| 2019-04-16 07:14:30 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | 1&2 FAMILY PLANS EXAMINER, SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | THE FOLLOWING REVIEW COMMENTS APPLY TO THE MAIN HOUSE |
| | AND CABANA. A NOTE HAS BEEN PROVIDED WHERE THE COMMENT |
| | APPLIES ONLY TO ONE STRUCTURE. |
| | |
| | 1. PROVIDE AIC CALCULATIONS |
| | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3 |
| | |
| | 2. PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE |
| | MARKED WITH THE AIC RATING. |
| | PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED |
| | WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT |
| | AVAILABLE PER NEC 110.24 & FBC RE E3606.4 |
| | PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. NEC |
| | 110.3, 110.9; FBC RE E3606.4 |
| | |
| | 3. PROVIDE ACCURATE LOAD CALCULATIONS FOR EACH PANEL |
| | SEPERATELY, INCLUDING ALL LOADS. NEC 220; FBC RE |
| | E3602.2 |
| | 3A. MAIN HOUSE CALCULATIONS - |
| | 3B. CABANA CALCULATIONS - |
| | 3C. COMBINATION CALCULATIONS - PROVIDED |
| | |
| | 4. HOUSE ONLY COMMENT - PLAN INDICATES A FPL METER |
| | COMBO AND A 150 AMP PANEL LOCATED IN FOYER. RISER |
| | DIAGRAHM INDICATES A SEPERATE METER CAN WITH A 200 AMP |
| | PANEL WITH A MCB. IF METER COMBO IS UTILIZED THEN THE |
| | DETAIL SHOWING A 2 INCH CONDUIT WITH 3-#3/0 CONDUCTORS |
| | WITH A #6 GRND. ( THIS WOULD BE AN INTERNAL CONNECTION) |
| | AND THE 150 AMP PANEL IN THE FOYER NEEDS TO BE REMOVED. |
| | PLEASE CLARIFY. |
| | |
| | 5. INDICATE ON PLAN THE TYPE OF GROUND TO BE USED AT |
| | EACH STRUCTURE. (I.E. GROUND RODS, CONCRETE ENCASED |
| | STEEL RE-INFORCING, WATER PIPES, ETC.) |
| | A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE |
| | ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND |
| | CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF |
| | GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC |
| | RE E3607.3 |
| | |
| | 6. IDENTIFY INTERSYSTEM BONDING TERMINAL AT EACH |
| | SERVICE. |
| | PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| | |
| | 7. GROUNDING ELECTRODE SHALL BE SIZED PER TABLE |
| | E3603.4. THIS IS IN REFERENCE TO THE DETAIL SHOWING |
| | SEPERATE METER AND SERVICE. #6 GROUND WIRE IS |
| | UNDERSIZED FOR 3-#3/0 UNGROUNDED CONDUCTORS. |
| | |
| | 8. CABANA ONLY COMMENT - PROVIDE SERVICE OUTLET FOR |
| | MINI-SPLIT OUTDOOR C/U UNIT. |
| | E3901.12 HVAC OUTLET. |
| | A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING |
| | AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE |
| | LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM) |
| | OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION |
| | EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED |
| | TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING |
| | MEANS. (210.63) |
| | |
| | 9. HOUSE ONLY COMMENT - LAUNDRY ROOM OUTLET SHALL BE |
| | GFCI PROTECTED. |
| | E3902.9 LAUNDRY AREAS. |
| | 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES |
| | INSTALLED IN LAUNDRY AREAS SHALL HAVE GROUND-FAULT |
| | CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL. |
| | [210.8(A)(9)] E3902.16. |
| | |
| | 10. PROVIDE ARC FAULT CIRCUT PROTECTION PER E3902.16 |
| | FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| | ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| | 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS, |
| | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED |
| | BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER |
| | INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. |
| | |
| | 11. PROVIDE THE FOLLOWING STATEMENT ON PLAN FOR |
| | PERMENTELY INSTALLED LUMINAIRES: |
| | PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. |
| | FBC EC C405.1, R404.1 |
| | |
| | 12. EXHAUST FAN SYMBOL MISSING FROM LEGEND. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 13. STATE CFM FOR EACH EXHAUST FANS. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |