Plan Review Notes
Plan Review Notes For Permit 19031377
Permit Number 19031377
Review Stop M
Sequence Number 1
Notes
Date Text
2019-04-15 15:20:12MECHANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SPECIFY EQUIPMENT TO BE INSTALLED. LIST EQUIPMENT ON
 ENERGY SUBMITTAL AND PLANS.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 2. PROVIDE EQUIPMENT SIZING.
 M1401.3 EQUIPMENT AND APPLIANCE SIZING.
 HEATING AND COOLING EQUIPMENT AND APPLIANCES SHALL BE
 SIZED IN ACCORDANCE WITH ACCA MANUAL S OR OTHER
 APPROVED SIZING METHODOLOGIES BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
  
 3. PROVIDE DETAIL FOR C/U ANCHORAGE.
 M1307.2 ANCHORAGE OF APPLIANCES.
 APPLIANCES DESIGNED TO BE FIXED IN POSITION SHALL BE
 FASTENED OR ANCHORED IN AN APPROVED MANNER. IN SEISMIC
 DESIGN CATEGORIES D0, D1 AND D2, AND IN TOWNHOUSES IN
 SEISMIC DESIGN CATEGORY C, WATER HEATERS AND THERMAL
 STORAGE UNITS SHALL BE ANCHORED OR STRAPPED TO RESIST
 HORIZONTAL DISPLACEMENT CAUSED BY EARTHQUAKE MOTION IN
 ACCORDANCE WITH ONE OF THE FOLLOWING:
 1. 1. ANCHORAGE AND STRAPPING SHALL BE DESIGNED TO
 RESIST A HORIZONTAL FORCE EQUAL TO ONE-THIRD OF THE
 OPERATING WEIGHT OF THE WATER HEATER STORAGE TANK,
 ACTING IN ANY HORIZONTAL DIRECTION. STRAPPING SHALL BE
 AT POINTS WITHIN THE UPPER ONE-THIRD AND LOVER
 ONE-THIRD OF THE APPLIANCE?S VERTICAL DIMENSIONS. AT
 THE LOWER POINT, THE STRAPPING SHALL MAINTAIN A MINIMUM
 DISTANCE OF 4 INCHES (102 MM) ABOVE THE CONTROLS.
 2. 2. THE ANCHORAGE STRAPPING SHALL BE IN ACCORDANCE
 WITH THE APPLIANCE MANUFACTURER?S RECOMMENDATIONS.
  
 4. PROVIDE DETAIL FOR LOCKING SERVICE PORTS.
 M1411.8 LOCKING ACCESS PORT CAPS.
 REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL
 BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR
 SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED
 ACCESS.
 EXCEPTION: NO LOCKING-TYPE TAMPER-RESISTANT CAPS ARE
 REQUIRED IF PORTS ARE LOCATED INSIDE THE CONDENSING
 UNIT CABINET.
  
 5. PROVIDE CFM OF EXHAUST FANS.
 6. PROVIDE DETAIL OF EXHAUST FAN DISCHARGE TO EXTERIOR.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  