| 2019-04-20 08:16:15 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SHOW CONDUCTOR SIZE FROM RISER TO METER-CAN FBC |
| | 107.2.1 |
| | |
| | 2. SHOW CONDUCTOR SIZE FROM METER-CAN TO MAIN-BREAKER |
| | PANEL. FBC 107.2.1 |
| | |
| | 3. PROVIDE ACCUATE LOAD CALCULATION. OCP FOR COOKTOP IS |
| | SHOWN AS 40AMPS BUT ONLY 1200 WATTS SHOWN IN LOAD |
| | CALCULATION. FBC 107.2.1 NEC 220 |
| | |
| | 4. SHOW CIRCUITS BEING FED FROM MAIN-BREAKER PANEL (IF |
| | ANY). FBC 107.2.1 |
| | |
| | 5. SHOW AFCI PROTECTION FOR KITCHEN LIGHTING AND |
| | KITCHEN COUNTERTOP RECEPTACLES. NEC 210.12 |
| | |
| | 6.SHOW AFCI PROTECTION FOR DISHWASHER AND DISPOSAL. NEC |
| | 210.12 |
| | |
| | 7. SHOW GFCI PROTECTION FOR DISHWASHER. NEC 210.8D |
| | |
| | 8. RECEPTACLE REQUIRED ON ISLAND. RECEPTACLE SHOWN IS |
| | NOT CODE COMPLIANT. OVERHANG OF COUNTERTOP IS MORE THAN |
| | 6''. PLEASE SEE NEC 210.52C5 (EXCEPTION TO #5) |
| | |
| | 9. SMOKE ALARM REQUIRED OUTSIDE OF NEW BEDROOM. FBC |
| | 314&315 |
| | |
| | 10. SHOW AFCI PROTECTION FOR RECEPTACLES IN |
| | LAUNDRY/UTILITY ROOM. NEC 210.12 |
| | |
| | 11. NOTE ON PLANS STATES 50% OF ALL LIGHTING WILL BE |
| | ENERGY EFFICIENT. PLEASE SEE FBC EC R404.1. MINIMUM IS |
| | 75% |
| | |
| | PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |
| | |