICHARD EUGENE JR |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |