| 2019-04-16 07:55:37 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE SANITARY ISOMETRIC HAS THE FOLLOWING CODE |
| | VIOLATIONS. |
| | A) THE FIXTURE BRANCH FOR THE WC SHALL BE MIN OF 3" PER |
| | FBC PL 420.4 |
| | B) THE FIXTURE BRANCHES FOR ALL THE FIXTURES IN THE |
| | BATHROOM GROUP SHALL CONNECT TO THE HORIZONTAL WET VENT |
| | INDIVIDUALLY THEY APPEAR TO BE CONNECTED TO THE |
| | VERTICAL VENT FOR THE LAVATORY. PER FBC PL 912.1.1 |
| | C) THE KITCHEN SINK SHALL NOT DISCHARGE TO THE BATHROOM |
| | GROUP IT SHALL CONNECT TO BUILDING DRAIN DOWN STREAM |
| | FROM ALL THE BATHROOM GROUP. PER FBC PL 912.1.1 |
| | D) THE WASHING MACHINE IS MISSING FROM THE SANITARY |
| | ISOMETRIC. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |