2019-04-16 07:14:30BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THE FOLLOWING REVIEW COMMENTS APPLY TO THE MAIN HOUSE
 AND CABANA. A NOTE HAS BEEN PROVIDED WHERE THE COMMENT
 APPLIES ONLY TO ONE STRUCTURE.
  
 1. PROVIDE AIC CALCULATIONS
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3404.2 & FBC RE E3606.3
  
 2. PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE
 MARKED WITH THE AIC RATING.
 PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED
 WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24 & FBC RE E3606.4
 PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. NEC
 110.3, 110.9; FBC RE E3606.4
  
 3. PROVIDE ACCURATE LOAD CALCULATIONS FOR EACH PANEL
 SEPERATELY, INCLUDING ALL LOADS. NEC 220; FBC RE
 E3602.2
 3A. MAIN HOUSE CALCULATIONS -
 3B. CABANA CALCULATIONS -
 3C. COMBINATION CALCULATIONS - PROVIDED
  
 4. HOUSE ONLY COMMENT - PLAN INDICATES A FPL METER
 COMBO AND A 150 AMP PANEL LOCATED IN FOYER. RISER
 DIAGRAHM INDICATES A SEPERATE METER CAN WITH A 200 AMP
 PANEL WITH A MCB. IF METER COMBO IS UTILIZED THEN THE
 DETAIL SHOWING A 2 INCH CONDUIT WITH 3-#3/0 CONDUCTORS
 WITH A #6 GRND. ( THIS WOULD BE AN INTERNAL CONNECTION)
 AND THE 150 AMP PANEL IN THE FOYER NEEDS TO BE REMOVED.
 PLEASE CLARIFY.
  
 5. INDICATE ON PLAN THE TYPE OF GROUND TO BE USED AT
 EACH STRUCTURE. (I.E. GROUND RODS, CONCRETE ENCASED
 STEEL RE-INFORCING, WATER PIPES, ETC.)
 A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC
 RE E3607.3
  
 6. IDENTIFY INTERSYSTEM BONDING TERMINAL AT EACH
 SERVICE.
 PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
 7. GROUNDING ELECTRODE SHALL BE SIZED PER TABLE
 E3603.4. THIS IS IN REFERENCE TO THE DETAIL SHOWING
 SEPERATE METER AND SERVICE. #6 GROUND WIRE IS
 UNDERSIZED FOR 3-#3/0 UNGROUNDED CONDUCTORS.
  
 8. CABANA ONLY COMMENT - PROVIDE SERVICE OUTLET FOR
 MINI-SPLIT OUTDOOR C/U UNIT.
 E3901.12 HVAC OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING, AIR-CONDITIONING
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 25 FEET (7620 MM)
 OF THE HEATING, AIR-CONDITIONING AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL NOT BE CONNECTED
 TO THE LOAD SIDE OF THE HVAC EQUIPMENT DISCONNECTING
 MEANS. (210.63)
  
 9. HOUSE ONLY COMMENT - LAUNDRY ROOM OUTLET SHALL BE
 GFCI PROTECTED.
 E3902.9 LAUNDRY AREAS.
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 INSTALLED IN LAUNDRY AREAS SHALL HAVE GROUND-FAULT
 CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL.
 [210.8(A)(9)] E3902.16.
  
 10. PROVIDE ARC FAULT CIRCUT PROTECTION PER E3902.16
 FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
  
 11. PROVIDE THE FOLLOWING STATEMENT ON PLAN FOR
 PERMENTELY INSTALLED LUMINAIRES:
 PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
  
 12. EXHAUST FAN SYMBOL MISSING FROM LEGEND. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 13. STATE CFM FOR EACH EXHAUST FANS. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  
  
  